background image

OPERATING CHECKS:

• IMPORTANT INFORMATION REGARDING THE 

REFRIGERANT USED:

This  product  contains  fluorinated  greenhouse  gas 

covered by the Kyoto protocol.
Refrigerant type: R-410A 
Global Warming Potential (GWP): 2088

WARNING:
1.  Any intervention on the refrigerant circuit of this product 

should be performed in accordance with the applicable 

legislation. In the EU, the regulation is called F-Gas, 

N°517/2014.

2.  Ensure that the refrigerant is never released to the 

atmosphere during installation, maintenance or equipment 

disposal.

3.  The deliberate gas release into the atmosphere is not 

allowed. 

4.  If a refrigerant leak is detected, ensure that it is stopped 

and repaired as quickly as possible.

5.  Only  a  qualified  and  certified  personnel  can  perform 

installation operations, maintenance, refrigerant circuit 

leak test as well as the equipment disposal and the 

refrigerant recovering.

6.  The gas recovery for recycling, regeneration or destruction 

is at customer charge.

7.  Periodic leak tests have to be carried out by the customer 

or by third parties. The EU regulation set the periodicity 

here after: 

System WITHOUT 

leakage detection

No 

Check

12 

Months

6 Months

3 Months

System WITH leakage 

detection

No 

Check

24 

Months 12 Months 6 Months

Refrigerant charge/ 

circuit (CO

2

 equivalent)

< 5 Tons

5 ≤

Charge

< 50 Tons

50 ≤

Charge

< 500 Tons

Charge

> 500 

Tons

(1)

Refrigerant charge/ 

Circuit (kg)

R134A

(GWP 1430)

Charge

< 3.5 kg

3.5 ≤

Charge

< 34.9 kg

34.9 ≤

Charge

< 349.7 kg

Charge

> 349.7 kg

R407C

(GWP 1774)

Charge

< 2.8 kg

2.8 ≤

Charge

< 28.2 kg

28.2 ≤

Charge

< 281.9 kg

Charge

> 281.9 kg

R410A

(GWP 2088)

Charge < 

2.4 kg

2.4 ≤

Charge

< 23.9 kg

23.9 ≤

Charge

< 239.5 kg

Charge

> 239.5 kg

HFO’s: R1234ze

No requirement

(1)  From 01/01/2017, units must be equipped with a leakage detection system.

8.  A logbook must be established for equipments subject to 

periodic leak tests. It should contain the quantity and the 

type  of  fluid  present  within  the  installation  (added  and 

recovered), the quantity of recycled fluid, regenerated or 

destroyed, the date and output of the leak test, the 

designation of the operator and its belonging company, 

etc.

9.  Contact your local dealer or installer if you have any 

questions.

PROTECTIVE DEVICE CHECKS:

• 

If no national regulations exist, check the protective 

devices  on  site  in  accordance  with  standard  EN378: 

once a year for the high pressure switches, every five 

years for external relief valves.

The company or organisation that conducts a pressure switch test 

must establish and implement detailed procedures for:

 

-

Safety measures,

 

-

Measuring equipment,

 

-

Values and tolerances for cut-off and discharge devices,

 

-

Test stages,

 

-

Recommissioning of the equipment.

Please  contact  Carrier  Service  for  this  type  of  test.  The  test 

principle set out here by Carrier does not involve removal of the 

pressure switch: 

 

-

Verify  and  record  the  nominal  values  for  activation  of  the 

pressure switches and external relief devices (pressure relief 

valves or rupture discs),

 

-

Be ready to switch off the main disconnect switch of the power 

supply if the pressure switch does not trigger (avoid over-

pressure  or  excess  gas  if  there  are  valves  on  the  high 

pressure side on the recovery air exchangers, for example),

 

-

Connect a pressure gauge protected against pulsations (filled 

with  oil  with  maximum  pointer  if  mechanical),  preferably 

calibrated (the values displayed on the user interface may 

be inaccurate in an instant reading because of the scanning 

delay applied in the control)

 

-

Complete an HP Test as provided by the software (refer to 

the Control IOM for details).

Caution: If the test results in the replacement of the pressure 

switch, it is necessary to recover the refrigerant charge; these 

pressure switches are not installed on Schrader type 

automatic valves.
Visually inspect the protective devices (relief valves, pressure 

switches) at least once a year.
If the machine operates in a corrosive atmosphere, inspect 

the devices more frequently.
Check regularly for leaks and, if detected, have these repaired 

immediately.
Regularly check that the vibration levels remain acceptable 

and close to those at the initial machine start-up.
Before opening a refrigerant circuit, drain and consult the 

pressure indicators.
After an equipment failure, replace the refrigerant in 

accordance with a procedure such as that described in NF 

E29-795,  or  have  a  refrigerant  analysis  carried  out  at  a 

specialist laboratory.
If the refrigerant circuit remains open after an intervention 

(such as a component replacement, etc.):

• Seal the openings if the duration is less than a day;

• If more than one day, charge the circuit with a dry, inert 

gas (e.g. nitrogen)

The objective is to prevent penetration of atmospheric 

humidity and the resulting corrosion of the unprotected 

internal steel walls.

1.4 - 

Repair safety considerations

All  parts  of  the  system  must  be  maintained  by  the  personnel 

responsible for such maintenance, in order to avoid any damage 

or accidents. Faults and leaks must be repaired immediately. An 

authorised  technician  must  remedy  the  fault  immediately. After 

each repair of the unit, check the operation of all protective devices 

and record operating readings for all parameters.
Comply with the regulations and recommendations given in the 

safety standards for refrigerant systems and machines, such as: 

EN 378, ISO 5149, etc.
If a leak occurs or if the refrigerant becomes contaminated (e.g. 

by a short circuit in a motor or freezing of the BPHE), remove the 

complete charge using a recovery unit and store the refrigerant 

in mobile containers. The compressors cannot transfer the whole 

refrigerant charge and can be damaged if used to pump-down. 

The  refrigerant  charge  should  not  be  transferred  to  the  high-

pressure side.
Detect and repair the leak, and recharge the circuit with the full 

charge of R410A indicated on the unit's nameplate. Do not top up 

the refrigerant charge. Only charge liquid refrigerant R-410A at 

the liquid line.

Check the type of refrigerant before adding the full charge to 

the machine.

1 - INTRODUCTION

6

Содержание Carrier 30RQM 160

Страница 1: ...A I N T E N A N C E I N S T R U C T I O N S Original document Reversible air to water heat pump 30RQM 160 520 A 30RQP 160 520 A Unit with low noise option Nominal heating capacity 170 540 kW Nominal...

Страница 2: ...7 Electric power reserve for the user 24 6 APPLICATION DATA 25 6 1 Operating range 25 6 2 Minimum water flow units without hydraulic module 25 6 3 Maximum water flow units without hydraulic module 26...

Страница 3: ...on Option 12 Fan with high static pressure 45 10 4 Installation 45 10 5 Nominal and maximum air flows per circuit A and B for 30RQP sizes 46 10 6 Factory installed duct connection interface on each fa...

Страница 4: ...remove them Fit devices at the valve or drain piping outlets to prevent the penetration of foreign bodies dust building debris etc and atmospheric agents water can form rust or ice These devices as we...

Страница 5: ...t and system All welding operations must be carried out by qualified specialists 30RQM 30RQP units use high pressure R 410A refrigerant the unit operating pressure is above 40 bar the pressure at an a...

Страница 6: ...ure relief valves or rupture discs Be ready to switch off the main disconnect switch of the power supply if the pressure switch does not trigger avoid over pressure or excess gas if there are valves o...

Страница 7: ...hydrocarbons under optimum quality conditions for the products and optimum safety conditions for people property and the environment are described in standard NF E29 795 Any refrigerant transfer and...

Страница 8: ...equipment tools etc If necessary damaged parts must be repaired or replaced See also the section on Maintenance 2 2 Handing and positioning 2 2 1 Handling See the section on Installation safety consid...

Страница 9: ...ine is charged with refrigerant Verify on the unit nameplate that the fluid transported is that recommended for operation and is not nitrogen Compare the complete system with the refrigeration system...

Страница 10: ...gs When designing a system refer to the certified dimensional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixi...

Страница 11: ...nsional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixing points weight distribution points and centre of gra...

Страница 12: ...to the certified dimensional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixing points weight distribution poi...

Страница 13: ...nsional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixing points weight distribution points and centre of gra...

Страница 14: ...e certified dimensional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixing points weight distribution points a...

Страница 15: ...low C Clearance recommended for coil removal Water inlet Water outlet Air outlet do not obstruct Control box 3 4 Installation of multiple heat pumps It is recommended to install multiple heat pumps in...

Страница 16: ...oved copper tubes and aluminum fins Fans Axial Flying Bird 4 with rotating shroud Quantity 3 4 4 4 5 5 6 6 7 8 8 8 Maximum total air flow l s 13542 18056 18056 18056 22569 22569 27083 27083 31597 3611...

Страница 17: ...nger Grooved copper tubes and aluminium fins Fans Axial Flying Bird 4 with rotating shroud Quantity 3 4 4 4 5 5 6 6 7 8 8 8 Maximum total air flow l s 13542 18056 18056 18056 22569 22569 27083 27083 3...

Страница 18: ...at 400 V Current 3 8 A Start up current 20 A Power input 1 75 kW 4 4 Electrical data 30RQP 160 520 30RQP 160 180 210 230 240 270 310 330 380 430 470 520 Power circuit Nominal voltage V ph Hz 400 3 50...

Страница 19: ...mber and registered address Same as above 5 Product s model number Same as above 6 Number of motor poles 2 2 2 2 2 2 2 2 2 2 2 2 7 1 Nominal shaft power output at full load and nominal voltage 400 V k...

Страница 20: ...om the electrical data table to the pump current draw For the high pressure single and dual pump motors for 30RQM 30RQP 160 520 units options 116R and 116V No 2 Description 3 Units 30RQM 30RQP 160 180...

Страница 21: ...ng using an appropriate company 12 Operating conditions for which the motor is specifically designed I Altitudes above sea level m 1000 4 II Ambient air temperature C 40 III Maximum operating temperat...

Страница 22: ...to 2000 m for hydraulic module see paragraph 4 7 in the IOM Presence of hard solid Class AE3 no significant dust present 1 Presence of corrosive and polluting substances class AF1 negligible Competenc...

Страница 23: ...uctor cables in closed conduits standardised routing no 41 Cable with PVC insulation Standard lug Narrow lug Recommended max lug width Section 2 Max length for a voltage drop 5 Cable type 3 Section 2...

Страница 24: ...ical box must ensure that the equipment remains compliant with local regulations In particular precautions must be taken to prevent accidental electrical contact between the circuits supplied by diffe...

Страница 25: ...0RQP units storage and transport minimum and maximum ambient temperatures to respect are 20 C and 52 C These temperature limits shall be considered in case of container shipment 30RQM 30RQP 160 520 un...

Страница 26: ...e Units supplied with a hydraulic module may include an expansion tank which limits the volume in the water loop option 293 The table below gives the maximum loop volume for pure water or ethylene gly...

Страница 27: ...for the maximum permitted water temperature difference conditions 10 K at the minimum water outlet temperature value 5 C 6 8 Pressure drop curves for the exchanger and standard water inlet outlet pipi...

Страница 28: ...nt suitable for the products The heat transfer fluid should be filled using devices fitted to the hydraulic circuit by the installer 7 1 Operating precautions and recommendations Before any system sta...

Страница 29: ...idestemperatureinformationforthewaterexchangerinlet seeControl manual 10 Pressure sensor Note Provides pressure information for the water exchanger outlet see Control manual 11 Check valve if dual pum...

Страница 30: ...p Presence of the stainless steel filter Coupling for expansion vessel option 293 Example Dual pump Presence of the stainless steel filter Coupling for expansion vessel option 293 See legend on the pr...

Страница 31: ...ill periodically start automatically Combination of options for the periods when the machine is in standby mode Ambient unit temperature range 30RQM 30RQP 160 520 without option 116 with option 116 0...

Страница 32: ...is only possible when the units are installed in parallel The master slave assembly is controlled on the water inlet without any additional sensors system return see example 1 Control of Master and Sl...

Страница 33: ...3 4 Stage 4 safety A Variation of the heat pump output with air temperature B Building thermal load C Point of equilibrium between the heat pump output and the building thermal load 7 7 Auxiliary ele...

Страница 34: ...y to clean up the system s hydraulic circuit presence of contaminating solids Perform another reading Compare this value to the initial value A decrease in the pressure drop value indicates that the f...

Страница 35: ...ems 5 and 14 Repeat until all fouling is removed from the filter 8 3 2 Procedure for controlling the pressure differential setpoint Once the circuit has been decontaminated place the water circuit in...

Страница 36: ...re for the water circuit Refer to the cleaning procedure for the water circuit in section 8 3 1 8 5 2 Procedure for controlling the flow Once the circuit is cleaned set the required water flow by adju...

Страница 37: ...maximum flow rate is reduced 8 6 1 30RQM 30RQP high pressure pumps Single pumps Water flow rate l s Manometric head kPa B C D E F 1 30RQM 30RQP 160 180 2 30RQM 30RQP 210 230 240 3 30RQM 30RQP 270 310...

Страница 38: ...P 210 230 3 30RQM 30RQP 240 270 310 4 30RQM 30RQP 330 380 430 5 30RQM 30RQP 470 520 Dual pumps Manometric head kPa B C D E F G H Water flow rate l s 1 30RQM 30RQP 160 2 30RQM 30RQP 180 3 30RQM 30RQP 2...

Страница 39: ...D E 1 30RQM 30RQP 160 180 2 30RQM 30RQP 210 3 30RQM 30RQP 230 4 30RQM 30RQP 240 Sizes 270 520 Available static pressure kPa Water flow rate l s F G H I 5 30RQM 30RQP 270 310 6 30RQM 30RQP 330 380 7 30...

Страница 40: ...kPa F G H I 5 30RQM 30RQP 310 6 30RQM 30RQP 330 380 430 7 30RQM 30RQP 470 8 30RQM 30RQP 520 Dual pumps Sizes 160 230 Available static pressure kPa Water flow rate l s B C D E 1 30RQM 30RQP 160 2 30RQ...

Страница 41: ...axial Flying Bird fans equipped with a rotating shroud and made of composite recyclable material Each motor is fixed with transverse supports The motors are three phase with permanently lubricated bea...

Страница 42: ...kPa on refrigerant side and of 3200 kPa on the water side The water connections of the heat exchanger are Victaulic connections The water heat exchanger is thermally insulated with 19 mm of nitrile fo...

Страница 43: ...are as follows these values may change depending on the suppliers It is therefore recommended that a medium or low temperature installation be commissioned by the manufacturer 9 13 2 Required glycol c...

Страница 44: ...y improve the seasonal efficiency ESEER and SCOP All fans in the same refrigerant circuit are controlled by a single variable speed drive Therefore they operate together at the same rotational speed T...

Страница 45: ...e drop while maintaining an optimized air flow per circuit All fans in the same circuit operating at the same time have the same speed The power supply for fans with a speed of 19 rps is increased com...

Страница 46: ...11441 180 230 9534 11441 9534 11441 240 270 9534 11441 14301 17161 310 330 9534 11441 19068 22882 380 14301 17161 19068 22882 430 520 19068 22882 19068 22882 10 6 Factory installed duct connection int...

Страница 47: ...n protection grilles must always remain in their position inside the ducts Use bellows or flexible sleeves for the duct connection At the outlet of each duct provide an access hatch with a minimum siz...

Страница 48: ...it A kg 16 0 22 2 23 7 25 5 29 2 29 2 34 6 36 8 46 2 55 2 56 7 59 2 tCO2e 33 3 46 3 49 4 53 2 60 9 60 9 72 2 76 9 96 5 115 3 118 3 123 6 Circuit B kg 23 7 23 7 23 7 25 5 37 1 38 5 49 7 55 2 55 2 55 2...

Страница 49: ...B Clearances required for maintenance and air flow C Clearance recommended for coil removal Water inlet Water outlet Control box NOTE Non contractual drawings When designing a system refer to the cer...

Страница 50: ...mm B Clearances required for maintenance and air flow C Clearance recommended for coil removal Water inlet Water outlet Control box NOTE Non contractual drawings When designing a system refer to the c...

Страница 51: ...mm B Clearances required for maintenance and air flow C Clearance recommended for coil removal Water inlet Water outlet Control box NOTE Non contractual drawings When designing a system refer to the c...

Страница 52: ...eater plate heat exchanger 4 Air heat exchanger coils 5 Expansion valve EXV 6 Damage limitation accessory in case of a fire 7 Electric heater to protect the desuperheater against frost not supplied 8...

Страница 53: ...eration C 5 15 Entering water temperature at shut down C 60 Desuperheater Entering water temperature at start up 2 C 25 60 Leaving water temperature during operation C 30 80 Entering water temperature...

Страница 54: ...artial heat recovery 49 Partial heat recovery by desuperheating of the compressor discharge gas Free high temperature hot water production simultaneously with chilled and hot water production 30RQM 30...

Страница 55: ...Compliance with Australian regulations 200 Unit approved to Australian code Conformance with Australian regulations 30RQM 30RQP 160 520 Coil defrost resistance heaters 252 Electric heaters under the...

Страница 56: ...e may be available locally maintenance service industrial site specialist subcontractor The frequency of this maintenance may be monthly or annual depending on the type of check In these cases the fol...

Страница 57: ...at exchanger and pump 30 Taptite M6 screw Pipe supports enclosure variable frequency drive supports 7 H M6 screw Pipe clip 10 H M10 nut Compressor chassis Compressor fixing 30 Oil equalisation screw O...

Страница 58: ...14 397 10 987 34 1981 58 3543 13 415 11 1020 35 2034 59 3624 12 434 12 1053 36 2087 60 3706 11 453 13 1087 37 2142 61 3789 10 473 14 1121 38 2197 62 3874 9 493 15 1156 39 2253 63 3961 8 514 16 1192 4...

Страница 59: ...the unit can be recycled for another purpose 12 3 Fluids to be recovered for treatment Refrigerant Heat transfer fluid depending on the installation water brine solution etc Compressor oil 12 4 Mater...

Страница 60: ...reliminary equipment check Is there any shipping damage If so where Will this damage prevent unit start up The unit is installed level The power supply corresponds to the unit nameplate The electrical...

Страница 61: ...rost protection included if required litres of Water pipes have been fitted an electric heater for trace heating up to the evaporator Return water piping is equipped with a screen filter with a mesh s...

Страница 62: ...The unit starts and operates correctly Temperatures and pressures WARNING Once the machine has been operating for a while and the temperatures and pressures have stabilised record the following Evapor...

Страница 63: ......

Страница 64: ...Check ongoing validity of certificate www eurovent certification com Order No 10018 05 2019 Supersedes order No 10018 11 2018 Manufactured by Carrier SCS Montluel France Manufacturer reserves the righ...

Отзывы: