Following are suggestions for lowering system operating vacuum levels at an existing 
pool or spa. 
 
 

1.  Reduce the pump size or reduce the pump impeller diameter 

 

2.  Check the main drain line for blockages 

 

3.  Replace the drain cover with another cover that has a higher open area 

 

4.  Replace return side nozzles with smaller orifices to slow down flow 

 
For new construction or a remodel project, increase the diameter of the connector piping 
and fittings where two or more main drains are employed, and increase the diameter of 
the main drain suction line to reduce pipe velocity and running vacuum level.  Minimize 
the use of 90 degree elbows and other fittings that increase the system pressure drop.  
Keep your pipe runs as short as possible. 
 
Once the system vacuum level is set at 15” Hg or less, the system can be prepared for 
SVRS installation. 
 

SVRS UNPACKING INSTRUCTIONS 
 

The VA2000 SVRS is packaged in a corrugated box with polystyrene upper and lower 
inserts to protect the unit from damage during shipment.  The product serial number is 
located on the top of the box, and on the upper back side of the unit (ARL Number).  
Carefully open the top of the box and note that the spanner key is housed in the 
polystyrene insert – Do not lose or misplace the spanner key.  Remove the upper insert 
after stowing the spanner key and lift the unit by grasping the tee at each end.  

DO NOT 

DROP THE UNIT!  

The Installation Instructions, DVD and Quick Installation Guide 

are located in the box stowed between the box and the lower polystyrene insert.

 

 
If the outer package appears to have been damaged during shipment, carefully inspect the 
unit. Closely inspect the vacuum gauge for possible damage in shipment; if the vacuum 
gauge is damaged or in need of replacement it can be ordered by calling the factory.  The 
gauge incorporates a ¼” tapered pipe thread end connection which is installed into a 
stainless steel gauge bushing.  The gauge and the bushing are threaded together at the 
factory with an anaerobic sealant.  This sealant hardens and makes the separation of the 
two parts difficult.  The gauge bushing has external straight pipe threads and is threaded 
into the main body of the unit with a non-hardening sealant.  The gauge and bushing 
together can be easily unthreaded from the main body by rotating the bushing counter 
clockwise until it is free.  The bushing can then be placed in a bench vise and removed 
from the gauge.

   

 

SVRS INSTALL REQUIREMENTS

   

 

Though the SVRS (Safety Vacuum Release System) is easily installed, Vac-Alert

TM

 

highly recommends that a licensed contractor or service company install the SVRS. 

 

When you properly install a Vac-Alert

TM

 SVRS, you are providing an important 

layer of protection against dangerous body and limb entrapment situations.  This 
system is not an effective defense against hair entanglement. This device may 
mitigate evisceration.  The Model VA-2000 SVRS unit shall only be installed in 

Содержание VA-2000

Страница 1: ...Safety Vacuum Release System Installation Instructions Model VA 2000 Vac AlertTM Industries LLC 775 8th Court Suite 4 Vero Beach FL 32962 www vac alert com April 29 2011...

Страница 2: ...ation o VAC ALERT MODEL VA 2000S Submerged The Vac AlertTM Model VA 2000S is a Safety Vacuum Release System SVRS designed for submerged suction applications Submerged suction in this case applies to a...

Страница 3: ...s located more than 42 above pool or spa water level contact your Vac AlertTM representative for further instructions For applications where the pump is located more than 24 below pool or spa water le...

Страница 4: ...at each end DO NOT DROP THE UNIT The Installation Instructions DVD and Quick Installation Guide are located in the box stowed between the box and the lower polystyrene insert If the outer package appe...

Страница 5: ...flow coming from the main drain line If the vacuum level is over 15 see previous suggestions for lowering system running vacuum level NOTE Do not use a flow restricted test valve or a slow acting tes...

Страница 6: ...o mount the SVRS off the installed tee A reducing bushing may also be required to mate the 1 1 2 diameter SVRS to the tee fitting installed Utilize pipe nipples to join fittings in a close coupled fas...

Страница 7: ...em Preparation for options on how to lower system operating vacuum level 2 NOTE Each SVRS comes factory set to remain closed non venting for vacuum levels up to 10 Hg If the pump start up test indicat...

Страница 8: ...ion setting is reached then back the adjustment screw off counter clockwise one revolution The adjustment screw must be positioned properly between the two travel stops to set the Vac AlertTM unit for...

Страница 9: ...dry running of self priming pumps where pump suction lift is less than 42 To make sure the unit is working properly turn off the pump and place the Vac AlertTM SVRS unit in the open venting position W...

Страница 10: ...valve is an optional alternative to a pole mounted test mat Each Vac AlertTM SVRS unit must be tested three 3 times to ensure proper adjustment and operation Where a hydro static valve is present the...

Страница 11: ...ain drain blockage b Using the installed test valve or a pole mounted test mat conduct routine testing of the SVRS device to ensure proper adjustment of the unit The Vac AlertTM Model VA 2000 SVRS uni...

Страница 12: ...s operate in a dry state Any indication that the unit is flooded or water logged as evidenced by water leakage from the SVRS unit requires immediate service attention Immediately shut down the pool or...

Страница 13: ...14...

Страница 14: ...l m m m m l l l l m m m l l...

Страница 15: ...l l l...

Страница 16: ...sceration Under no circumstances should any child ever be left unattended at or by any body of water Never sit lay or swim near or by suction ports suction ttings or main drains THIS PRODUCT IS 3RD PA...

Страница 17: ...ION LOCATION INFORMATION Name of Purchaser ________________________________________________________________ Installation Address _______________________________________________________________ I have...

Отзывы: