IMPORTANT REMARKS
For any installation problem please contact our Customer Service
at the 39-0172.812411 operating Monday to Friday
from 8:30 to 12:30 and from 14:00 to 18:00.
V2 has the right to modify the product without previous notice;
it also declines any responsibility to damage or injury to people or
things caused by improper use or wrong installation.
• This instruction manual is only for qualified technicians, who
specialize in installations and automations.
• The contents of this instruction manual do not concern the end
user.
• Every programming and/or every maintenance service should
be done only by qualified technicians.
• The installer must provide for a device (es. magnetotermical
switch) ensuring the omnipolar sectioning of the equipment
from the power supply. The standards require a separation of
the contacts of at least 3 mm in each pole (EN 60335-1).
• After making connections on the terminal board, use one
hose clamp to fix dangerous voltage wires near the terminal
board and another hose clamp to fix safety low voltage wires
used for accessories connection; this way, in case of accidental
detachment of a conducting wire, dangerous voltage parts will
not come into contact with safety low voltage ones.
• The plastic case has an IP55 insulation; to connect flexible or
rigid pipes, use pipefittings having the same insulation level.
• Also the automation upstream electric system shall comply with
the laws and rules in force and be carried out workmanlike.
COMPATIBILITY
The device LUX2+ is compatible with the following control units:
CITY1-EVO from version 1.0 onwards
CITY1-ECD from version 2.4 onwards
CITY2+ from version 2.3 onwards
CITY4 from version 2.2 onwards
INSTALLATION
LUX2+ is an optional module that allows you to increase the
capabilities of the V2 control unit controlling two independent
relay outputs.
The outputs are programmable with 5 different functions via the
programming menu i.Adi of the control unit.
m
ATTENTION: the installation of the device must be
performed with the power supply of the control unit
disconnected.
Position the card LUX2+ inside the box of the control unit and
connect the two ADI connectors (LUX2+ control unit) via the flat
cable supplied (Fig.1).
Power on the control unit: the green led on the LUX2+ module
begins to blink, indicating that the device is active.
Perform wiring and proceed with the programming of the
operating parameters.
WIRING
On the device there are 3 terminal blocks:
M1
relay 1 output
M2
output for powering low voltage devices
M3
relay 2 output
If the module has to control low voltage lights, make the
connections as shown in figure 2.
ATTENTION: the voltage supplied by the exit M2 depends
on the control unit:
• 230V-120V control units
g
M2 = 20 Vdc - 100mA
• 24V control units
g
M2 = 12 Vdc - 100mA
If the module has to control lights or other devices
(e.g. electric brake) with 230V/ 120V make the connections as
shown in figure 3.
LEDS
On the device there are 3 signalling leds:
FUNCTION
: green led that flashes when LUX2+ is active
Ch1
: red led that lights up when the relay 1 output is closed
Ch2
: red led that lights up when the relay 2 output is closed
USE OF THE PROGRAMMING KEYS
The programming of the functions is performed by means of a
configuration menu, accessible via the 3 keys
h
(UP),
i
(DOWN)
and
OK
beneath the display of the control unit.
Below is a table that describes the functions of the keys:
Press and release the key
OK / MENU
Press and release the key
h
/ UP
Press and release the key
i
/ DOWN