Appendix
0020213394_01 flexoTHERM exclusive Installation and maintenance instructions
43
Setting level
Values
Unit
Increment, select, ex-
planation
Default setting
Setting
Min.
Max.
T.105 Air inlet temp. Fan unit 1:
(only for air/brine environment
circuit type)
−
40
90
℃
0.1
T.106 Brine outlet temp. Fan unit
1: (only for air/brine environment
circuit type)
−
40
90
℃
0.1
T.107 Safety cut-out Fan unit 1:
(only for air/brine environment
circuit type)
Closed
Open
Closed, Open
Closed
T.108 Air inlet temp. Fan unit 2
(only for air/brine environment
circuit type)
−
40
90
℃
0.1
T.109 Brine outlet temp. Fan unit
2 (only for air/brine environment
circuit type)
−
40
90
℃
0.1
T.110 Safety cut-out Fan unit 2
(only for air/brine environment
circuit type)
Closed
Open
Closed, Open
Closed
Refrigeration circuit sensors
T.121 Compressor outlet temper-
ature
−
40
135
℃
0.1
T.122 Compressor inlet temper-
ature
−
40
90
℃
0.1
T.123 EEV-VI inlet temperature
−
40
90
℃
0.1
T.124 EEV-VI outlet temperature
−
40
90
℃
0.1
T.127 High pressure
0
47
bar (abs)
0.1
T.128 Condensation temperature
−
40
70
℃
0.1
T.129 Low pressure
0
47
bar (abs)
0.1
T.130 Evaporation temperature
−
40
90
℃
0.1
T.131 Superheating target value
−
40
90
K
0.1
T.132 Superheating actual value
−
40
90
K
0.1
to 20 K are normal op-
erating parameters
T.134 High-pressure switch
Closed
Open
Closed, Open
Closed
T.135 Temperature switch: Com-
pressor outlet
Closed
Open
Closed, Open
Closed
Further sensors
T.146 Outside temperature
−
40
90
℃
0.1
T.147 DCF status
Current value
No DCF signal
Validate DCF signal
Valid DCF signal
T.148 System temperature
−
40
90
℃
0.1
T.149 MPI input
Closed
Open
Closed, Open
Open
Installer level
→
Configuration
→
Language
Current language
Languages available for
selection
02 English
Contact details, Telephone num-
ber
Phone number
0 - 9
Compressor starts at
−
999
0
°min
1
−
60
Max. return temp.
30
70
℃
1
70
Comp. hysteresis
3
15
1
7
Max. rem. feed head
200
1000
mbar
10
1000
Conf. heat. build. pump
Auto
100
%
1
Auto
1)
See overview of fault codes