Vac - Alert VA-2000 Скачать руководство пользователя страница 7

 

7

 

 

PUMP START-UP TEST 
 
     1.    At this point, the pump start-up vacuum level for the system needs to be 
            determined.  Close the SVRS vent by pushing down on the reset lever.  

 

Use the vacuum gauge on the installed SVRS unit to read the pump start-up 
vacuum level in the main drain line.  

The peak start-up vacuum level should be 

read with full prime on the pump, all air bled from the filter system, at 
maximum return rate of flow, and with all suction flow directed from the 
main drain.

  This condition will typically produce the peak vacuum level that the 

SVRS will be exposed to during pump start-up.  

Set valves and equipment to 

the above conditions, and…

  

 

¾

 

Turn on the pump.  Observe the SVRS response.  Make sure to notice the 
peak vacuum level on the SVRS vacuum gauge.  If the peak vacuum level 
exceeds 10” Hg, the SVRS will require adjustment  (See Item 2. below).  

 

 

The Vac-Alert

TM

 SVRS unit is designed for systems that operate at vacuum 

levels less than 15” Hg.  Do not install a Vac-Alert

TM

 SVRS unit on any 

system that operates at a vacuum level above 15” Hg.  See Initial System 
Preparation for options on how to lower system operating vacuum level. 

 

 

2.

 

NOTE

:  Each SVRS comes factory set to remain closed (non-venting) for 

vacuum levels up to 10” Hg. 

 

¾

 

If the pump start-up test indicates a vacuum level above 10” Hg, the SVRS 
will either leak air into the system momentarily, and then re-seal, or the 
SVRS may lock open in the venting position.  Given a start-up vacuum in 
excess of 10” Hg, or the SVRS is allowing too much air to leak into the 
system, the SVRS will need adjustment for site-specific vacuum levels.   

 

¾

 

If the pump start-up test indicates a vacuum level of less than 10” Hg,  
and the SVRS is not leaking air into the system, the SVRS should 
not need any further adjustment. 

 

SVRS ADJUSTMENT 

 
The SVRS is field adjustable for vacuum levels from 0” Hg to 15” Hg. As previously 
stated each unit is shipped from the factory set at about 10” Hg.  

To adjust the  

Vac-Alert

TM

 unit for site-specific vacuum conditions proceed as follows:

 

 

1.

 

NOTE

 -Before making any adjustment to the SVRS spring compression screw, 

make sure the pump is turned off and the Vac-Alert

TM

 unit is in the open (venting) 

position.  The SVRS can be placed in the open position from the vent end (gray 
end) by utilizing a screwdriver.  Remove the vent screen and place the screwdriver 

Содержание VA-2000

Страница 1: ...Safety Vacuum Release System Installation Instructions Model VA 2000 Vac AlertTM Industries LLC 775 8th Court Suite 4 Vero Beach FL 32962 www vac alert com April 29 2011...

Страница 2: ...ation o VAC ALERT MODEL VA 2000S Submerged The Vac AlertTM Model VA 2000S is a Safety Vacuum Release System SVRS designed for submerged suction applications Submerged suction in this case applies to a...

Страница 3: ...s located more than 42 above pool or spa water level contact your Vac AlertTM representative for further instructions For applications where the pump is located more than 24 below pool or spa water le...

Страница 4: ...at each end DO NOT DROP THE UNIT The Installation Instructions DVD and Quick Installation Guide are located in the box stowed between the box and the lower polystyrene insert If the outer package appe...

Страница 5: ...flow coming from the main drain line If the vacuum level is over 15 see previous suggestions for lowering system running vacuum level NOTE Do not use a flow restricted test valve or a slow acting tes...

Страница 6: ...o mount the SVRS off the installed tee A reducing bushing may also be required to mate the 1 1 2 diameter SVRS to the tee fitting installed Utilize pipe nipples to join fittings in a close coupled fas...

Страница 7: ...em Preparation for options on how to lower system operating vacuum level 2 NOTE Each SVRS comes factory set to remain closed non venting for vacuum levels up to 10 Hg If the pump start up test indicat...

Страница 8: ...ion setting is reached then back the adjustment screw off counter clockwise one revolution The adjustment screw must be positioned properly between the two travel stops to set the Vac AlertTM unit for...

Страница 9: ...dry running of self priming pumps where pump suction lift is less than 42 To make sure the unit is working properly turn off the pump and place the Vac AlertTM SVRS unit in the open venting position W...

Страница 10: ...valve is an optional alternative to a pole mounted test mat Each Vac AlertTM SVRS unit must be tested three 3 times to ensure proper adjustment and operation Where a hydro static valve is present the...

Страница 11: ...ain drain blockage b Using the installed test valve or a pole mounted test mat conduct routine testing of the SVRS device to ensure proper adjustment of the unit The Vac AlertTM Model VA 2000 SVRS uni...

Страница 12: ...s operate in a dry state Any indication that the unit is flooded or water logged as evidenced by water leakage from the SVRS unit requires immediate service attention Immediately shut down the pool or...

Страница 13: ...14...

Страница 14: ...l m m m m l l l l m m m l l...

Страница 15: ...l l l...

Страница 16: ...sceration Under no circumstances should any child ever be left unattended at or by any body of water Never sit lay or swim near or by suction ports suction ttings or main drains THIS PRODUCT IS 3RD PA...

Страница 17: ...ION LOCATION INFORMATION Name of Purchaser ________________________________________________________________ Installation Address _______________________________________________________________ I have...

Отзывы: