Control connections
Version: 2020 / V3
Seite: 35
BAMOCAR-PG-D3-700-900
4.4
Signal contact Ready (Solid State Relay) / Ready BTB / RDY
Hardware: Safety circuit with solid state relay contact.
Software: State signal parameter state RDY (0x40 Bit 14)
Ready BTB = logic 1
In case of errors this safety circuit is separated by the relay and the state RDY is set to 0.
Further control units (e.g. BMS, VCU, etc.) may respond.
Contact for max. 48 V / 0.5 A (not short-circuit proof)
Capacitive load: max. 1 µF
Contact
resistance: max. 2 Ω
Ready for BTB
The BTB relay contact is closed.
Not ready
BTB relay contact is open.
Red LED and error messages with
Status 7-segment-LED.
BTB/RDY always insert contact into the safety circuit!
Secure BTB/RDY signal path with 0.5 AF!
BTB function with undervoltage monitoring:
BTB signal even if power voltage is missing.
Programming in NDrive: Parameter BTB Power = without (0x5A
Bit 5
= 1).
No BTB message if power voltage is missing.
Programming in NDrive: Parameter BTB.Power = with (0x5A
Bit 5
= 0).
(see Manual NDrive-x)
Содержание BAMOCAR-PG-D3-700-900
Страница 20: ...Mechanical installation Version 2020 V3 Seite 19 BAMOCAR PG D3 700 900 2 2 Dimensions BAMOCAR PG D3 700 900...
Страница 23: ...Electrical installation Version 2020 V3 Seite 22 BAMOCAR PG D3 700 900 3 2 Circuit diagramm...
Страница 24: ...Electrical installation Version 2020 V3 Seite 23 BAMOCAR PG D3 700 900...
Страница 25: ...Electrical installation Version 2020 V3 Seite 24 BAMOCAR PG D3 700 900 3 3 Connection diagramm...