ENGLISH
37
4.7 - SAFETY RIBBONS
The control unit considers two kinds of safety ribbons,
depending on the terminal to which they are connected:
•
Type 1
: when type 1 safety ribbons operate during
the gate opening phase, the control unit will close the doors
for 3 seconds, then it stands still; when type 1 safety ribbons
operate during the gate closing phase, the control unit will
stand still immediately. The direction of the gate at next
command of START or PEDESTRIAN START depends upon the
parameter STOP (it inverts or continues the motion).
If the input STOP is disabled, the command makes the motion
continue in the same direction.
•
Type 2
: when type 2 safety ribbons operate during the gate
opening phase, the control unit will stand still immediately;
when type 2 safety ribbons operate during the gate closing,
the control unit will open the doors for 3 seconds, then it will
stand still. The direction of the gate at next command of
START or PEDESTRIAN START depends upon the parameter
STOP (it inverts or continues the motion). If the input STOP
is disabled, the command makes the motion continue in the
same direction.
Both the input can manage the classic safety edge with n.c.
contact and the conductive rubber safety edge with 8,2 kohm
nominal resistance.
Connect type 1 safety ribbons cables between terminals
M7
and
M9
of the control unit.
Connect type 2 safety ribbons cables between terminals
M8
and
M9
of the control unit.
In order to meet the requirements of the EN12978 rules, it is
necessary to install safety edges controlled by a control unit
continuously checking the proper working. If using control units
suited to the test by power outage, connect the power supply
cables of the control unit between terminals
M11
and
M12
of
the control unit.
Otherwise, connect them between terminals
M10
and
M11
.
m
WARNING:
• Make use of safety ribbons having outputs with normally
close contact.
• Outputs of same kind safety ribbons must be connected in
series.
4.8 - EXTERNAL AERIAL
We suggest to use the external aerial (model: ANS433) in
order to guarantee the maximal range.
Connect the antenna hot pole to terminal
A2
of the control unit
and the braiding to terminal
A1
.
4.5 - STOP
For a better safety, you can fit a stop switch that will cause the
immediate gate stop when activated. This switch must have a
normally close contact that will get open in case of operation.
In case the stop switch is operated while the gate is open, the
automatic closing function will always be disabled. To close the
gate again, you will need a start command.
Connect the stop switch cables between terminal
M3
and
M4
of
the control unit.
The STOP switch function can be activated by means of a
remote control stored on channel 3 of MRx receiver
4.6 - PHOTOCELLS
The control unit considers two kinds of photocells, depending on
the terminal to which they are connected:
•
Photocell 1:
that is to say, photocells installed on the gate
inner side, which are active both during the opening and the
closing phase. When photocells 1 operate, the control unit
stops the gate; as soon as the photocell beam is free, the
control unit will open the gate completely.
m
WARNING: Type 1 photocells must be installed so
that they completely cover the opening area of the gate.
•
Photocell 2:
that is to say, photocells installed on the external
gate side and which are active during the closing phase only.
When photocells 2 operate, the control unit opens the gate
immediately, without waiting for release.
PD19 control unit supplies a 24VAC power supply to photocells
and it can perform a photocell operation test before starting the
gate opening phase. Photocell power terminals are protected by
an electronic fuse that stops current in case of overload.
• Connect power supply cables of photocells transmitter
between terminals
M11
and
M12
of the control unit.
• Connect power supply cables of photocells receiver between
terminals
M10
and
M11
of the control unit.
• Connect receiver output of photocells 1 between terminals
M5
and
M9
of the control unit and receiver output of
photocells 2 between terminals
M6
and
M9
of the control
unit.
Use outputs having normally closed contact.
m
ATTENZIONE:
• If several couples of same kind photocells are mounted,
their outputs must be connected in series.
• In case of reflection photocells, power supply must be
connected to terminals
M11
and
M12
of the control unit to
carry out the operation test.