Options
vacon • 80
8
11
100
Output phase
supervision
Current measurement has detected
that there is no current in one motor
phase.
Check motor cable and motor.
12
110
Brake chopper
supervision
(hardware fault)
No brake resistor installed.
Brake resistor is broken.
Brake chopper failure.
Check brake resistor and
cabling.
If these are ok, the chopper is
faulty. Contact the distributor
near to you.
111
Brake chopper
saturation alarm
13
120
AC drive under-
temperature
(fault)
Too low temperature measured in
power unit’s heatsink or board. Heat-
sink temperature is under -10°C.
Check the ambient tempera-
ture
14
130
AC drive over-
temperature
(fault, heatsink)
Too high temperature measured in
power unit’s heatsink or board. Heat-
sink temperature is over 100°C.
Check the correct amount and
flow of cooling air.
Check the heatsink for dust.
Check the ambient tempera-
ture.
Make sure that the switching
frequency is not too high in
relation to ambient tempera-
ture and motor load.
131
AC drive over-
temperature
(alarm, heatsink)
132
AC drive over-
temperature
(fault, board)
133
AC drive over-
temperature
(alarm, board)
15
140
Motor stalled
Motor is stalled.
Check motor and load.
16
150
Motor overtem-
perature
Motor is overloaded.
Decrease motor load.
If no motor overload exists,
check the temperature model
parameters.
17
160
Motor underload Motor is underloaded.
Check load.
19
180
Power overload
(short-time
supervision)
Drive power is too high.
Decrease load.
181
Power overload
(long-time super-
vision)
25
240
Motor control
fault
Start angle identification has failed.
Reset the fault and restart.
Should the fault re-occur, con-
tact the distributor near to you.
241
Generic motor control fault.
30
290
STO fault
Safe OFF signal A does not allow AC
drive to be set to READY state.
Reset the fault and restart.
Should the fault re-occur, con-
tact the distributor near to you.
291
Safe OFF signal B does not allow AC
drive to be set to READY state.
32
312
Fan cooling
Fan life time is up.
Change fan and reset fan life
time counter.
33
320
Fire mode
enabled
Fire mode of the drive is enabled. The
drive's protections are not in use.
Check the parameter settings
37
360
Device changed
(same type)
Option board changed for one previ-
ously inserted in the same slot. The
board’s parameter settings are saved.
Device is ready for use. Old
parameter settings will be
used.
Fault
code
Fault
ID
Fault name
Possible cause
Remedy
Table 25. Fault codes and descriptions.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание 100X series
Страница 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 14: ...1 vacon 11 Safety Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 26: ...3 vacon 23 Mounting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 60: ...7 vacon 57 Technical data Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 86: ...8 vacon 83 Options Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 99: ...Safe Torque Off vacon 96 9 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...