4.2 -
Physical data 30RQP 160-520
30RQP
160 180 210 230 240 270 310 330 380 430 470 520
Sound levels
Standard unit
Sound power
(1)
dB(A)
90
91
91
91
92
92
93
93
94
94
94
94
Sound pressure at 10 m
(2)
dB(A)
58
59
59
59
60
60
61
61
62
62
62
62
Standard unit + option 15
(3)
Sound power
(1)
dB(A)
89
90
90
90
91
91
91
92
92
93
93
93
Sound pressure at 10 m
(2)
dB(A)
57
58
58
58
59
59
59
60
60
61
61
61
Standard unit + option 15LS
(3)
Sound power
(1)
dB(A)
84
85
86
86
86
87
87
87
88
89
89
89
Sound pressure at 10 m
(2)
dB(A)
52
53
54
54
54
55
55
55
56
57
57
57
Dimensions
Length
mm
2410
3604
4797
Width
mm
2253
2253
2253
Height
mm
2322
2322
2322
Unit length with water buffer tank module opt
mm
3604
4798
5991
Operating weight
(4)
Standard unit
kg
1450 1526 1654 1677 2085
2233 2355
2585
3050 3331 3343 3393
Standard unit + option 15 /15LS
kg
1533
1609 1762 1785
2193 2359
2481 2729
3212 3512 3524 3573
Standard unit + option 15/15LS + option 116W
(3)
kg
1673
1749 1914
1936 2354
2568 2699
2934 3416 3757 3806 3854
Unit + option 15 + option 116W + Water buffer tank module
kg
2632
2708
2873
2895
3313 3527 3658 3893 4375
4716 4765
4813
Compressors
Hermetic Scroll 48,3 r/s
Circuit A
1
1
2
2
2
2
2
2
3
4
4
4
Circuit B
2
2
2
2
2
3
3
4
4
4
4
4
No. of control stages
3
3
4
4
4
5
5
6
7
8
8
8
Refrigerant
(4)
R-410A
Circuit A charge
kg
14,5 22,0
23,0
24,0 27,0 27,0
30,0 33,0
42,0
53,0
54,0 56,0
tCO
2
e
30,3
45,9 48,0 50,1 56,4 56,4 62,6 68,9 87,7 110,7 112,8 116,9
Circuit B charge
kg
23,0 23,0 23,0
24,0
35,0 36,0
48,5
53,0 53,0 53,0
54,0 56,0
tCO
2
e 48,0 48,0 48,0 50,1
73,1
75,2
101,3
110,7 110,7 110,7 112,8 116,9
Control
Smart View Control
Minimum capacity
%
33% 33%
25% 25% 25% 20% 20% 17% 14%
13% 13% 13%
Air heat exchanger
Grooved copper tubes and aluminium fins
Fans
Axial Flying Bird 4 with rotating shroud
Quantity
3
4
4
4
5
5
6
6
7
8
8
8
Maximum total air flow
l/s
13542
18056 18056 18056 22569 22569
27083 27083 31597 36111 36111 36111
Maximum rotation speed
rps
16
16
16
16
16
16
16
16
16
16
16
16
Water heat exchanger
Dual-circuit plate heat exchanger
Water volume
l
15
15
15
19
27
27
35
44
44
44
47
53
Max. water-side operating pressure without hydraulic
module
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic module (option)
Pump, Victaulic screen filter, relief valve, water and air drain valve, pressure
sensors, expansion tank (option)
Pump
Centrifugal pump, monocell, 48,3 rps, low- or high-pressure (as required), single
or dual (as required)
Expansion vessel volume
l
50
50
50
50
80
80
80
80
80
80
80
80
Max. water-side operating pressure with hydraulic
module
kPa
400
400
400
400
400
400
400
400
400
400
400
400
Water connections with or without hydraulic module
Victaulic type
Connections
inch
3
3
3
3
4
4
4
4
4
4
4
4
External diameter
mm
88,9 88,9 88,9 88,9
114,3 114,3 114,3 114,3 114,3 114,3 114,3 114,3
Chassis paintwork
Colour code: RAL 7035
(1) en dB ref=10
-12
W, pondération (A). Valeur d’émission sonore déclarée dissociée conformément à l'ISO 4871 (avec une incertitude de +/-3dB(A)). Mesurée selon ISO
9614-1 aux conditions de fonctionnement nominales EN14511 - mode froid.
(2) en dB ref 20µPa, pondération (A). Valeur d’émission sonore déclarée dissociée conformément à l'ISO 4871 (avec une incertitude de +/-3dB(A)). Pour information,
calculée à partir de la puissance acoustique Lw(A).
(3) Options: 15 = bas niveau sonore, 15LS = très bas niveau sonore, 116W = Module hydraulique pompe double haute pression vitesse variable
(4) Valeurs données à titre indicatif. Se référer à la plaque signalétique de l'unité.
Eurovent certified values
4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS
17