78 • vacon
CONTROL KEYPAD
7
7.3.1
Monitoring menu (M1)
You can enter the Monitoring menu from the Main menu by pushing the
Menu button right
when the
location indication M1 is visible on the first line of the display. How to browse through the monitored values
is presented in Figure 7-4.
The monitored signals carry the indication V#.# and they are listed in Table 7-1. The values are updated
once every 0.3 seconds.
This menu is meant only for signal checking. The values cannot be altered here. For changing values of
parameters see Chapter 7.3.2.
Figure 7-4. Monitoring menu
Code
Signal name
Unit
Description
V1.1
Output frequency
Hz
Frequency to the motor
V1.2
Frequency reference
Hz
V1.3
Motor speed
rpm
Calculated motor speed
V1.4
Motor current
A
Measured motor current
V1.5
Motor torque
%
Calculated motor shaft torque
V1.6
Motor power
%
Calculated motor shaft power
V1.7
Motor voltage
V
Calculated motor voltage
V1.8
DC-link voltage
V
Measured DC-link voltage
V1.9
Unit temperature
ºF
Heat sink temperature
V1.10
Motor temperature
%
Calculated motor temperature. See All in One
application manual.
V1.11
Voltage input
V
AI1*
V1.12
Current input
mA
AI2*
V1.13
DIN1, DIN2, DIN3
Digital input statuses
V1.14
DIN4, DIN5, DIN6
Digital input statuses
V1.15
DO1, RO1, RO2
Digital and relay output statuses
V1.16
Analogue output
current
mA
AO1
M1.17
Multimonitoring items
Displays three selectable monitoring values. See
chapter 7.3.6.5.
Table 7-1. Monitored signals
* If the unit is supplied with +24V only (for control board power-up) this value is not reliable.
The All in One applications embody more monitoring values.
V1 V14
READY
Local
13.95 Hz
READY
Local
13.95 Hz
R EADY
Loca l
RUN
RUN
RUN
Monitor
Output frequency
FreqReference
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]