Timer mode:

it is similar to the standard mode but the gate

stays open (completely or partially) while the contact is closed 
on input; as soon as the contact is open the pause time count 
down will start, after which the gate will be closed again. 
This function allows programming the gate opening time 
during the day, by making use of an external timer. 
Automatic closing must be enabled.

In all modes, inputs must be connected to devices having 
normally open contacts.

Connect cables of device controlling the first input between 
terminals 

1

and 

4

of the control unit.

Connect cables of device controlling the second input between
terminals 

2

and 

4

of the control unit.

The first input function can also be activated by pressing UP key
outside the programming menu or by means of a remote control
stored on channel 1 (see relevant instructions of MR1 receiver).

The second input function can also be activated by pressing
DOWN key outside the programming menu or by means of a
remote control stored on channel 2.

PLUG IN RECEIVER

Pd8

control unit is suitable for plugging in a Personal Pass MR1

receiver having a high-sensitivity super-heterodyne architecture.

WARNING: it is necessary to turn off the control unit 

power before doing the operations mentioned here below.
Pay attention to the way you connect the removable
modules.

MR1 module receiver is provided with 4 channels and each of
them is suitable for a command of 

Pd8

control unit:

CHANNEL  1  

쩚쩛

START

CHANNEL  2  

쩚쩛

PEDESTRIAN START 

CHANNEL  3  

쩚쩛

STOP

CHANNEL  4  

쩚쩛

FOR FUTURE USES 

WARNING: Before programming 4 channels and 

function logics read carefully the instructions of MR1.

EXTERNAL AERIAL

We suggest to use the external aerial (model: ANSGP433) in
order to guarantee the maximal range.
Connect the antenna hot pole to terminal 

20

of the control unit

and the braiding to terminal 

21

.

CONTROL PANEL

When power is on, the control unit checks that display correctly
operates by switching on all segments for 1.5 sec. 

8.8.8.8

.

Firmware version, e.g. 

Pr I.9

, will be viewed in the following 

1.5 sec. Panel will be viewed upon completion of this test.

The control panel represents the physical status of the 
terminal board contacts and of the program mode keys: if the
upper vertical segment is on, the contact is closed; if the lower
vertical segment is on, the contact is open (the above picture
shows an instance where the inputs START, START P, FOTO 1,
FOTO 2,COSTA 1, COSTA 2 and STOP have all been correctly
connected).

Points being among display digits show the status of
programming push-buttons: as soon as a push-button is pressed,
its relevant point turns on. 

The arrows on the display left side show the status of the ends
of stroke. The arrows go on when the related limit sensor 
indicates that the gate is completely closed or open.

The arrows on the display right side show the gate status:
• The highest arrow turns on when the gate is into its opening 

phase. If it blinks, it means that the opening has been 
caused by a safety device (border or obstacle detector).

• The central arrow shows that the gate is on pause. If it 

blinks, it means that the time countdown for the automatic 
closing has been activated. 

• The lowest arrow blinks when the gate is into its closing 

phase. If it blinks, it means that the closing has been 
caused by a safety device (border or obstacle detector).

Содержание Gold Series

Страница 1: ...DI PESO CENTRALE DI COMANDO DIGITALE INCORPORATA 230V 120V ELECTRO MECHANICAL IRREVERSIBLE RACK ACTUATOR FOR SLIDING GATES UP TO 600 400 KG BUILT IN DIGITAL CONTROL UNIT OPERATEUR ELECTROMECANIQUE 230...

Страница 2: ...ESCRIPTION OF THE CONTROL UNIT 31 INSTALLATION 31 POWER SUPPLY 31 MOTOR 31 BLINKER 31 PHOTOCELLS 31 SAFETY RIBBONS 32 END OF STROKE 32 STOP 32 ACTIVATION INPUTS 32 PLUG IN RECEIVER 33 EXTERNAL AERIAL...

Страница 3: ...well as any local rule in force Also the automation upstream electric system shall comply with the laws and rules in force and be carried out workmanlike The door thrust force adjustment shall be meas...

Страница 4: ...00D 230V GOLD400DM 230V GOLD400D 120V GOLD400DM 120V Gate maximum weight 600 Kg 600 Kg 400 Kg 400 Kg Power supply 230V 50Hz 120V 60Hz 230V 50Hz 120V 60Hz Maximum power 500 W 500 W 350 W 400 W Idling c...

Страница 5: ...late will be fixed Provide a channel for two hoses that will house the cables in the main hole D on the counter plate Such counter plate shall be fixed to the ground by means of two anchors next to th...

Страница 6: ...ly in order to be distinguished from each other RED MAGNET CLOSING LIMIT SWITCH BLUE MAGNET OPENING LIMIT SWITCH INSTALLING THE MECHANICAL LIMIT SWITCHES Install limit switches on the rack and fix the...

Страница 7: ...and impacts against the safety stroke end i e wrong regulation of the limit switches and a manual unclamp would be necessary before using the above procedure you have to replace the leaf setting away...

Страница 8: ...us alternate current motor Max available power is 700W The motor comes connected already to terminals 15 16 and 17 by means of a polarized connector CAUTION Never reverse the connector BLINKER Pd8 con...

Страница 9: ...of same kind safety ribbons must be connected in series END OF STROKE Limit sensors come connected already to terminals 22 23 24 and 25 by means of a polarized connector CAUTION Never reverse the conn...

Страница 10: ...4 channels and function logics read carefully the instructions of MR1 EXTERNAL AERIAL We suggest to use the external aerial model ANSGP433 in order to guarantee the maximal range Connect the antenna...

Страница 11: ...of available options When you enter into a function menu the current active option will be viewed you can scroll all available options through DOWN and UP keys By pressing the MENU key you will activa...

Страница 12: ...en the procedure is started up The gate will be activated in opening direction until the stop end or the opening end of stroke is reached In case the sensors have not been enabled or if you realize th...

Страница 13: ...1 To avoid that the door does not close completely we recommend to setup a longer time than t APP opening time LOADING OF DEFAULT PARAMETERS If necessary it is possible to restore all the parameters t...

Страница 14: ...it begins moving the initial inertia must be faced therefore if your gate is quite heavy it could not move In case the SPUNTO pickup function is activated for the first 2 seconds of motion of each do...

Страница 15: ...n case it receives a Start command when the gate is open during its pause phase ChiU the gate starts closing no command is ignored Select option ChiU to set up the step by step operation logic Select...

Страница 16: ...d therefore a time shorter than CH AU is generally used Ch AU will be used when no is set up As for semi automatic operation this function is not active Blinker during pause time Blinker usually opera...

Страница 17: ...with single plate clutch is installed on a very heavy gate owing to inertia the gate does not stop immediately and it can move about ten centimetres reducing safety 0 the brake function is never activ...

Страница 18: ...safety devices In order to achieve a safer operation for the user the unit performs a safety devices operational test before a normal working cycle If no operational faults are found the gate starts m...

Страница 19: ...only for the time necessary to recover the actually covered journey This could be not sufficient particularly in the case of very heavy gates as because of the inertia at the inversion moment the gate...

Страница 20: ...rections to carry out do not quit the programming Si end of programming THE INSERTED DATA HAVE BEEN MEMORIZED THE CONTROL UNIT IS READY TO BE USED Automatic Learning of the Operation Time This menu wi...

Страница 21: ...ou can alternate the display of thousands or units Area 2 is the reading of the number of cycles before the next request for service its value is rounded down to the hundreds Area 3 is the setup of th...

Страница 22: ...any obstacle If you set on 0 obstacle detection will be disabled WARNING apart from any setup sensitivity value this system will detect an obstacle only if the gate is stopped therefore no obstacle b...

Страница 23: ...no Slow down disabled St AP Start in opening PAUS no Start command is not available ChiU Command close gate PAUS Stop the gate and goes in pause St Ch Start in closing StoP Stop Start command stop th...

Страница 24: ...vices no no Function not active Foto Test enabled only for photocells CoSt Test enabled only for safety edges Ft Co Test enabled either for photocells or for safety edges CoS1 no Si Border 1 input fix...

Страница 25: ...4 VAC for photocells and other accessories 11 12 Photocell TX power supply for functional test 13 14 Flashing light 230VAC 40W Pd8 120VAC 40W Pd8 120V 15 16 17 Motor 18 Neutral 230 VAC 120VAC 19 Power...

Отзывы: