5 Mechanical installation
5.1 Installation example
SD0000061
B
A
C
E
F
D
Item
Description
A
In-wall cabinet
B
Heat interface unit
C
Underfloor heating manifold
D
Heating supply (primary)
E
Heating return (primary)
F
Cold water from riser (CW)
The above installation example shows a typical installation with
Combi Port E in an in-wall cabinet with an underfloor heating
manifold.
A Uponor Smatrix controller for room temperature control is mounted
and connected to the manifold.
5.2 In-wall installation
Preparations
SI0000295
A
B
C
Item
Description
A
Cabinet body
B
Frame
C
Door
1.
Dismount the frame and door.
2.
Store the frame and door for later mounting.
Adjusting the in-wall cabinet
The in-wall cabinets are adjustable inside the niche in height and
depth.
The niche height is calculated using the floor height and is measured
from the bare floor. The specified floor installation height has to be
set according to the values visible on the feet.
CD0000349
f =
0-200
Dimensions of in-wall mounted
cabinet (width x height x depth
mm)
Niche dimensions in-wall (width
x height x depth mm)
750 x 850 x 150
770 x (850 + 30 + f) x 155
750 x 1200 x 150
770 x (1190 + 30 + f) x 155
Combi Port E
|
Installation and operation manual
|