Table 7-1 Parameter Setting
No.
Parameters
Units
Standard Value
15S
16S
1
Equalization charge voltage
V
54.1
56.5
2
Float charge voltage
V
54.0
56.4
3
4
Standard charge current
A
0.2C
0.2C
5
Charge current limitation
A
20.0
20.0
6
Condition to equalization charge
A
NA
NA
7
Condition to float charge
A
0.05C
0.05C
8
Recovered LLVD voltage
V
50.0
53.3
9
LLVD
V
47.0
50.1
10
BLVD
V
43.2
46.1
11
Temperature compensation for float charge
-mV/°C
NA
NA
Temperature compensation for
equalization charge
-mV/°C
NA
NA
The content in the table is just our suggestion, and actually need to refer to
other related requirements.
The setting items of different chargers will be different.
NOTE
Details refer to the “Operation Manual of the VM UI Software”.
Please recharge the battery before put into use according to this manual.