68 • vacon
CABLING AND CONNECTIONS
6
6.2.1.1
Control cables
The control cables shall be at least 0.0008 in
2
screened multicore cables, see Table 6-1. The maximum
terminal wire size is 0.004 in
2
for the relay terminals and 0.002 in
2
for other terminals.
Find the tightening torques of the option board terminals in Table below.
Terminal
screw
Tightening torque
Nm
lb-in.
Relay and
thermistor
terminals
(screw M3)
0.5
4.5
Other terminals
(screw M2.6)
0.2
1.8
Table 6-8. Tightening torques of terminals
6.2.1.2
Galvanic isolation barriers
The control connections are isolated from the mains potential and the GND terminals are permanently
connected to ground. See Figure 6-28.
The digital inputs are galvanically isolated from the I/O ground. The relay outputs are additionally double-
isolated from each other at 300VAC (EN-50178).