Vac - Alert VA-2000 Скачать руководство пользователя страница 8

 

8

in the hole at the vent end.  Push the Vac-Alert

TM

 piston towards the adjustment 

end until the lockout mechanism is engaged.  A clicking sound is heard when the 
lockout mechanism is engaged. 

 

2.

 

Remove the security cap from the adjustment end (white end with Vac-Alert

TM

 

embossing on body) utilizing the spanner tool shipped with the unit.  The security 
cap is removed by unthreading it, rotating in a counterclockwise direction.  Once 
the security cap is removed, the spring compression adjustment screw is visible 
inside the Vac-Alert

TM

 body.  To adjust this screw, a flat bladed (straight slot) 

screwdriver is required. 

 

3.

 

With the Vac-Alert

TM

 in the open position, turn the adjustment screw clockwise to 

increase spring compression (for higher vacuum operating levels), and counter-
clockwise to decrease spring compression (for lower vacuum operating levels). 

 

¾

 

To adjust the Vac-Alert

TM

 for an operating vacuum level of less 

than 5” Hg, rotate the adjustment screw counterclockwise until 
the screw travel stop (minimum spring compression setting) is 
reached. 

 

¾

 

To adjust the SVRS unit for an operating vacuum level of up to 
15” Hg, rotate the adjustment screw clockwise until the screw 
travel stop (maximum spring compression setting) is reached, then 
back the adjustment screw off counter-clockwise one revolution.  

   

¾

 

The adjustment screw must be positioned properly between the 
two travel stops to set the Vac-Alert

TM

 unit for operating vacuum 

levels greater than 5” Hg and less than 15” Hg. 

 

NOTE:  Always adjust the Vac-Alert

TM

 adjustment screw with the unit in the open 

(venting) position.  The SVRS can be placed in the open position from the vent end 
(gray end) by utilizing a screwdriver.  Remove the vent screen and place the 
screwdriver in the hole at the vent end.  Push the Vac-Alert

TM

 piston towards the 

adjustment end until the lockout mechanism is engaged.  A clicking sound is heard 
when the lockout mechanism is engaged.  Once screw adjustment is made, the SVRS 
can be returned to the closed position by gently pressing down the reset lever. 
 
FINAL ADJUSTMENT

  

 

   1.  The Vac-Alert

TM

 should be adjusted to a spring compression level that ensures the 

SVRS unit does not lock open during pump start-up.  Do not over tighten the 
adjustment screw.  Adjust the screw in increments of two full rotations, then reset 
the unit, and retest for air venting.  The SVRS should be tested at various 
adjustment levels to determine the balance point at which venting begins to occur 
at pump start-up.  

 

2.  Once the balance point is determined, the adjustment screw should be positioned 

clockwise two (2) full turns beyond this point as the 

final SVRS setting. 

 

Содержание VA-2000

Страница 1: ...Safety Vacuum Release System Installation Instructions Model VA 2000 Vac AlertTM Industries LLC 775 8th Court Suite 4 Vero Beach FL 32962 www vac alert com April 29 2011...

Страница 2: ...ation o VAC ALERT MODEL VA 2000S Submerged The Vac AlertTM Model VA 2000S is a Safety Vacuum Release System SVRS designed for submerged suction applications Submerged suction in this case applies to a...

Страница 3: ...s located more than 42 above pool or spa water level contact your Vac AlertTM representative for further instructions For applications where the pump is located more than 24 below pool or spa water le...

Страница 4: ...at each end DO NOT DROP THE UNIT The Installation Instructions DVD and Quick Installation Guide are located in the box stowed between the box and the lower polystyrene insert If the outer package appe...

Страница 5: ...flow coming from the main drain line If the vacuum level is over 15 see previous suggestions for lowering system running vacuum level NOTE Do not use a flow restricted test valve or a slow acting tes...

Страница 6: ...o mount the SVRS off the installed tee A reducing bushing may also be required to mate the 1 1 2 diameter SVRS to the tee fitting installed Utilize pipe nipples to join fittings in a close coupled fas...

Страница 7: ...em Preparation for options on how to lower system operating vacuum level 2 NOTE Each SVRS comes factory set to remain closed non venting for vacuum levels up to 10 Hg If the pump start up test indicat...

Страница 8: ...ion setting is reached then back the adjustment screw off counter clockwise one revolution The adjustment screw must be positioned properly between the two travel stops to set the Vac AlertTM unit for...

Страница 9: ...dry running of self priming pumps where pump suction lift is less than 42 To make sure the unit is working properly turn off the pump and place the Vac AlertTM SVRS unit in the open venting position W...

Страница 10: ...valve is an optional alternative to a pole mounted test mat Each Vac AlertTM SVRS unit must be tested three 3 times to ensure proper adjustment and operation Where a hydro static valve is present the...

Страница 11: ...ain drain blockage b Using the installed test valve or a pole mounted test mat conduct routine testing of the SVRS device to ensure proper adjustment of the unit The Vac AlertTM Model VA 2000 SVRS uni...

Страница 12: ...s operate in a dry state Any indication that the unit is flooded or water logged as evidenced by water leakage from the SVRS unit requires immediate service attention Immediately shut down the pool or...

Страница 13: ...14...

Страница 14: ...l m m m m l l l l m m m l l...

Страница 15: ...l l l...

Страница 16: ...sceration Under no circumstances should any child ever be left unattended at or by any body of water Never sit lay or swim near or by suction ports suction ttings or main drains THIS PRODUCT IS 3RD PA...

Страница 17: ...ION LOCATION INFORMATION Name of Purchaser ________________________________________________________________ Installation Address _______________________________________________________________ I have...

Отзывы: