Error 2

When a Start command is given and the gate does not open and
the following writing appears on display:

It means that triac test failed.
Before sending the control unit to V2 S.p.A. for repair, be sure
that motors have been properly connected. 

Error 3

When a Start command is given and the gate does not open and
the following writing appears on display:

It means that the photocell test failed.

1.

Be sure that no obstacle interrupted the photocell beam 
when the Start command was given.

2.

Be sure that photocells, as enabled by their relevant menus, 
have been installed actually.

3.

If you have photocells 2, be sure that 

Fot2

menu item is on

CF.CH

.

4.

Be sure that photocells are powered and working; when you 
interrupt their beam, you should hear the relay tripping.

Error 4

When a Start command is given and the gate does not open (or
does a partial opening) and the following writing appears on
display:

It means that the end of stroke is damaged or that the wiring
that connects the sensor to the control unit is broken.
Change the end of stroke sensor or the broken wiring.
If the error persists send the control unit to V2 S.p.A. for repair.

Error 5

Once given a start control, the gate does not open and the
display shows:

It means that the test of the safety edges failed. Make sure that
the control unit driving the safety edges is correctly connected
and properly working. Make sure that the safety edges enabled
by menu are actually installed.

Too long pre-blinking

When a Start command is given and the blinker switches on
immediately but the gate is late in opening, it means that the
setup cycle count down expired and the control unit shows that
service is required.

OBSTACLE SENSOR OPERATION

Pd8

control unit is equipped with a sophisticated system that

allows detecting if there is any obstacle stopping the gate
motion. The sensitivity of this system can be adjusted through
the 

Sens

menu: the higher is the setup value, the prompter will

be the control unit intervention if there is any obstacle. If you set
on 0, obstacle detection will be disabled.

WARNING: apart from any setup sensitivity value, this 

system will detect an obstacle only if the gate is stopped; 
therefore, no obstacle braking the gate without stopping
it will be detected. In addition, this system does not work
when the gate move at slowed down speed.

The control unit reaction in case an obstacle is detected depends
on the 

t.rAL

menu setup and on the moment when such

obstacle is detected.

Slowing down disabled

The door motor on which an obstacle is detected will stop
pushing and, for a second fraction, it will be given the command
to go backwards, so not to keep its gears under stress.

Slowing down enabled

Obstacle detection will be performed only if the gate move at a
normal speed. The gate will stop and it will be given the 
command to go backwards for 3 seconds, to take out the
obstacle detected. The following Start command will let the 
former gate motion start again. In case the slowing down phase
has already begun, no obstacle will be detected and this kind of
situation cannot be considered as dangerous since the motor,
when working according to its slowing down function, will push
the obstacle with a very low pressure.

OPERATION DEFECTS

This paragraph shows some possible operation defects, along
with their cause and applicable remedy.

MAINS led does not switch on 

It means that there is no voltage on 

Pd8

control unit card.

1.

Before acting on the control unit, disconnect through the 
disconnecting switch on the power line and remove the 
power supply terminal.

2.

Be sure that there is no voltage break upstream the control 
unit.

3.

Check whether the fuse is burnt-out, if so replace it with 
same value.

OVERLOAD led is on

It means that there is an overload on accessory power supply.

1.

Remove the extractable part containing terminals 1 to 12. 
OVERLOAD led will switch off.

2.

Remove the overload cause.

3.

Reinsert the terminal board extractable part and check that 
this led is not on again.

Error 1

The following writing appears on display when you exit from 
programming:

It means that changed data could not be stored.
This kind of defect has no remedy and the control unit must be
sent to V2 S.p.A. for repair.

Содержание Gold Series

Страница 1: ...DI PESO CENTRALE DI COMANDO DIGITALE INCORPORATA 230V 120V ELECTRO MECHANICAL IRREVERSIBLE RACK ACTUATOR FOR SLIDING GATES UP TO 600 400 KG BUILT IN DIGITAL CONTROL UNIT OPERATEUR ELECTROMECANIQUE 230...

Страница 2: ...ESCRIPTION OF THE CONTROL UNIT 31 INSTALLATION 31 POWER SUPPLY 31 MOTOR 31 BLINKER 31 PHOTOCELLS 31 SAFETY RIBBONS 32 END OF STROKE 32 STOP 32 ACTIVATION INPUTS 32 PLUG IN RECEIVER 33 EXTERNAL AERIAL...

Страница 3: ...well as any local rule in force Also the automation upstream electric system shall comply with the laws and rules in force and be carried out workmanlike The door thrust force adjustment shall be meas...

Страница 4: ...00D 230V GOLD400DM 230V GOLD400D 120V GOLD400DM 120V Gate maximum weight 600 Kg 600 Kg 400 Kg 400 Kg Power supply 230V 50Hz 120V 60Hz 230V 50Hz 120V 60Hz Maximum power 500 W 500 W 350 W 400 W Idling c...

Страница 5: ...late will be fixed Provide a channel for two hoses that will house the cables in the main hole D on the counter plate Such counter plate shall be fixed to the ground by means of two anchors next to th...

Страница 6: ...ly in order to be distinguished from each other RED MAGNET CLOSING LIMIT SWITCH BLUE MAGNET OPENING LIMIT SWITCH INSTALLING THE MECHANICAL LIMIT SWITCHES Install limit switches on the rack and fix the...

Страница 7: ...and impacts against the safety stroke end i e wrong regulation of the limit switches and a manual unclamp would be necessary before using the above procedure you have to replace the leaf setting away...

Страница 8: ...us alternate current motor Max available power is 700W The motor comes connected already to terminals 15 16 and 17 by means of a polarized connector CAUTION Never reverse the connector BLINKER Pd8 con...

Страница 9: ...of same kind safety ribbons must be connected in series END OF STROKE Limit sensors come connected already to terminals 22 23 24 and 25 by means of a polarized connector CAUTION Never reverse the conn...

Страница 10: ...4 channels and function logics read carefully the instructions of MR1 EXTERNAL AERIAL We suggest to use the external aerial model ANSGP433 in order to guarantee the maximal range Connect the antenna...

Страница 11: ...of available options When you enter into a function menu the current active option will be viewed you can scroll all available options through DOWN and UP keys By pressing the MENU key you will activa...

Страница 12: ...en the procedure is started up The gate will be activated in opening direction until the stop end or the opening end of stroke is reached In case the sensors have not been enabled or if you realize th...

Страница 13: ...1 To avoid that the door does not close completely we recommend to setup a longer time than t APP opening time LOADING OF DEFAULT PARAMETERS If necessary it is possible to restore all the parameters t...

Страница 14: ...it begins moving the initial inertia must be faced therefore if your gate is quite heavy it could not move In case the SPUNTO pickup function is activated for the first 2 seconds of motion of each do...

Страница 15: ...n case it receives a Start command when the gate is open during its pause phase ChiU the gate starts closing no command is ignored Select option ChiU to set up the step by step operation logic Select...

Страница 16: ...d therefore a time shorter than CH AU is generally used Ch AU will be used when no is set up As for semi automatic operation this function is not active Blinker during pause time Blinker usually opera...

Страница 17: ...with single plate clutch is installed on a very heavy gate owing to inertia the gate does not stop immediately and it can move about ten centimetres reducing safety 0 the brake function is never activ...

Страница 18: ...safety devices In order to achieve a safer operation for the user the unit performs a safety devices operational test before a normal working cycle If no operational faults are found the gate starts m...

Страница 19: ...only for the time necessary to recover the actually covered journey This could be not sufficient particularly in the case of very heavy gates as because of the inertia at the inversion moment the gate...

Страница 20: ...rections to carry out do not quit the programming Si end of programming THE INSERTED DATA HAVE BEEN MEMORIZED THE CONTROL UNIT IS READY TO BE USED Automatic Learning of the Operation Time This menu wi...

Страница 21: ...ou can alternate the display of thousands or units Area 2 is the reading of the number of cycles before the next request for service its value is rounded down to the hundreds Area 3 is the setup of th...

Страница 22: ...any obstacle If you set on 0 obstacle detection will be disabled WARNING apart from any setup sensitivity value this system will detect an obstacle only if the gate is stopped therefore no obstacle b...

Страница 23: ...no Slow down disabled St AP Start in opening PAUS no Start command is not available ChiU Command close gate PAUS Stop the gate and goes in pause St Ch Start in closing StoP Stop Start command stop th...

Страница 24: ...vices no no Function not active Foto Test enabled only for photocells CoSt Test enabled only for safety edges Ft Co Test enabled either for photocells or for safety edges CoS1 no Si Border 1 input fix...

Страница 25: ...4 VAC for photocells and other accessories 11 12 Photocell TX power supply for functional test 13 14 Flashing light 230VAC 40W Pd8 120VAC 40W Pd8 120V 15 16 17 Motor 18 Neutral 230 VAC 120VAC 19 Power...

Отзывы: