Vac - Alert VA-2000 Скачать руководство пользователя страница 2

 

2

o

 

VAC-ALERT MODEL VA-2000L (Lift) 

  
The Vac-Alert

TM

 Model VA-2000L is a Safety Vacuum Release System (SVRS) 

designed for 

suction lift

 applications.  Suction lift in this case applies to all applications 

where the circulating pump suction is no more than 24” below, or no more than 42” 
above the level of the pool or spa water surface.  This unit incorporates a 0.170” diameter 
orifice opening installed below the surge tube section.  This orifice opening is sized to 
prevent nuisance tripping of the SVRS unit caused by high vacuum surges typical of 
many pump start-up conditions. 
 
The Model VA-2000L SVRS unit also utilizes a check valve assembly equipped with a 
3.5 pound spring, a poppet disc and a one-way (up only) vented poppet. This check valve 
assembly permits continued water flow to the circulating pump while the SVRS unit is in 
the open or vented position.  The 3.5 pound spring further compressed by the poppet disc, 
creates enough sealing force within the check valve to allow partial water flow to the 
circulating pump for suction lifts up to 42 inches.  This is critical to the elimination of 
circulating pump damage that can be caused by a sustained dry-running condition.  The 
one-way vented poppet allows the surge chamber to be internally recharged when the 
circulating pump is turned off.  This feature prevents nuisance tripping of the SVRS unit 
on pools and spas that utilize a timer or air switch for circulation pump operation. 
 

o

 

VAC-ALERT MODEL VA-2000S (Submerged) 

  
The Vac-Alert

TM

 Model VA-2000S is a Safety Vacuum Release System (SVRS) 

designed for 

submerged suction

 applications.  Submerged suction in this case applies to 

applications where the circulating pump suction is more than 24” below the level of the 
pool water surface.  

The Model VA-2000S is recommended on commercial pool 

applications where the pump has a submerged suction of any depth and runs 24/7.  
In submerged suction applications, for pumps 10 horsepower and greater, or for 
pumps located 10 feet or more below the water line, a pump shut-off switch (Model 
PSAC) is recommended.

  The Model VA-2000S unit incorporates a 0.375” diameter 

orifice opening installed below the surge tube section.  This orifice opening is sized to 
provide a limited amount of pump start-up surge protection, while at the same time 
allowing enough air into the piping system to insure dissipation of the dynamic suction 
force caused by the circulating pump. 
 
The Model VA-2000S SVRS unit also utilizes a check valve assembly equipped with a 
0.25 pound spring and a non-vented poppet (no poppet disc or hole through the poppet).   
This check valve assembly utilizes a light duty spring to minimize the sealing force of the 
check valve.  The non-vented poppet insures that water from the circulating system, 
under a positive hydrostatic head condition, does not migrate up into the SVRS unit.  
 

 
NOTE:  

The Model VA-2000 type is indicated on the outside of the box 

and on the unit itself.  Make sure you have the correct Model SVRS for 
your application!  SVRS in these instructions refers specifically to the 
Vac-Alert

TM

 Model VA-2000. 

Содержание VA-2000

Страница 1: ...Safety Vacuum Release System Installation Instructions Model VA 2000 Vac AlertTM Industries LLC 775 8th Court Suite 4 Vero Beach FL 32962 www vac alert com April 29 2011...

Страница 2: ...ation o VAC ALERT MODEL VA 2000S Submerged The Vac AlertTM Model VA 2000S is a Safety Vacuum Release System SVRS designed for submerged suction applications Submerged suction in this case applies to a...

Страница 3: ...s located more than 42 above pool or spa water level contact your Vac AlertTM representative for further instructions For applications where the pump is located more than 24 below pool or spa water le...

Страница 4: ...at each end DO NOT DROP THE UNIT The Installation Instructions DVD and Quick Installation Guide are located in the box stowed between the box and the lower polystyrene insert If the outer package appe...

Страница 5: ...flow coming from the main drain line If the vacuum level is over 15 see previous suggestions for lowering system running vacuum level NOTE Do not use a flow restricted test valve or a slow acting tes...

Страница 6: ...o mount the SVRS off the installed tee A reducing bushing may also be required to mate the 1 1 2 diameter SVRS to the tee fitting installed Utilize pipe nipples to join fittings in a close coupled fas...

Страница 7: ...em Preparation for options on how to lower system operating vacuum level 2 NOTE Each SVRS comes factory set to remain closed non venting for vacuum levels up to 10 Hg If the pump start up test indicat...

Страница 8: ...ion setting is reached then back the adjustment screw off counter clockwise one revolution The adjustment screw must be positioned properly between the two travel stops to set the Vac AlertTM unit for...

Страница 9: ...dry running of self priming pumps where pump suction lift is less than 42 To make sure the unit is working properly turn off the pump and place the Vac AlertTM SVRS unit in the open venting position W...

Страница 10: ...valve is an optional alternative to a pole mounted test mat Each Vac AlertTM SVRS unit must be tested three 3 times to ensure proper adjustment and operation Where a hydro static valve is present the...

Страница 11: ...ain drain blockage b Using the installed test valve or a pole mounted test mat conduct routine testing of the SVRS device to ensure proper adjustment of the unit The Vac AlertTM Model VA 2000 SVRS uni...

Страница 12: ...s operate in a dry state Any indication that the unit is flooded or water logged as evidenced by water leakage from the SVRS unit requires immediate service attention Immediately shut down the pool or...

Страница 13: ...14...

Страница 14: ...l m m m m l l l l m m m l l...

Страница 15: ...l l l...

Страница 16: ...sceration Under no circumstances should any child ever be left unattended at or by any body of water Never sit lay or swim near or by suction ports suction ttings or main drains THIS PRODUCT IS 3RD PA...

Страница 17: ...ION LOCATION INFORMATION Name of Purchaser ________________________________________________________________ Installation Address _______________________________________________________________ I have...

Отзывы: