background image

vacon  nx

ac drives

user manual

®

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание NX_ 0003 5

Страница 1: ...vacon nx ac drives user manual Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 2: ...tion you want to use and confirm by pressing the Enter button If the Start Up wizard is not active follow the instructions 7a and 7b 7a Select the language of the keypad from the Menu M6 page 6 1 Inst...

Страница 3: ...UAL INDEX 1 SAFETY 2 EU DIRECTIVE 3 RECEIPT OF DELIVERY 4 TECHNICAL DATA 5 INSTALLATION 6 CABLING AND CONNECTIONS 7 CONTROL KEYPAD 8 COMMISSIONING 9 FAULT TRACING Phone 800 894 0412 Fax 888 723 4773 W...

Страница 4: ...ble If you have the electronic version at your disposal you will be able to benefit from the following features The manual contains several links and cross references to other locations in the manual...

Страница 5: ..._5 Mains voltage 380 500 V 19 4 2 2 Vacon NX_6 Mains voltage 525 690 V 20 4 2 3 Vacon NX_2 Mains voltage 208 240 V 21 4 3 Brake resistor ratings 22 4 4 Technical data 24 5 INSTALLATION 26 5 1 Mounting...

Страница 6: ...en red 74 7 1 4 Text lines 74 7 2 Keypad push buttons 75 7 2 1 Button descriptions 75 7 3 Navigation on the control keypad 76 7 3 1 Monitoring menu M1 78 7 3 2 Parameter menu M2 79 7 3 3 Keypad contro...

Страница 7: ...rive 9 Do not touch the components on the circuit boards Static voltage discharge may damage the components 1 2 Safety instructions 1 The components of the power unit of the AC drive are live when Vac...

Страница 8: ...any case be not less than 0 001 in2 if mechanical protection is provided or O 01 in2 if mechanical protection is not provided The earth fault protection inside the AC drive protects only the converte...

Страница 9: ...makes the EMC requirements of customers different As far as the immunity is concerned all Vacon NX_ AC drives are designed to fulfil even the strictest requirements while as regards the emission leve...

Страница 10: ...Vacon NX_ AC drive from class H or L to class T please refer to the instructions given in Chapter 6 1 3 2 2 3 1 Environment definitions in product standard EN 61800 3 2004 First environment Environme...

Страница 11: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 12: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 13: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 14: ...c B no local control keypad F dummy keypad G graphic display Enclosure class 0 IP00 FR9 only 2 IP21 NEMA 1 3 IP21 NEMA 1 cabinet mounted 5 IP54 NEMA 12 7 IP54 NEMA 12 EMC emission level C fulfils requ...

Страница 15: ...Check operation of cooling fan check for cor rosion on terminals busbars and other surfaces Check door filters in case of cabinet installation 5 7 years Change cooling fans main fan internal NEMA12 f...

Страница 16: ...eration outside the rated specifications Neither can the manufacturer be held responsible for consequential damages The Manufacturer s time of warranty is 18 months from the delivery or 12 months from...

Страница 17: ...rols the motor basing on the information it receives through measurements parameter settings control I O and control keypad The motor and application control block controls the motor control ASIC whic...

Страница 18: ...on are easy to use If a more versatile interface or parameters are required a more suitable application can be chosen from the All in One Application Package See the All in One Application Manual for...

Страница 19: ...5 7x15 4x8 4 17 86 NX_ 0031 5 31 34 23 35 46 20 15 25 20 FR5 5 7x15 4x8 4 17 86 NX_ 0038 5 38 42 31 47 62 25 20 29 4 25 FR6 7 7x20 4x9 3 40 79 NX_ 0045 5 46 51 38 57 76 29 4 25 40 29 4 FR6 7 7x20 4x9...

Страница 20: ...7 6 27 29 7 22 33 0 44 29 4 25 25 20 FR6 7 7x20 4x9 3 40 8 NX_ 0034 6 34 37 27 41 54 40 29 4 30 25 FR6 7 7x20 4x9 3 40 8 NX_ 0041 6 41 45 34 51 68 50 40 40 30 FR7 9 3x23 3x10 1 77 2 NX_ 0052 6 52 57 4...

Страница 21: ...x7 5 11 NX_ 0007 2 6 6 7 3 4 8 7 2 9 6 1 5 1 1 5 1 FR4 5 0x11 5x7 5 11 NX_ 0008 2 7 8 8 6 6 6 9 9 13 2 2 1 5 2 1 5 FR4 5 0x11 5x7 5 11 NX_ 0011 2 11 12 1 7 8 11 7 15 6 3 2 3 2 FR4 5 0x11 5x7 5 11 NX_...

Страница 22: ...Table 4 4 Brake resistor ratings Vacon NX_ supply voltage 380 500V Mains voltage 525 690 V 50 60 Hz 3 Converter type Max brake current I Resistor nom ohm Converter type Max brake current I Resistor n...

Страница 23: ...NX_ 0075 2 148 3 3 NX_ 0008 2 15 30 NX_ 0088 2 148 3 3 NX_ 0011 2 15 30 NX_ 0114 2 148 3 3 NX_ 0012 2 15 30 NX_ 0140 2 296 1 4 NX_ 0017 2 15 30 NX_ 0170 2 296 1 4 NX_ 0025 2 15 30 NX_ 0205 2 296 1 4...

Страница 24: ...z Field weakening point 8 320 Hz Acceleration time 0 1 3000 sec Deceleration time 0 1 3000 sec Braking torque DC brake 30 TN without brake option Ambient conditions Ambient operating temperature FR4 F...

Страница 25: ...uxiliary voltage 24V 10 max volt ripple 100mVrms max 250mA Dimensioning max 1000mA control box Output reference voltage 10V 3 max load 10mA Analogue output 0 4 20mA RL max 500 Resolution 10 bit Accura...

Страница 26: ...with four screws or bolts depending on the unit size The dimensions of installation are presented in Figure 5 11 and Table 5 10 Lift units bigger than FR7 out of the package using a jib crane Ask the...

Страница 27: ...x 1 11 0048 0061 NXS2 0038 0061 NX_5 0004 0034 NX_6 7 68 5 83 21 97 21 3 20 43 9 33 0 4 0 1 x 1 46 0075 0114 NXS2 0072 0105 NX_5 0041 0052 NX_6 9 33 7 48 24 80 24 17 23 27 10 12 0 4 0 1 x 1 85 0140 02...

Страница 28: ...0 87 7 48 3 03 0 3 0017 0031 NXS2 0016 0031 NX_5 5 67 4 72 17 09 16 54 16 5 1 42 0 71 8 43 3 94 0 3 0048 0061 NXS2 0038 0061 NX_5 0004 0034 NX_6 7 68 6 69 22 05 21 61 22 1 18 0 79 9 33 4 17 0 3 Table...

Страница 29: ...NX_5 4 84 4 45 12 40 12 8 0 2 0 3 0017 0031 NXS2 0016 0031 NX_5 5 31 4 72 16 14 16 54 0 2 0 3 0048 0061 NXS2 0038 0061 NX_5 0004 0034 NX_6 7 28 6 69 6 18 21 22 21 61 0 3 0 2 0 3 Table 5 3 Dimensions f...

Страница 30: ...4 8 188 5 7 42 0 91 0 79 10 11 4 61 0 2 0140 0205 NXS2 0140 0205 NX_5 0062 0100 NX_6 11 38 14 13 32 76 29 88 10 16 10 43 1 69 2 24 13 54 4 33 0 4 Table 5 4 Dimensions for different AC drive types FR7...

Страница 31: ...sions for the opening for flange mounting FR7 Figure 5 6 The opening needed for the flange mounting FR8 Type Dimensions inch W1 H1 H2 H3 H4 0140 0205 NXS2 0140 0205 NX_5 0062 0100 NX_6 12 99 10 16 10...

Страница 32: ...0 NXS2 0261 0300 NX_5 0125 0208 NX_6 18 9 400 15 74 0 4 2 13 45 28 44 09 28 39 8 07 0 63 7 40 14 25 13 39 11 22 0 83 Table 5 7 The dimensions Vacon NX_ FR9 Brake resistor terminal box H6 not included...

Страница 33: ...3 0261 0300 NXS2 0261 0300 NX_5 0125 0208 NX_6 20 87 20 08 19 09 7 87 0 2 51 65 45 28 16 5 3 94 1 38 0 4 0 08 14 25 13 39 4 29 0 83 Table 5 8 Vacon NX_ dimensions FR9 flange mounted W1 W2 W3 H1 W4 W4...

Страница 34: ...85 0520 NX_5 0261 0416 NX_6 23 43 11 46 5 16 0 59 79 45 74 8 56 5 20 161 57 23 70 0590 0730 NX_5 0460 0590 NX_6 31 26 15 35 9 06 0 6 79 45 74 8 56 5 20 161 57 23 70 Table 5 9 Vacon NX_ dimensions FR10...

Страница 35: ...N vacon 35 5 Figure 5 10 Vacon NXP dimensions FR12 floorstanding units Type plate Detail Y 1 5 15 Y X Warning plate Detail X 1 5 1197 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info...

Страница 36: ...mensions inch A A2 B C D 0004 0012 NXS2 0003 0012 NX_5 0 79 0 79 3 94 1 97 0017 0031 NXS2 0016 0031 NX_5 0 79 0 79 4 72 2 36 0048 0061 NXS2 0038 0061 NX_5 0004 0034 NX_6 1 18 0 79 6 3 3 15 0075 0114 N...

Страница 37: ...16 0031 NX_5 0004 0013 NX_6 112 0048 0061 NXS2 0038 0061 NX_5 0018 0034 NX_6 112 0075 0114 NXS2 0072 0105 NX_5 0041 0052 NX_6 250 0140 0205 NXS2 0140 0205 NX_5 0062 0100 NX_6 383 0261 0300 NXS2 0261 0...

Страница 38: ...0 NX_5 0460 0590 NX_6 1 97 3 94 2 76 5 91 0820 1030 NX_5 0650 0820 NX_6 1 97 3 94 A Minimum distance to the side walls or adjacent components B Minimum distance from the top of the cabinet C Free spac...

Страница 39: ...d hour yd3 h 0385 0520 5 0261 0416 6 3400 7 0650 0730 5 0460 0590 6 5101 01 0820 1030 5 0650 0820 6 6801 3 Table 5 13 Required cooling air Figure 5 12 Cabinet installation space Mounting space dimensi...

Страница 40: ...igure 5 14 Power loss as function of switching frequency NX_5 0016 0031 0 00 20 00 40 00 60 00 80 00 100 00 120 00 140 00 160 00 180 00 200 00 0 00 2 00 4 00 6 00 8 00 10 00 12 00 14 00 16 00 Switchin...

Страница 41: ...4 00 6 00 8 00 10 00 12 00 Switching frequency kHz P W 0072NX5 400V 0072NX5 500V 0087NX5 400V 0087NX5 500V 0105NX5 400V 0105NX5 500V 0 00 200 00 400 00 600 00 800 00 1000 00 1200 00 1400 00 0 00 2 00...

Страница 42: ...0 3000 00 3500 00 4000 00 0 00 2 00 4 00 6 00 8 00 10 00 12 00 Switching frequency kHz P W 0140NX5 400V 0140NX5 500V 0168NX5 400V 0168NX5 500V 0205NX5 400V 0205NX5 500V 0 00 500 00 1000 00 1500 00 200...

Страница 43: ...frequency NX_5 0385 0520 0 00 1000 00 2000 00 3000 00 4000 00 5000 00 6000 00 7000 00 8000 00 1 2 3 4 Switchingfrequency kHz P W 0385NX400V 0385NX500V 0460NX400V 0460NX500V 0520NX400V 0520NX500V Phone...

Страница 44: ...e or more cables are used in parallel for bigger units each cable requires a separate overload protection These instructions apply only to cases with one motor and one cable connection from the AC dri...

Страница 45: ...h terminal mm2 FR4 NX0004 2 0008 2 NX0003 5 0009 5 3 8 3 9 10 3 1 5 1 5 1 4 1 4 NX0011 2 0012 2 NX0012 5 11 12 12 16 3 2 5 2 5 1 4 1 4 FR5 NX0017 2 NX0016 5 17 16 20 3 4 4 1 10 1 10 NX0025 2 NX0022 5...

Страница 46: ...0 6 0013 6 10 13 16 3 2 5 2 5 2 5 50 Cu 6 50 Al 2 5 35 NX0018 6 18 20 3 4 4 2 5 50 Cu 6 50 Al 2 5 35 NX0022 6 22 25 3 6 6 2 5 50 Cu 6 50 Al 2 5 35 NX0027 6 0034 6 27 34 35 3 10 10 2 5 50 Cu 6 50 Al 2...

Страница 47: ...to FR12 1 based on correction factor 0 7 6 1 1 7 Cable and fuse sizes NX_6 FR10 to FR12 The table below shows typical cable sizes and types that can be used with the converter The final selection shou...

Страница 48: ...drive in frame sizes FR4 to FR12 Figure 6 1 Topology of mechanical sizes FR4 FR12 M M M nk6_18 fh8 FR4 9 FR10 Single input Single output FR11 Double input Single output FR12 Double input Double output...

Страница 49: ...ry see below and note the date Unless already done attach the sticker close to the nameplate of the AC drive FR4 and FR5 Figure 6 2 Changing of EMC protection class FR4 left and FR5 right First remove...

Страница 50: ...protection class FR7 NOTE Only a Vacon service person may change the EMC protection class of Vacon NXS P FR8 and FR9 Remove this screw Remove this screw and replace with plastic screw M4 Phone 800 89...

Страница 51: ...es all components except 4 and 5 Mounting procedure 1 Make sure that the plastic bag you have received contains all necessary components 2 Open the cover of the AC drive Figure 1 3 Remove the cable co...

Страница 52: ...52 vacon CABLING AND CONNECTIONS 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 53: ...mains cables as advised in Table 6 6 and Figure 6 6 Remove the screws of the cable protection plate Do not open the cover of the power unit Make holes into and pass the cables through the rubber grom...

Страница 54: ...4 0 4 1 6 FR6 0 79 3 5 0 59 2 4 0 79 3 5 0 59 2 4 FR7 0 98 4 7 0 98 4 7 0 98 4 7 0 98 4 7 FR8 0140 0168 0205 0 91 1 1 9 4 9 4 0 91 1 1 9 4 9 4 0 91 1 1 9 4 9 4 0 91 1 1 9 4 9 4 FR9 1 1 11 6 1 1 11 6...

Страница 55: ...l brake resistor connection P6 7 1 on page 100 in this manual Figure 6 7 Vacon NXS P FR4 Figure 6 8 Cable installation in Vacon NXS P FR4 NOTE Two protective conductors are required for FR4 according...

Страница 56: ...56 vacon CABLING AND CONNECTIONS 6 Figure 6 9 Additional grounding connector for FR4 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 57: ...10 Vacon NXS P FR5 Figure 6 11 Cable installation in Vacon NXS P FR5 NOTE See chapter 1 3 Mains cable Motor cable Earth terminals Brake resistor terminals DC terminals Phone 800 894 0412 Fax 888 723 4...

Страница 58: ...ble installation in Vacon NXS P FR6 NOTE See chapter 1 3 Mains cable Motor cable Earth terminals Brake resistor terminals Brake resistor terminals Mains cable Motor cable Earth terminals DC terminals...

Страница 59: ...14 Vacon NXS P FR7 Figure 6 15 Cable installation in Vacon NXS P FR7 NOTE See chapter 1 3 Mains cable Motor cable Earth terminals Brake resistor terminals DC terminals Phone 800 894 0412 Fax 888 723 4...

Страница 60: ...60 vacon CABLING AND CONNECTIONS 6 Figure 6 16 Vacon NXS P FR8 with optional DC brake resistor connection box on top Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 61: ...Cable installation in Vacon NXS P FR8 Figure 6 18 Brake resistor terminal box on top of FR8 Mains cable Motor cable Earth terminal DC terminals Brake resistor terminals Phone 800 894 0412 Fax 888 723...

Страница 62: ...G AND CONNECTIONS 6 Figure 6 19 Vacon NXS P FR9 Figure 6 20 Cable installation in Vacon NXS P FR9 Mains cable Motor cables Earth terminals Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email...

Страница 63: ...vacon 63 6 Figure 6 21 DC and brake resistor terminals on FR9 DC terminals marked with B and B brake resistor terminals marked with R and R B B R R Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr c...

Страница 64: ...Figure 6 22 Example of NXS P standalone drives FR11 Note More information on cabling for frames FR10 and greater you will find in Vacon NXP C User s Manual Phone 800 894 0412 Fax 888 723 4773 Web www...

Страница 65: ...h phase conductor and the protective ground conductor The insulation resistance must be 1M 2 Mains cable insulation checks Disconnect the mains cable from terminals L1 L2 and L3 of the AC drive and fr...

Страница 66: ...ntrol signal descriptions The I O boards mounted at the factory are indicated in the type code For more information on the option boards see Vacon NX option board manual ud741 The control board can be...

Страница 67: ...2 RO1 3 RO2 1 2 2 RO2 3 ac dc 21 22 23 24 25 26 NX6_6 fh8 21 22 23 25 26 RO1 1 1 2 RO1 3 2 1 RO2 2 ac dc 28 29 TI1 TI1 t Switching 8A 24Vdc 0 4A 125Vdc 2kVA 250Vac Continuously 2Arms Basic relay boar...

Страница 68: ...solation barriers The control connections are isolated from the mains potential and the GND terminals are permanently connected to ground See Figure 6 28 The digital inputs are galvanically isolated f...

Страница 69: ...er backup for the control unit and fieldbus 7 GND I O ground Ground for reference and controls 8 DIN1 Digital input 1 Ri min 5k 18 30V 1 9 DIN2 Digital input 2 10 DIN3 Digital input 3 11 CMA Digital i...

Страница 70: ...Thermistor input 29 TI1 Table 6 11 Control I O terminal signals on basic relay board OPT A3 6 2 2 1 Digital input signal inversions The active signal level depends on which potential the common input...

Страница 71: ...the jumpers on the OPT A1 board The positions of the jumpers determine the signal type of analogue and digital inputs On the A1 basic board there are four jumper blocks X1 X2 X3 and X6 each containin...

Страница 72: ...Voltage input 10 10V Jumper block X2 AI2 mode AI2 mode 0 20mA Current input AI2 mode Voltage input 0 10V AI2 mode Voltage input 0 10V differential AI2 mode Voltage input 10 10V Jumper block X3 CM A a...

Страница 73: ...ne potential 7 1 Indications on the Keypad display Figure 7 1 Vacon control keypad and drive status indications 7 1 1 Drive status indications The drive status indications tell the user what the statu...

Страница 74: ...ator READY is lit up Illuminates when the drive is running Blinks when the STOP button has been pushed and the drive is ramping down Blinks when unsafe operating conditions were encountered due to whi...

Страница 75: ...ns 2 fault history reset 2 3 seconds Browser button up Browse the main menu and the pages of different submenus Edit values Browser button down Browse the main menu and the pages of different submenus...

Страница 76: ...enu can be entered from the main menu using the Menu buttons When there still are pages to enter under the currently displayed menu or page you can see an arrow in the lower right corner of the displa...

Страница 77: ...erm P1 P15 READY I Oterm 13 95 Hz READY Loc al P1 P3 READY I Oterm STOP READY I Oterm STOP enter enter F0 STOP FAULT I Oterm Parameters Basic parameters Min Frequency 11 Output phase Operation days 17...

Страница 78: ...ated motor shaft torque V1 6 Motor power Calculated motor shaft power V1 7 Motor voltage V Calculated motor voltage V1 8 DC link voltage V Measured DC link voltage V1 9 Unit temperature F Heat sink te...

Страница 79: ...n right once again Now you will be able to edit the value digit by digit This editing manner may come in handy when a relatively greater or smaller value than that on the display is desired Confirm th...

Страница 80: ...EADY Keypad P1 P18 READY Keypad 13 95 Hz READY Keypad G1 G8 Keypad READY Keypad 13 95 Hz enter READY Keypad 14 45 Hz Parameters Basic parameters Min Frequency Input signals Min Frequency Min Frequency...

Страница 81: ...ce There are three different places sources which the AC drive can be controlled from For each control place a different symbol will appear on the alphanumeric display Control place Symbol I O termina...

Страница 82: ...meter is 0 the STOP button will stop the motor only when the keypad has been selected as the active control place Note Additional Information on controlling the motor with the keypad is given in Chapt...

Страница 83: ...T the red led on the keypad starts to blink If several faults occur simultaneously the list of active faults can be browsed with the Browser buttons The memory of active faults can store the maximum o...

Страница 84: ...he drive stop Actions need to be taken in order to restart the drive AR Fault Autoreset If an AR fault occurs the drive will also stop immediately The fault is reset automatically and the drive tries...

Страница 85: ...r avail able as options Activate overvoltage controller Check input voltage 3 Earth fault Current measurement has detected that the sum of motor phase current is not zero insulation failure in cables...

Страница 86: ...the ambient temperature Make sure that the switching frequency is not too high in relation to ambient temperature and motor load 15 Motor stalled Motor stall protection has tripped Check motor and lo...

Страница 87: ...ature IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current Check loading Check motor size Make identification run 42 Brake resistor overtemperature Brake...

Страница 88: ...n run Motor is not connected to AC drive There is load on motor shaft 58 Brake Actual status of the brake is different from the control signal Check mechanical brake state and connections 59 Follower...

Страница 89: ...ode d T 2 Counted operation hours Fault 43 Counted operation days hh mm ss d T 3 Output frequency Fault 43 Counted operation hours Hz hh mm ss T 4 Motor current A T 5 Motor voltage V T 6 Motor power T...

Страница 90: ...order of appearance The number of faults currently in the fault history is shown on the value line of the main page H1 H The order of the faults is indicated by the location indication in the upper le...

Страница 91: ...Step Application PID Control Application Multi Purpose Control Appl Pump and Fan Control Appl S6 3 Copy parameters S6 3 1 Parameter sets Store set 1 Load set 1 Store set 2 Load set 2 Load factory def...

Страница 92: ...T6 8 2 5 Clear operating time counter S6 8 3 Software info S6 8 3 1 Software package S6 8 3 2 System software version S6 8 3 3 Firmware interface S6 8 3 4 System load S6 8 4 Applications S6 8 4 Name...

Страница 93: ...ction page S6 2 This is done by pushing the Menu button right when on the first page of the System menu Change then the application by pushing the Menu button right once again The name of the applicat...

Страница 94: ...rameter sets S6 3 1 The Vacon NX_ AC drive features a possibility for the user to load back the factory default parameter values and to store and load two customised parameter sets all parameters incl...

Страница 95: ...pad to a drive provided that the drive is in STOP status Enter the From keypad page S6 3 3 from the Parameter copy menu Push the Menu button right to enter the edit mode Use the Browser buttons to sel...

Страница 96: ...when applications are changed If you want to transfer the parameters from one application to another you have to upload them first to the keypad 7 3 6 4 Parameter comparison In the Parameter comparis...

Страница 97: ...t the units Then push the Menu button left and you can set the tens etc Finally confirm the password setting with the Enter button After this you have to wait until the Timeout time P6 6 3 see page 10...

Страница 98: ...the values for a set of parameters common to all applications as well as for a set of application dependent parameters Always accept the value with the Enter button scroll options or change values wi...

Страница 99: ...below has expired or as the power is switched on to the keypad If the Default Page value is 0 the function is not activated i e the last displayed page remains on the keypad display Press the Menu but...

Страница 100: ...see Timeout time P6 6 3 7 3 6 7 Hardware settings NOTE The Hardware settings submenu is protected with a password see chapter Password S6 5 1 Store the password in a safe place In the Hardware setting...

Страница 101: ...mode shown starts to blink Use the Browser buttons to change the fan mode Accept the change with the Enter button or return to the previous level with the Menu button left Figure 7 22 Fan control func...

Страница 102: ...shown starts to blink Use the Browser buttons to change the amount of retries Accept the change with the Enter button or return to the previous level with the Menu button left See Figure 7 23 for the...

Страница 103: ...r Operation time counter Example When you want to reset the operation counters you should do the following Figure 7 24 Counter reset Software S6 8 3 The Software information page includes information...

Страница 104: ...8 5 1 Power unit type code 6 8 5 2 Nominal voltage of the unit 6 8 5 3 Brake chopper 6 8 5 4 Brake resistor Table 7 11 Hardware information pages Expander boards S6 8 6 In the Expander boards pages y...

Страница 105: ...s Debug menu S6 8 7 This menu is meant for advanced users and application designers Contact factory for any assistance needed E1 E5 READY I Oterm A NXOPTA1 I Oterm READY B NXOPTA2 I Oterm E1 E2 I Oter...

Страница 106: ...12 and Figure 7 27 Expander board parameters Code Parameter Min Max Default Cust Selections P7 1 1 1 AI1 mode 1 5 3 1 0 20 mA 2 4 20 mA 3 0 10 V 4 2 10 V 5 10 10 V P7 1 1 2 AI2 mode 1 5 1 See P7 1 1...

Страница 107: ...has expired 6 Before connecting the AC drive to mains make sure that the Vacon NX_ front cover is closed 7 When running the side of converter FR8 is burning hot Do not touch with hands 8 When running...

Страница 108: ...sing the Browser buttons d Check in the Monitoring menu M1 that the value of Output frequency changes according to the change of frequency reference e Push the Stop button on the keypad stop 9 Run the...

Страница 109: ...the startup test was run without the motor being connected a Before running the tests make sure that this can be done safely b Inform your co workers of the tests c Repeat test 8A or 8B Phone 800 894...

Страница 110: ...motor Subcode in T 14 S1 Hardware trip S2 Reserved S3 Current controller supervision Check loading Check motor Check cables Make identification run 2 Overvoltage The DC link voltage has exceeded the l...

Страница 111: ...no brake resistor installed brake resistor is broken brake chopper failure Check brake resistor and cabling If the these are ok the chopper is faulty Contact the distributor near to you 13 AC drive un...

Страница 112: ...XP Power Unit and vice versa Change control unit 37 Device changed same type Option board or control unit changed Same type of board or same power rating of drive Reset Device is ready for use Old par...

Страница 113: ...or 56 PT100 board temp fault Temperature limit values set for the PT100 board parameters have been exceeded Find the cause of temperature rise 57 Identification Identification run has failed Run comma...

Страница 114: ...Document ID Rev A Finland Subject to change without prior notice 2013 Vacon Plc Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Отзывы: