100 • vacon
CONTROL KEYPAD
7
Default page in the operating menu (P6.6.2)
Here you can set the location (page) in the
Operating menu
(in special applications only) to which the
display automatically moves as the set
Timeout time
(see below) has expired or as the power is switched
on to the keypad. See setting of Default page above.
Timeout time (P6.6.3)
The Timeout time setting defines the time after which the keypad display returns to the Default page
(P6.6.1) see above.
Move to the Edit menu by pressing the
Menu button right
. Set the timeout time you want and confirm the
change with the
Enter button
. You can return to the previous step anytime by pushing the
Menu button left
.
Figure 7-20. Timeout time setting
Note: If the
Default page
value is 0 the
Timeout time
setting has no effect.
Contrast adjustment (P6.6.4)
In case the display is unclear you can adjust its contrast through the same procedure as that for the
timeout time setting (see above).
Backlight time (P6.6.5)
Giving a value for the
Backlight time
, you can determine how long the backlight stays on before going out.
You can select here any time between 1 and 65535 minutes or
'Forever'
. For the value setting procedure
see Timeout time (P6.6.3).
7.3.6.7
Hardware settings
NOTE: The
Hardware settings submenu
is protected with a password (see chapter Password (S6.5.1)).
Store the password in a safe place!
In the
Hardware settings submenu
(S6.7) under the
System menu
you can further control some functions
of the hardware in your AC drive. The functions available in this menu are
Internal brake resistor
connection, Fan control, HMI acknowledge timeout and HMI retry.
Internal brake resistor connection (P6.7.1)
With this function you can tell the AC drive, whether the internal brake resistor is connected or not. If you
have ordered the AC drive with an internal brake resistor, the default value of this parameter is
Connected.
However, if it is necessary to increase braking capacity by installing an external brake resistor, or if the
internal brake resistor is disconnected for another reason, it is advisable to change the value of this
function to
Not conn.
in order to avoid unnecessary fault trips.
Enter the edit mode by pushing the
Menu button right
. Use the
Browser buttons
to change the internal
brake resistor status. Accept the change with the
Enter button
or return to the previous level with the
Menu button left
.
90 s
READY
RE ADY
READY
90 s.
enter
60 s.
Timeout time
Timeout time
Timeout time
CANC EL
CONFIRM CHANGE