Urbana U50I-S Скачать руководство пользователя страница 14

14  |

Unpacking and Initial Setup

Pilot Adjustment 

Screw

Manifold

Pressure Tap

Inlet

Pressure Tap

Stepper

Regulator

Gas Supply Varification

Ensure the appliance is seeing correct gas pressures and 

inputs. Verify the following information matches that of 

the rating label.

 

Pressure taps are located on the valve 

(see image). A 5/16 (8mm) I.D. hose is required to make the 

connections. Check gas pressures as follows: 

1. 

Open inlet pressure tap (half turn) and use 

a manometer to verify inlet pressure with unit 

running on HI. Pressure cannot exceed 1/2 PSIG 

(14" W.C.) or valve damage may occur. Adjust inlet 

pressure as needed and shut pressure tap.

2. 

Open manifold pressure tap (half turn) and connect 

manometer. Verify gas pressures are within range while 

unit is running on HI and LO. Release manometer and 

shut pressure tap. 

Contact your dealer if proper 

pressures cannot be achieved.

 

NOTE: 

Do not spray leak-testing liquid in pressure taps or 

results will not be accurate.

r

Note 

- The fireplace must be isolated from the gas 

supply piping system by closing its equipment shut-

off valve during any pressure testing of that system 

at test pressures in excess of 1/2 psi (3.5 kPa).

Maintenance and Service

Propane

Main Orifice

#49 (U50) / #44 (U70)

Manifold Pressure

10.0” W.C. (2.49 KPa)

Min. Manifold Pressure

6.4” W.C. (1.59 KPa)

Max Supply Pressure

11.0” W.C. (2.74 KPa)

Min. Supply Pressure

10.4” W.C. (2.59 KPa)

U50 Max BTU/hr Input

38,000 BTU/hr (11.1 kW)

U50 Min BTU/hr Input

32,000 BTU/hr (9.38 kW)

U70 Max BTU/hr Input

52,500 BTU/hr (15.3 kW)

U70 Min BTU/hr Input

43,000 BTU/hr (12.6 kW)

Natural Gas

Main Orifice

#32 (U50) / #28 (U70)

Manifold Pressure

3.5” W.C. (0.89 KPa)

Min. Manifold Pressure

1.6” W.C. (0.39 KPa)

Max Supply Pressure

7.0” W.C. (1.74 KPa)

Min. Supply Pressure

4.5” W.C. (1.12 KPa)

U50 Max BTU/hr Input

38,000 BTU/hr (11.1 kW)

U50 Min BTU/hr Input

25,000 BTU/hr (7.33 kW)

U70 Max BTU/hr Input

52,500 BTU/hr (15.3 kW)

U70 Min BTU/hr Input

39,000 BTU/hr (11.4 kW)

 Valve Access

The valve may need to be accessed for service or 
maintenance. Access valve as follows:

1. 

Remove screens

(see page 22).

2. 

Remove trim bezel 

(see page 23).

3. 

 Remove the thumb screws (X2) to release 

the support bracket and gain valve access.

4. 

Replace support bracket securely when finished.

Содержание U50I-S

Страница 1: ...ES WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Installation and service must be performed b...

Страница 2: ...ur s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or t...

Страница 3: ...ividuals If the barrier becomes damaged the barrier shall be replaced with the manufacturer s barrier for this appliance FOR YOUR SAFETY Installation and service must be performed by a qualified insta...

Страница 4: ...URAL GAS PROPANE GAS CERTIFIED TO ANSI Z21 88 CSA 2 33 VENTED GAS FIREPLACE HEATERS CSA 2 17 GAS FIRED APPLIANCES FOR HIGH ALTITUDES This Urbana Fireplace Has been certified for use with either natura...

Страница 5: ...al 22 Initial Setup 23 Media Placement 23 Final Firebox Sealing 24 Final Firebox Sealing Optional 24 Framing and Installation 25 Chase Framing 25 Framing Options 25 Framing Air Gaps 25 Minimum Framing...

Страница 6: ...0 S 47 1194 mm U50 S U70 S 41 1041mm U50 S U70 S 28 15 16 736mm U50 S U70 S 37 939mm U50 S U70 S 17 7 8 455 mm Remove the outer screens barrier to access the rating label and lighting instructions The...

Страница 7: ...control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Read the owner s manual including the section on Remote C...

Страница 8: ...set 3 6 Documentation 10 Outer Screen Set Bezels Switch tool 7 Carrying handles Vermiculite Media 1 Front Heat Deflector WIFI Enabled Remote Control 6 4 1 Media stops only required if an optional medi...

Страница 9: ...been designed to be used with 2X4 lumber Assemble as follows 1 Cut two 2X4 no shorter than 18 this is the minimum distance needed to safely span both handles 2 Bend support leg into position labelled...

Страница 10: ...6 total needed to install the front heat shield come installed on the shield itself use a 1 4 socket to remove the fasteners 2 The front heat shield installs behind the top lip of the cabinet Use the...

Страница 11: ...emove left side and front screen Remove lower bezel and locate the electrical junction box Fireplace Leveling NOTES 1 It is essential to level the unit from proper operation 2 This step is not necessa...

Страница 12: ...S CONNECTIONS TO THIS APPLIANCE NOTE Consult your local authorities codes or the CAN CGA B 149 1 or 2 installation code in Canada or in the USA gas installations follow either local codes or the curre...

Страница 13: ...slots and tilt it inward and out through the opening 6 Route the incoming gas line as desired and connect to the 1 2 NPT female fitting of the shut off valve use gas approved pipe sealant Note the ac...

Страница 14: ...olated from the gas supply piping system by closing its equipment shut off valve during any pressure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa Propane Main Orifice 49 U50 4...

Страница 15: ...Visually check pressure relief gasket for damage or deterioration replace if necessary Clean inner glass see page 20 for removal instructions Use a soft lint free cloth with a mild glass cleaner to e...

Страница 16: ...Fuse Top Light 50 2076 C Power Terminal Bar Covered TILT UP FOR ACCESS D Ground Terminal Bar TILT UP FOR ACCESS E Wiring Clip WARNING ELECTRIC SHOCK RISK DISCONNECT POWER FROM BREAKER BEFORE ACCESSING...

Страница 17: ...pilot flame should cover 1 4 to 1 2 7 to 13mm of the flame sensor see photo The pilot flow adjustment is set to maximum from the factory and should not need adjustment However should the need arise ad...

Страница 18: ...dy to use MAIN BURNER SWITCH Power Vent PV Switch For convenience the fireplace comes pre wired for power vent applications If needed to switch into power vent PV mode locate the PV switch next to the...

Страница 19: ...ft out Maintenance and Service Top Light Replacement Occasionally the top light bulb s good will need to be replaced Replace the top light as follows 1 Disconnect electrical power to the unit 2 Remove...

Страница 20: ...rst burn Use a mild glass cleaner and a soft cloth Depending on the amount of use the glass should require cleaning no more than two or three times a season CAUTION Abrasive cleaners will damage the g...

Страница 21: ...simply lift up and slide forward Magnet Bracket Removal Should the magnet bracket ever need to be replaced it can be removed as follows 1 Remove the front and both side screens 2 Locate the magnet bra...

Страница 22: ...ved be sure back stops are adjusted correctly Remove the front inner glass as follows 1 Remove screens see page 22 2 Remove trim bezel see page 23 3 Loosen the 3 sets of knobs at the bottom of the gla...

Страница 23: ...bezel see page 23 3 Remove front inner glass see page 22 4 Evenly spread out vermiculite onto burner 5 Insert the steel bezel onto the burner platform make sure it s sitting flat 6 Add any additional...

Страница 24: ...adjustments if necessary 3 When unit has cooled blob some clear high temp silicone not included around the 4 corners of the front glass Make sure you fill up any space between the glass and firebox SI...

Страница 25: ...hat vents the chase into the same room It is not permitted to vent the chase into an adjoining room The fireplace cooling system bleeds heat into the chase as opposed to climbing up the front face Thi...

Страница 26: ...trictions be followed in order for the fireplace to be enjoyed safely NOTES Chase may be framed beyond minimum framing for taller ceilings overhangs etc Chase cannot be open to joists or rafters above...

Страница 27: ...r heat release min 12 305mm wide F Distance spanning both finishing edges G Open Top Height from open enclosure heat release to ceiling G Closed Top Surface area calculations do not apply to dimension...

Страница 28: ...Framing illustrations are for example only and are not necessarily meant to be followed exactly HEAT RELEASE FRONT FIREPLACE ON PEDESTAL HEAT RELEASE OPEN FIREPLACE ON PEDESTAL Framing and Installati...

Страница 29: ...s are for example only and are not necessarily meant to be followed exactly HEAT RELEASE TRADITIONAL WITH FALSE CEILING FIREPLACE ON THE FLOOR HEAT RELEASE SIDES ONLY BOTH SIDES FIREPLACE ON PEDESTAL...

Страница 30: ...be followed to ensure safe heat dissipation Combustible materiel is acceptable when constructing the valance Follow the minimum dimensions below Framing Pedestal An optional pedestal can be added to...

Страница 31: ...31 Framing illustrations are for example only and are not necessarily meant to be followed exactly HEAT RELEASE OPEN FIREPLACE ON THE FLOOR WITH PLINTH Framing and Installation...

Страница 32: ...be increased to prevent the mounting screws from penetrating the fireplace cabinet 2 51mm Min 4 102mm Min Clearance From Opening 12 305mm Min Clearance From Heat Release Not shown to scale 12 305mm Mi...

Страница 33: ...to minimize condensation Use at least 3 screws at each vent connection Check periodically that the vents are unrestricted especially the exterior vent cap Venting Considerations 1 A power vent system...

Страница 34: ...xtended above meter regulator assembly I 3 ft 91 cm 3 ft 91 cm Radial clearance around service regulator vent outlet J 12 in 30 cm 9 in 23 cm Clearance to non mechanical air supply inlet to building o...

Страница 35: ...of pipe required measure room height ceiling thickness and vertical rise in an attic or second story Firestops are required at each floor level beyond the first floor ceiling support wall thimble cove...

Страница 36: ...vent termination is not being attached to wood the four wood screws provided should be replaced with material appropriate fasteners 5 For buildings with vinyl siding a vinyl standoff should be instal...

Страница 37: ...nimum Rise U50I S U70I S 79 3 4 Min Vent Height This gas appliance must be direct vented and can t be connected to a chimney flue serving a separate solid burning appliances Clearances to combustibles...

Страница 38: ...d Rigid Venting Manufacturer Trade Name Nominal Sizes ICC EXCELDirect 5 x 8 M G Dura Vent Direct Vent Pro 5 x 8 Selkirk DIRECT TEMP 5 x 8 Sekirk AMP DV 5 x 8 Metal Fab Sure Seal 5 x 8 Refer to the tab...

Страница 39: ...VA WT3 58DVA WTU3 5WT 5DT WT 5DWT 5DWT 5DWT11 Wall thimble 58DVA SC SQSC SC 5DT SC 5DSC 5DSC Storm collar 58DVA WFS 5DT FS 5DFSH Wall Fire stop 58DVA FS 5CS 5DT FS 5DFSP 5DFS 5DSPFS Ceiling Fire stop...

Страница 40: ...ting with aluminum vent tape and apply sufficient self tapping screws Any Urbana Fireplace Flex Starter Adapter DV Flex Venting not supplied Flex End Adapter Any UrbanaApproved Rigid Venting Use gear...

Страница 41: ...ember to consider elbows in the HORIZONTAL plane account for horizontal distance as stated above Use the corresponding exhaust restrictor setting indicated on the graph See the following section in th...

Страница 42: ...member to consider elbows in the HORIZONTAL plane account for horizontal distance as stated above Use the corresponding exhaust restrictor setting indicated on the graph See the following section in t...

Страница 43: ...es Tune the air shutter venturi in conjunction with restrictor WARNING Improperly set restrictor setting can cause overheating issues which can lead to building fire Rotate the dial counter clockwise...

Страница 44: ...SEGMENTED LINER 1 PCE PART USED IN U30 U50 U70 50 3820 U50 INFINITY GLASS BEZEL BLACK 50 3827 U70 INFINITY GLASS BEZEL BLACK 50 3887 PF2 WIFI READY IFC PART USED IN U30 U50 U70 50 3888 PF2 WIFI READY...

Страница 45: ...FUSE PART USED IN U30 U50 U70 Gaskets Part numbers U Series Firebox Glass gasket 20ft 50 3896 U Series Silicone Glass Gasket 4ft 50 3897 U30 Relief Gasket 2 pcs 50 3910 U50 U70 Relief Gasket 2 pcs 50...

Страница 46: ...ame Check sensor hook is not touching pilot hood Check white sensor wire has rm connec on with IFC Check sensor hook for corrosion lm or debris Check pilot for healthly ground check pilot hood con nui...

Страница 47: ...system Ensure ven ng system is properly set up Check ven ng con gura on is approved Check for ven ng obstruc ons Exhaust restrictor se ng Exhaust restrictor se ng too high Reduce exhaust restric on I...

Страница 48: ...TOP LIGHT lumi re sup rieure TOP LIGHT lumi re sup rieure U70 ONLY uniquement contr leur IFC INSIDE l int rieur IFC fil PV N fil PV L fil PV interrupteur r initialisation interrupteur du br leur ante...

Страница 49: ...____________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy NATURAL GAS NAT PROPANE LPG INLET GAS PRESSURE ____...

Страница 50: ...or the dealer including serial number Exclusions An expanded list of exclusions is available at www urbanafireplaces com warranty html This warranty does not cover Damage as a result of improper usag...

Страница 51: ...MANUFACTURED BY SHERWOOD INDUSTRIES LTD 6782 OLDFIELD RD SAANICHTON BC CANADA V8M 2A3 www urbanafireplaces com July 2022 C 16582...

Отзывы: