Installation instructions geoTHERM VWS/VWW 0020057444_01
28
6.4.3 Dual circuit feed, special tariff
(Electroplan 3)
PE
S
S A Z
N
L3 L2 L1
N
PE
L3 L2 L1
L3
L3
L3 L2 L1
N
N N
N
PE
PE
PE L2
L1
L3
N
(VWW)
1
2
3
400 V / 50 Hz
230 V / 50 Hz
+
+
Fig. 6.4 Dual circuit feed, special tariff
Key to Fig. 6.4
Pump
Compressor
Controller
Auxiliary heater
Heat source circuit
In this instance the heat pump is operated on two tariffs
(two consumer meters). A permanent supply (
2
) for the
secondary consumers (circulation pumps, controller,
etc.)
must be ensured via a meter. The
low tariff sup-
ply (1) for the compressor and the auxiliary heating
is
effected via a second meter and can be interrupted by
the power company at peak times.
• Remove the jumpers (dashed lines,
3
).
• Connect the permanent power supply to the controller
mains feed (
2
).
• Connect the low tariff power supply to the low tariff
mains feed (
1
).
• Connect the ripple control signal relay to terminal 13,
"EVU" (see Fig 6.6), if required by the power compa-
ny. The heat pump is blocked with this signal when the
contact is closed.
You will find an overview of the complete wiring dia-
gram in the appendix.
6 Electrical installation