ENGLISH
45
DISPLAY
DATA
FUNCTION
DEFAULT MEMO
FrEn
Brake Function
5
1 - 1 0
When a sliding motor is used with a very heavy gate, because of the inertia,
the gate does not block immediately when stopped and its motion can last for
another 10 cm, compromising the working of the safety devices.
This menu allows enabling the brake function thanks to which it is possible to
block immediately the gate after a control or the intervention of a safety
device.
The brake power is proportional to the set value
WARNING: each braking entails a mechanical stress to the components
of the motor. We suggest to set the minimum value with which there
is a satisfactory stop distance.
0
Function deactivated
rA .A P
Slow down in opening
1 5
0 - 1 00
This menu allows regulating the percentage of the ride/drive that is
carried out at reduced speed during the last opening stretch
rA .Ch
Slow down in closing
1 5
0 - 1 00
This menu allows regulating the percentage of the ride/drive that is
carried out at reduced speed during the last closing stretch
St .A P
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a Start
command during the opening phase
PA US
PA US
The gate stops and goes to pause
ChiU
The gate immediately starts closing
no
The gate go on with the opening phase (command is ignored)
St .Ch
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the closing phase
StoP
StoP
The gate stops and its cycle is considered as finished
A PEr
The gate opens again
St .PA
Start command during the pause
This menu allows fixing the control unit conduct in case it receives a
Start command when the gate is open during its pause phase
ChiU
ChiU
The gate starts closing
no
Command is ignored
PA US
The pause time is reset (
Ch.A U
)
SP.A P
Pedestrian Start during the partial opening phase
This menu allows fixing the control unit conduct in case it receives a
Pedestrian Start command during the partial opening phase.
WARNING: a Start command in any phase of partial opening
will cause the total opening; the Start Pedestrian command is
always ignored during a total opening
PA US
PA US
The gate stops and goes to pause
ChiU
The gate immediately starts closing
no
The gate goes on with the opening phase (command is ignored)