8 - ELECTRICAL CONNECTIONS
8.12 Frost Protection
Frost protection in combination with ON/Off
thermostat.
•
If ON/Off thermostat is used, protect any rooms where
there is a risk of freezing by using freeze thermostat
(FT). Radiator valves or zone where there is risk of
freezing must be open.
•
Connect frost thermostat in parallel with On/Off room
thermostat (RT
) to ON/Off_OT terminals of control
board connection.
Frost protection in combination with outdoor
temperature sensor.
• Heating system can be protected against freezing in
combination with
1 K
Ω
outdoor temperature sensor.
Radiator valve or zone must be open where there is a
risk of freezing.
• Connect
1 K
Ω
outdoor temperature sensor to "T out"
terminals of control board.
• Frost protection activates when
1 K
Ω
outdoor
temperature sensor reads a temperature lower than
10°F (-10°C ). This can be adjusted using parameter
P30. Circulation pump will switch on and operate
continuously until the outdoor temperature increases
past value set on parameter P30.
FIGURE 8-13 Frost Protection in Combination with
ON/OFF Thermostat
8.11 10 K
Ω DHW Indirect Water Heater
Connect 10 K
Ω DHW indirect tank sensor or thermostat
(TS
) to "
T dhw
" terminals on control board.
10 K
Ω
FIGURE 8-12 10 K
Ω Indirect Water Heater Thermostat
8.13 Pump Anti-Seize Protection
• If the boiler is in standby for 76 hours the pump will run
1 minute to prevent seizing.