Appendix
0020213394_01 flexoTHERM exclusive Installation and maintenance instructions
71
VWF 57/4
VWF 87/4
VWF 117/4
VWF 157/4
VWF 197/4
Heat source module
VWW 11/4 SI
VWW 11/4 SI
VWW 11/4 SI
VWW 19/4 SI
VWW 19/4 SI
Heating output W10/W35
Δ
T 5 K
6.40 kW
10.00 kW
12.90 kW
16.80 kW
23.00 kW
Power consumption W10/W35
Δ
T 5 K
1.40 kW
1.90 kW
2.40 kW
3.10 kW
4.40 kW
Output figure W10/W35
Δ
T 5 K/coefficient
of performance EN 14511
4.80
5.20
5.10
5.40
5.20
Heating output W10/W45
Δ
T 5 K
6.30 kW
10.10 kW
12.90 kW
16.60 kW
23.60 kW
Power consumption W10/W45
Δ
T 5 K
1.70 kW
2.50 kW
3.10 kW
4.00 kW
5.60 kW
Output figure W10/W45
Δ
T 5 K/coefficient
of performance EN 14511
3.70
4.10
4.00
4.20
4.10
Heating output W10/W55
Δ
T 8 K
6.30 kW
10.30 kW
13.30 kW
17.10 kW
23.80 kW
Power consumption W10/W55
Δ
T 8 K
2.10 kW
3.00 kW
3.90 kW
4.80 kW
6.80 kW
Output figure W10/W55
Δ
T 8 K/coefficient
of performance EN 14511
3.00
3.50
3.30
3.60
3.50
Sound power level W10/W35
EN 12102/EN 14511 L
WI
in heating mode
41.2 dB(A)
47.9 dB(A)
45.0 dB(A)
49.9 dB(A)
50.6 dB(A)
Sound power level W10/W45
EN 12102/EN 14511 L
WI
in heating mode
40.9 dB(A)
50.3 dB(A)
47.8 dB(A)
48.0 dB(A)
47.8 dB(A)
Sound power level W10/W55
EN 12102/EN 14511 L
WI
in heating mode
41.8 dB(A)
53.8 dB(A)
47.6 dB(A)
49.1 dB(A)
46.4 dB(A)
Application limits for the heat pump: Heating (heat source = groundwater)
–
At the same volume flow rates in the heating circuit (
Δ
T 5 K or
Δ
T 8 K) and the groundwater circuit (
Δ
T 3 K) as for the
nominal heat output test under standard nominal conditions. Operation of the pump outside the application limits results
in the heat pump being switched off by the internal control and safety devices.
–
Application limits for the heat pump: Heating (Groundwater heat source):
–
W15/W65
–
W25/W59
–
W25/W25
–
W10/W25
–
W10/W65