vacon • 10
Safety
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Figure 4. Insulation system (single-phase version).
1.7
Compatibility with RCDs
(*)
Only for 3~ units.
(**)
The relays may be used also with DVC A circuits. This is possible only if both
relays are used for DVC A circuitry:
to mix Mains and DVC A is not allowed.
By performing the cabling, a suitable clearance has to be guaranteed between
DVC A circuits and Mains (reinforced insulation is required, according to IEC
61800-5-1).
This product can cause a d.c. current in the protective grounding conductor.
Where a residual current-operated protective (RCD) or monitoring (RCM) device
is used for protection in case of direct or indirect contact, only an RCD or RCM of
Type B is allowed on the supply side of this product.
POWER UNIT
L
N
U
V
W
R01 __
R02 __
10Vref __
Analog Inputs __
Digital Inputs__
Analog Output __
24V __
RS485 __
Keypad
CONTROL UNIT
Reinforced
Mains
DVC A
DVC A or Mains
(**)
DC-
DC+