77
Installation instructions geoTHERM VWS/VWW 0020057444_01
Description
Unit
VWS 61/2
VWS 81/2
VWS 101/2
VWS 141/2
VWS 171/2
Internal sound level
dbA
46
48
50
52
53
Conforms to safety regulations
-
CE mark
Low Voltage Directive 73/23/EWG
EMC Directive 89/336/EWG
EN 60335
ISO 5149
Table 13.1 Technical data - VWS (cont)
a
Caution!
R 407 C is a chlorine-free coolant which
does not affect the ozone layer. Never-
theless, any servicing work on the cool-
ant circuit should only be carried out by
authorised specialists.
13.2
Technical data - VWW
Description
Unit
VWW 61/2
VWW 81/2
VWW 101/2
VWW 141/2
VWW 171/2
Article number
-
0010002789
0010002790
0010002791
0010002792
0010002793
Height without connections
Width
Depth without pillars
Depth with pillars
mm
mm
mm
mm
1200
600
650
840
Weight
- with packaging
- without packaging
- ready for operation
kg
kg
kg
154
139
145
161
146
153
164
149
157
182
174
186
189
174
186
Rated voltage
- Heating circuit/Compressor
- Control circuit
- Auxiliary heating
-
3/N/PE 400 V 50 Hz
1/N/PE 230 V 50 Hz
3/N/PE 400 V 50 Hz
Fuse, slow-blow
A
3 x 16
3 x 16
3 x 16
3 x 25
3 x 25
Start-up current
- without start-up current limiter
- with start-up current limiter
A
A
26
< 16
40
< 16
46
< 16
64
< 25
74
< 25
Electrical power consumption:
- min. for W10W35
- max. for W20W60
- Auxiliary heating
kW
kW
kW
1,5
3.1
6
2.1
3.8
6
2.5
4.9
6
3.5
6.8
6
4.3
7.7
6
EN 60529 level of protection
-
IP 20
Hydraulic connections
- Heating circuit flow and return
- Heat source flow and return
mm
mm
G 1 1/4", diameter 28
G 1 1/4", diameter 28
Heat source circuit
- max. operating pressure
- min. inlet temperature
- max. inlet temperature
MPa (bar)
°C
°C
0.3 (3)
4
20
- Nominal flow rate dT 3K
- Residual head dT 3K
- Nominal flow rate dT 4K
- Residual head dT 4K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
1816
-
1362
-
-
2604
-
1953
-
-
3045
-
2284
-
-
4267
-
3200
-
-
4983
-
3737
-
-
CH circuit
- max. operating pressure
- min. flow temperature
- max. flow temperature
MPa (bar)
°C
°C
0.3 (3)
25
62
- Nominal flow rate dT 5K
- Residual head dT 5K
- Nominal flow rate dT 10K
- Residual head dT 10K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
1404
297
728
450
93
1998
180
993
418
93
2371
97
1229
382
93
3370
92
1724
469
132
4173
0
2050
516
205
Table 13.2 Technical data - VWW
Technical data 13
Содержание geoTHERM VWS Series
Страница 1: ...For the heating engineer Installation instructions geoTHERM Heat pump VWS VWW GB ...
Страница 90: ......