INSTALLATION
vacon • 37
5
Type
Cooling air required
CFM (cubic feet per minute, ft
3
/min)
0004—0012 NXS2
0003—0012 NX_5
41.2
0017—0031 NXS2
0016—0031 NX_5
0004—0013 NX_6
112
0048—0061 NXS2
0038—0061 NX_5
0018—0034 NX_6
112
0075—0114 NXS2
0072—0105 NX_5
0041—0052 NX_6
250
0140—0205 NXS2
0140—0205 NX_5
0062—0100 NX_6
383
0261—0300 NXS2
0261—0300 NX_5
0125—0208 NX_6
765
Table 5-11. Required cooling air