10 - EMERGENCY MAN PRESENT OPERATION
This operational mode can be used to move the gate in
Man Present mode
in particular cases, such as installation/maintenance or in the
case of malfunctioning of photocell, edge, limit switches or encoder.
To start the “emergency” dead man operating mode activate the start command (START) for 3 seconds.
Note:
if the
Strt
parameter is set as
StA n
, the Start command (from the terminal block or remote control) moves the gate in the
open and closed directions alternatively (unlike the normal Man Present mode).
Emergency man present mode ends after 10 seconds of the gate not moving.
9 - INSTALLATION MENÙ (SEt)
This menu allows you to perform the movements of the gate
needed during installation.
The automatic learning procedure enables to save run limits
based on data collected by the encoder.
The manual handling procedure allows to control the gate in hold
to run mode in special cases such as during
installation/maintenance or a malfunction of the photocells or
edges
m
CAUTION: ATTENTION: before proceeding, make sure
to position the mechanical stops and the limit sensors
correctly.
1.
Press and hold the
OK
key until the display shows
-SEt
2.
Release the
OK
key: the display shows
ESC
(only press the
OK
key if it is desired to exit this menu)
3.
Use the keys
h
and
i
to select the menu
Mov
to activate
manual handling or
A PPr
to start the automatic learning
procedure of the run limits.
4.
Press
OK
to start the selected procedure
9.1 - AUTOMATIC LEARNING OF THE RUN
LIMITS
m
CAUTION: to perform the self-learning procedure it is
necessary to disable the ADI interface by means of the
menu i.Adi . If some safeties are controlled by means of the
ADI module, they will not be active during the self-learning
NOTE:
during the self-learning the slowdown in the limit switch
area is not active. To slowdown the motor press the button
i
of
the control unit or activate the command START P. (cabled or
radio) when the gate comes near to the limit switch.
5.
The display shows the control panel and the automatic
learning procedure of the run limits starts.
5.1
Gate closing is activated until the closing limit switch is
reached.
5.2
Gate opening is activated until the opening limit switch
is reached.
5.3
Gate closing is activated until the closing limit switch is
reached.
6.
At the end of the automatic learning procedure, the control
unit automatically exits this menu and returns to normal
operation.
9.2 - MANUAL HANDLING
m
WARNING: when this procedure is activated the
safeties are not active.
5.
The display shows
MA n
6.
Press and hold the
h
key to open the gate or the
i
button to
close the gate
7.
Release the button to stop the gate
8.
To exit this menu, press
OK
.
NOTE: If the motor is inactive for more than one minute
the procedure terminates automatically.