Commissioning
vacon • 57
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
6.1
Commissioning of the drive
Read carefully the safety instructions in Chapter 1 and above and follow them.
After the installation:
Check that both the AC drive and the motor are grounded.
Check that the mains and motor cables comply with the requirements given in
chapter 4.1.1.
Check that the control cables are located as far as possible from the power cables,
see chapter 4.4.
Check that the shields of the shielded cables are connected to protective earth
marked with
.
Check the tightening torques of all terminals.
Check that the wires do not touch the electrical components of the drive.
Check that the common inputs of digital input groups are connected to +24V or
ground of the I/O terminal.
Check the quality and quantity of cooling air.
Check the inside of the AC drive for condensation.
Check that all Start/Stop switches connected to the I/O terminals are in the Stop-
position.
Before connecting the AC drive to mains: Check mounting and condition of all fus-
es and other protective devices.