ENGLISH
- 53 -
16 - READING OF CYCLE COUNTER
PD16 control unit counts the completed opening cycles of the
barrier and, if requested, it shows that service is required after a
fixed number of cycles.
There are two counters available:
• A totalizing counter for completed opening cycles thatcannot
be zeroed (option
tot
of item
Cont
)
• A downward counter for the number of cycles before the next
request for service (option
SErv
of item
Cont
).
This counter can be programmed according to the desired value.
The scheme hereafter shows how to read the totalizing counter,
how to read the number of cycles before the next service is
required as well as how to program the number of cycles before
the next request for service (as for the example shown, the control
unit completed no. 12451 cycles and there are no. 1300 cycles
before the next service request.
Area 1
is the reading of the total number of completed cycles;
through
h
and
i
keys, you can alternate the display of thousands
or units.
Area 2
is the reading of the number of cycles before the next
request for service: its value is rounded down to the hundreds.
Area 3
is the setup of this latter counter; if you press once
h
or
i
key, the current counter value will be rounded up or down
to thousands, any following pressure will have the setup be
increased or decreased of 1000 units. The previous displayed
count will get lost.
16.1 - SIGNAL OF SERVICE REQUIRED
As soon as the counter of cycles before the next request for
service is zero, the control unit shows the request for service
through an additional 5-second pre-blinking.
This signal will be repeated at each opening cycle, until the
installer enters into the counter reading and setup menu, and
possibly programs the number of cycles after which the next
service will be requested.
In case no new value is setup (that is to say that the counter value
is left at zero), the signalling function for the service request will
be disabled and no signal will be repeated anymore.
m
WARNING: service operations shall be carried out by
qualified staff only.
3
2
-Cnt
tot
SEru
ESC
-01.3
-02.0
-01.0
-03.0
1
0 12.
.45 1
Содержание 36A022
Страница 2: ...1153 mm 320 mm 287 mm 218 mm 897 mm 1168 mm 374 mm 239 mm 319 mm 897 mm...
Страница 7: ...ITALIANO 5 NIUBA4 NIUBA6...
Страница 11: ...ITALIANO 9 FIG 3 FIG 4...
Страница 13: ...ITALIANO 11 A D E C F F G E A B D C O N M...
Страница 31: ...ITALIANO 29...
Страница 34: ...ITALIANO 32...
Страница 39: ...ENGLISH 37 NIUBA4 NIUBA6...
Страница 43: ...ENGLISH 41 FIG 3 FIG 4...
Страница 45: ...ENGLISH 43 A D E C F F G E A B D C O N M...
Страница 63: ...ENGLISH 61...
Страница 66: ...ENGLISH 64...
Страница 71: ...FRAN AIS 69 NIUBA4 NIUBA6...
Страница 75: ...FRAN AIS 73 FIG 3 FIG 4...
Страница 77: ...FRAN AIS 75 A D E C F F G E A B D C O N M...
Страница 95: ...FRAN AIS 93...
Страница 98: ...FRAN AIS 96...
Страница 103: ...ESPA OL 101 NIUBA4 NIUBA6...
Страница 107: ...ESPA OL 105 FIG 3 FIG 4...
Страница 109: ...ESPA OL 107 A D E C F F G E A B D C O N M...
Страница 127: ...ESPA OL 125...
Страница 130: ...ESPA OL 128...
Страница 131: ......