4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS
4.1 -
Physical data 30RQM 160-520
30RQM
160
180
210
230
240
270
310
330
380
430
470
520
Sound levels
Standard unit
Sound power
(1)
dB(A)
90
91
91
91
92
92
93
93
94
94
94
94
Sound pressure at 10 m
(2)
dB(A)
58
59
59
59
60
60
61
61
62
62
62
62
Standard unit + option 15
(3)
Sound power
(1)
dB(A)
89
90
90
90
91
91
91
92
92
93
93
93
Sound pressure at 10 m
(2)
dB(A)
57
58
58
58
59
59
59
60
60
61
61
61
Dimensions
Length
mm
2410
3604
4797
Width
mm
2253
2253
2253
Height
mm
2322
2322
2322
Unit length with water buffer tank module opt
mm
3604
4798
5991
Operating weight
(4)
Standard unit
kg
1415 1490 1618 1641 2049 2197
2318
2548
3013 3274 3286 3327
Standard unit + option 15
kg
1497 1572 1726 1749 2157
2323
2444
2693 3175 3454 3466 3507
Standard unit + option 15 + option 116W
(3)
kg
1637
1712 1878 1900
2318 2531
2662 2897
3380 3700 3748 3788
Unit + option 15 + option 116W + Water buffer tank module
kg
2585 2656 2821 2844
3257 3471 3598 3833 4312 4643
4692
4732
Compressors
Hermetic Scroll 48,3 r/s
Circuit A
1
1
2
2
2
2
2
2
3
4
4
4
Circuit B
2
2
2
2
2
3
3
4
4
4
4
4
No. of control stages
3
3
4
4
4
5
5
6
7
8
8
8
Refrigerant
(4)
R-410A
Circuit A charge
kg
14,5 22,0
23,0
24,0 27,0 27,0
30,0 33,0
42,0
53,0
54,0 56,0
tCO
2
e
30,3
45,9 48,0 50,1 56,4 56,4 62,6 68,9 87,7 110,7 112,8 116,9
Circuit B charge
kg
23,0 23,0 23,0
24,0
35,0 36,0
48,5
53,0 53,0 53,0
54,0 56,0
tCO
2
e 48,0 48,0 48,0 50,1
73,1
75,2
101,3
110,7 110,7 110,7 112,8 116,9
Control
Smart View Control
Minimum capacity
%
33% 33%
25% 25% 25% 20% 20% 17% 14%
13% 13% 13%
Air heat exchanger
Grooved copper tubes and aluminum fins
Fans
Axial Flying Bird 4 with rotating shroud
Quantity
3
4
4
4
5
5
6
6
7
8
8
8
Maximum total air flow
l/s
13542
18056 18056 18056 22569 22569
27083 27083 31597 36111 36111 36111
Maximum rotation speed
rps
16
16
16
16
16
16
16
16
16
16
16
16
Water heat exchanger
Dual-circuit plate heat exchanger
Water volume
l
15
15
15
19
27
27
35
44
44
44
47
53
Max. water-side operating pressure without hydraulic
module
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic module (option)
Pump, Victaulic screen filter, relief valve, water and air drain valve, pressure
sensors, expansion tank (option)
Pump
Centrifugal pump, monocell, 48,3 rps, low- or high-pressure (as required), single
or dual (as required)
Expansion vessel volume
l
50
50
50
50
80
80
80
80
80
80
80
80
Max. water-side operating pressure with hydraulic
module
kPa
400
400
400
400
400
400
400
400
400
400
400
400
Water connections with or without hydraulic module
Victaulic type
Connections
inch
3
3
3
3
4
4
4
4
4
4
4
4
External diameter
mm
88,9 88,9 88,9 88,9
114,3 114,3 114,3 114,3 114,3 114,3 114,3 114,3
Chassis paintwork
Colour code: RAL 7035
(1) en dB ref=10
-12
W, pondération (A). Valeur d’émission sonore déclarée dissociée conformément à l'ISO 4871 (avec une incertitude de +/-3dB(A)). Mesurée selon ISO
9614-1 aux conditions de fonctionnement nominales EN14511 - mode froid.
(2) en dB ref 20µPa, pondération (A). Valeur d’émission sonore déclarée dissociée conformément à l'ISO 4871 (avec une incertitude de +/-3dB(A)). Pour information,
calculée à partir de la puissance acoustique Lw(A).
(3) Options: 15 = bas niveau sonore, 116W = Module hydraulique pompe double haute pression vitesse variable
(4) Valeurs données à titre indicatif. Se référer à la plaque signalétique de l'unité.
Eurovent certified values