background image

1 - INTRODUCTION

Prior to the initial start-up of the 30RQM/30RQP units, everyone 

involved  in  the  works  should  be  thoroughly  familiar  with  these 

instructions and with the characteristics of the installation site, and 

ensure these are respected.
30RQM/30RQP heat pumps are designed to provide a very high 

level of safety and reliability, making installation, start-up, operation 

and maintenance easier and safer.
They  will  provide  safe  and  reliable  service  if  used  within  their 

application ranges.

They are designed to offer a service life of 15 years, assuming a 

utilisation  factor  of  75%,  which  corresponds  to  approximately 

100,000 operating hours.

The  procedures  in  this  manual  are  arranged  in  the  sequence 

required for installation, start-up, operation and maintenance of 

the units. Ensure that you follow all the required safety precautions, 

including  those  listed  in  this  guide,  such  as:  wearing  personal 

protective equipment (gloves, safety glasses, safety shoes), having 

the  appropriate  tools,  skills  and  qualifications  (electrical,  air 

conditioning, local legislation).
To  find  out  whether  these  products  comply  with  European 

directives  (machine  safety,  low  voltage,  electromagnetic 

compatibility, pressure equipment, etc.) check the declarations of 

conformity for these products. 

1.1 - 

Specific features of 30RQP units

The  30RQP  units  differ  from  the  30RQM  units  by  introducing 

variable speed drives on all of the fans and optimising the overall 

energy efficiency of the unit depending on the operating conditions 

(air  temperature,  circuit  capacity).  This  improves  the  seasonal 

efficiency (SCOP and ESEER).
All fans in the same refrigerant circuit are controlled by a single 

variable speed drive. Therefore, they operate together at the same 

rotational speed. The rotational speed of each circuit is controlled 

by  an  algorithm  that  continuously  optimises  the  condensing 

temperature in cooling mode or the evaporating temperature in 

heating mode. This ensures optimal energy efficiency of the units 

(EER and COP) whatever the operating conditions.

1.2 - 

Installation safety considerations

After the unit has been received, and before it is started up, it must 

be visually inspected for damage. Check that the refrigerant circuits 

are intact, taking care to check that no components or pipes have 

shifted or been damaged (following an impact, for example). If in 

doubt, carry out a leak tightness check. If damage is detected 

upon receipt, file a claim with the shipping company immediately.

Do not remove the skid or the packaging until the unit is in 

its final position.
These units can be safely moved with a fork lift truck, as long 

as the forks are positioned in the location and direction shown 

on the unit. 
The  units  can  also  be  lifted  with  slings,  using  only  the 

designated lifting points marked on the unit (labels on the 

chassis and label with the unit handling instructions, attached 

to the unit).
Use  slings  with  the  correct  capacity,  and  follow  the  lifting 

instructions given on the certified drawings for the unit.
Safety  can  only  be  guaranteed  if  these  instructions  are 

carefully followed. Failure to do so may result in damage to 

the equipment and physical injury.

DO NOT OBSTRUCT THE PROTECTIVE DEVICES. 

This applies to any valves fitted on the refrigerant or heat 

transfer fluid circuits. Check whether the original protection 

plugs are still present at the valve outlets. These plugs are 

generally  made  of  plastic  and  must  be  removed  before 

operation. If they are still present, please remove them. Fit 

devices at the valve or drain piping outlets to prevent the 

penetration of foreign bodies (dust, building debris, etc.) and 

atmospheric  agents  (water  can  form  rust  or  ice).  These 

devices, as well as the drain piping, must not impair operation 

and must not lead to a pressure drop that is higher than 10% 

of the control pressure.
Classification and control:
In  accordance  with  the  Pressure  Equipment  Directive  and 

national usage monitoring regulations in the European Union, 

the protective devices fitted to these machines are classified 

as follows:

Safety 

accessory

(1)

Accessory for limitation of 

damage in the event of an 

external fire

(2)

Refrigerant Side

High pressure switch

X

External relief valve

(3)

X

Rupture disk

X

Fuse plug

X

Heat transfer fluid side

External relief valve

(4)

(4)

(1)  Classified for protection in normal service situations.

(2)  Classified for protection in abnormal service situations. These accessories are 

sized for fires with a thermal flow of 10kW/m

2

. No combustible matter should 

be placed within 6.5 m of the unit.

(3)  The instantaneous over-pressure limitation of 10% of the operating pressure 

does not apply to this abnormal service situation.

The control pressure can be higher than the service pressure. In this case, either 

the design temperature or the high-pressure switch ensures that the service 

pressure is not exceeded in normal service situations.

(4)  The selection of these relief valves must be made by the personnel responsible 

for completing the hydraulic installation.

Do not remove these valves under any circumstances, even 

if the fire risk is under control for a particular system. There 

is no guarantee that the accessories have been re-installed 

if the system is changed or for transport with a gas charge. 

When the unit is subjected to fire, a safety device prevents 

rupture due to over-pressure by releasing the refrigerant. The 

fluid can then break down into toxic residues when in contact 

with flames:

• 

Stay away from the unit;

• 

Ensure the personnel in charge of extinguishing the 

fire are duly warned and issued with recommendations;

• 

Fire extinguishers appropriate to the system and the 

refrigerant type must be easily accessible.

All factory-installed relief valves are lead-sealed to prevent 

any calibration change. 
The external relief valves must always be piped to a safe, 

external location if the units are installed in a enclosed space. 

Refer  to  the  installation  regulations,  for  example  those  of 

European standard EN 378 and EN 13136. Discharge ductwork 

must  be  installed  in  a  way  that  ensures  that  people  and 

property are not exposed to vented refrigerant. As the fluids 

can be diffused in the air, ensure that refrigerant is discharged 

away from building air intakes or that it is discharged into a 

sufficient  quantity  of  suitable  absorbent  material.  Relief 

valves must be checked periodically (See the paragraph on 

“Maintenance safety considerations”).
If the relief valves are installed on a change-over valve, this 

is equipped with a relief valve on each of the two outlets. 
Only one of the two relief valves is in operation, the other one 

is  isolated.  Never  leave  the  change-over  valve  in  the 

intermediate  position,  i.e.  with  both  ways  open  (Bring  the 

actuator in abutment, front or back according to the outlet to 

isolate).  If  a  relief  valve  is  removed  for  checking  or 

replacement please ensure that there is always an active relief 

valve on each of the change-over valves installed in the unit.
Provide a drain in the discharge duct, close to each valve, to 

avoid  an  accumulation  of  condensate  or  rain  water.  All 

precautions  concerning  handling  of  refrigerant  must  be 

observed in accordance with local regulations.

4

Содержание Carrier 30RQM 160

Страница 1: ...A I N T E N A N C E I N S T R U C T I O N S Original document Reversible air to water heat pump 30RQM 160 520 A 30RQP 160 520 A Unit with low noise option Nominal heating capacity 170 540 kW Nominal...

Страница 2: ...7 Electric power reserve for the user 24 6 APPLICATION DATA 25 6 1 Operating range 25 6 2 Minimum water flow units without hydraulic module 25 6 3 Maximum water flow units without hydraulic module 26...

Страница 3: ...on Option 12 Fan with high static pressure 45 10 4 Installation 45 10 5 Nominal and maximum air flows per circuit A and B for 30RQP sizes 46 10 6 Factory installed duct connection interface on each fa...

Страница 4: ...remove them Fit devices at the valve or drain piping outlets to prevent the penetration of foreign bodies dust building debris etc and atmospheric agents water can form rust or ice These devices as we...

Страница 5: ...t and system All welding operations must be carried out by qualified specialists 30RQM 30RQP units use high pressure R 410A refrigerant the unit operating pressure is above 40 bar the pressure at an a...

Страница 6: ...ure relief valves or rupture discs Be ready to switch off the main disconnect switch of the power supply if the pressure switch does not trigger avoid over pressure or excess gas if there are valves o...

Страница 7: ...hydrocarbons under optimum quality conditions for the products and optimum safety conditions for people property and the environment are described in standard NF E29 795 Any refrigerant transfer and...

Страница 8: ...equipment tools etc If necessary damaged parts must be repaired or replaced See also the section on Maintenance 2 2 Handing and positioning 2 2 1 Handling See the section on Installation safety consid...

Страница 9: ...ine is charged with refrigerant Verify on the unit nameplate that the fluid transported is that recommended for operation and is not nitrogen Compare the complete system with the refrigeration system...

Страница 10: ...gs When designing a system refer to the certified dimensional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixi...

Страница 11: ...nsional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixing points weight distribution points and centre of gra...

Страница 12: ...to the certified dimensional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixing points weight distribution poi...

Страница 13: ...nsional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixing points weight distribution points and centre of gra...

Страница 14: ...e certified dimensional drawings provided with the unit or available on request Please refer to the certified dimensional drawings for the positioning of the fixing points weight distribution points a...

Страница 15: ...low C Clearance recommended for coil removal Water inlet Water outlet Air outlet do not obstruct Control box 3 4 Installation of multiple heat pumps It is recommended to install multiple heat pumps in...

Страница 16: ...oved copper tubes and aluminum fins Fans Axial Flying Bird 4 with rotating shroud Quantity 3 4 4 4 5 5 6 6 7 8 8 8 Maximum total air flow l s 13542 18056 18056 18056 22569 22569 27083 27083 31597 3611...

Страница 17: ...nger Grooved copper tubes and aluminium fins Fans Axial Flying Bird 4 with rotating shroud Quantity 3 4 4 4 5 5 6 6 7 8 8 8 Maximum total air flow l s 13542 18056 18056 18056 22569 22569 27083 27083 3...

Страница 18: ...at 400 V Current 3 8 A Start up current 20 A Power input 1 75 kW 4 4 Electrical data 30RQP 160 520 30RQP 160 180 210 230 240 270 310 330 380 430 470 520 Power circuit Nominal voltage V ph Hz 400 3 50...

Страница 19: ...mber and registered address Same as above 5 Product s model number Same as above 6 Number of motor poles 2 2 2 2 2 2 2 2 2 2 2 2 7 1 Nominal shaft power output at full load and nominal voltage 400 V k...

Страница 20: ...om the electrical data table to the pump current draw For the high pressure single and dual pump motors for 30RQM 30RQP 160 520 units options 116R and 116V No 2 Description 3 Units 30RQM 30RQP 160 180...

Страница 21: ...ng using an appropriate company 12 Operating conditions for which the motor is specifically designed I Altitudes above sea level m 1000 4 II Ambient air temperature C 40 III Maximum operating temperat...

Страница 22: ...to 2000 m for hydraulic module see paragraph 4 7 in the IOM Presence of hard solid Class AE3 no significant dust present 1 Presence of corrosive and polluting substances class AF1 negligible Competenc...

Страница 23: ...uctor cables in closed conduits standardised routing no 41 Cable with PVC insulation Standard lug Narrow lug Recommended max lug width Section 2 Max length for a voltage drop 5 Cable type 3 Section 2...

Страница 24: ...ical box must ensure that the equipment remains compliant with local regulations In particular precautions must be taken to prevent accidental electrical contact between the circuits supplied by diffe...

Страница 25: ...0RQP units storage and transport minimum and maximum ambient temperatures to respect are 20 C and 52 C These temperature limits shall be considered in case of container shipment 30RQM 30RQP 160 520 un...

Страница 26: ...e Units supplied with a hydraulic module may include an expansion tank which limits the volume in the water loop option 293 The table below gives the maximum loop volume for pure water or ethylene gly...

Страница 27: ...for the maximum permitted water temperature difference conditions 10 K at the minimum water outlet temperature value 5 C 6 8 Pressure drop curves for the exchanger and standard water inlet outlet pipi...

Страница 28: ...nt suitable for the products The heat transfer fluid should be filled using devices fitted to the hydraulic circuit by the installer 7 1 Operating precautions and recommendations Before any system sta...

Страница 29: ...idestemperatureinformationforthewaterexchangerinlet seeControl manual 10 Pressure sensor Note Provides pressure information for the water exchanger outlet see Control manual 11 Check valve if dual pum...

Страница 30: ...p Presence of the stainless steel filter Coupling for expansion vessel option 293 Example Dual pump Presence of the stainless steel filter Coupling for expansion vessel option 293 See legend on the pr...

Страница 31: ...ill periodically start automatically Combination of options for the periods when the machine is in standby mode Ambient unit temperature range 30RQM 30RQP 160 520 without option 116 with option 116 0...

Страница 32: ...is only possible when the units are installed in parallel The master slave assembly is controlled on the water inlet without any additional sensors system return see example 1 Control of Master and Sl...

Страница 33: ...3 4 Stage 4 safety A Variation of the heat pump output with air temperature B Building thermal load C Point of equilibrium between the heat pump output and the building thermal load 7 7 Auxiliary ele...

Страница 34: ...y to clean up the system s hydraulic circuit presence of contaminating solids Perform another reading Compare this value to the initial value A decrease in the pressure drop value indicates that the f...

Страница 35: ...ems 5 and 14 Repeat until all fouling is removed from the filter 8 3 2 Procedure for controlling the pressure differential setpoint Once the circuit has been decontaminated place the water circuit in...

Страница 36: ...re for the water circuit Refer to the cleaning procedure for the water circuit in section 8 3 1 8 5 2 Procedure for controlling the flow Once the circuit is cleaned set the required water flow by adju...

Страница 37: ...maximum flow rate is reduced 8 6 1 30RQM 30RQP high pressure pumps Single pumps Water flow rate l s Manometric head kPa B C D E F 1 30RQM 30RQP 160 180 2 30RQM 30RQP 210 230 240 3 30RQM 30RQP 270 310...

Страница 38: ...P 210 230 3 30RQM 30RQP 240 270 310 4 30RQM 30RQP 330 380 430 5 30RQM 30RQP 470 520 Dual pumps Manometric head kPa B C D E F G H Water flow rate l s 1 30RQM 30RQP 160 2 30RQM 30RQP 180 3 30RQM 30RQP 2...

Страница 39: ...D E 1 30RQM 30RQP 160 180 2 30RQM 30RQP 210 3 30RQM 30RQP 230 4 30RQM 30RQP 240 Sizes 270 520 Available static pressure kPa Water flow rate l s F G H I 5 30RQM 30RQP 270 310 6 30RQM 30RQP 330 380 7 30...

Страница 40: ...kPa F G H I 5 30RQM 30RQP 310 6 30RQM 30RQP 330 380 430 7 30RQM 30RQP 470 8 30RQM 30RQP 520 Dual pumps Sizes 160 230 Available static pressure kPa Water flow rate l s B C D E 1 30RQM 30RQP 160 2 30RQ...

Страница 41: ...axial Flying Bird fans equipped with a rotating shroud and made of composite recyclable material Each motor is fixed with transverse supports The motors are three phase with permanently lubricated bea...

Страница 42: ...kPa on refrigerant side and of 3200 kPa on the water side The water connections of the heat exchanger are Victaulic connections The water heat exchanger is thermally insulated with 19 mm of nitrile fo...

Страница 43: ...are as follows these values may change depending on the suppliers It is therefore recommended that a medium or low temperature installation be commissioned by the manufacturer 9 13 2 Required glycol c...

Страница 44: ...y improve the seasonal efficiency ESEER and SCOP All fans in the same refrigerant circuit are controlled by a single variable speed drive Therefore they operate together at the same rotational speed T...

Страница 45: ...e drop while maintaining an optimized air flow per circuit All fans in the same circuit operating at the same time have the same speed The power supply for fans with a speed of 19 rps is increased com...

Страница 46: ...11441 180 230 9534 11441 9534 11441 240 270 9534 11441 14301 17161 310 330 9534 11441 19068 22882 380 14301 17161 19068 22882 430 520 19068 22882 19068 22882 10 6 Factory installed duct connection int...

Страница 47: ...n protection grilles must always remain in their position inside the ducts Use bellows or flexible sleeves for the duct connection At the outlet of each duct provide an access hatch with a minimum siz...

Страница 48: ...it A kg 16 0 22 2 23 7 25 5 29 2 29 2 34 6 36 8 46 2 55 2 56 7 59 2 tCO2e 33 3 46 3 49 4 53 2 60 9 60 9 72 2 76 9 96 5 115 3 118 3 123 6 Circuit B kg 23 7 23 7 23 7 25 5 37 1 38 5 49 7 55 2 55 2 55 2...

Страница 49: ...B Clearances required for maintenance and air flow C Clearance recommended for coil removal Water inlet Water outlet Control box NOTE Non contractual drawings When designing a system refer to the cer...

Страница 50: ...mm B Clearances required for maintenance and air flow C Clearance recommended for coil removal Water inlet Water outlet Control box NOTE Non contractual drawings When designing a system refer to the c...

Страница 51: ...mm B Clearances required for maintenance and air flow C Clearance recommended for coil removal Water inlet Water outlet Control box NOTE Non contractual drawings When designing a system refer to the c...

Страница 52: ...eater plate heat exchanger 4 Air heat exchanger coils 5 Expansion valve EXV 6 Damage limitation accessory in case of a fire 7 Electric heater to protect the desuperheater against frost not supplied 8...

Страница 53: ...eration C 5 15 Entering water temperature at shut down C 60 Desuperheater Entering water temperature at start up 2 C 25 60 Leaving water temperature during operation C 30 80 Entering water temperature...

Страница 54: ...artial heat recovery 49 Partial heat recovery by desuperheating of the compressor discharge gas Free high temperature hot water production simultaneously with chilled and hot water production 30RQM 30...

Страница 55: ...Compliance with Australian regulations 200 Unit approved to Australian code Conformance with Australian regulations 30RQM 30RQP 160 520 Coil defrost resistance heaters 252 Electric heaters under the...

Страница 56: ...e may be available locally maintenance service industrial site specialist subcontractor The frequency of this maintenance may be monthly or annual depending on the type of check In these cases the fol...

Страница 57: ...at exchanger and pump 30 Taptite M6 screw Pipe supports enclosure variable frequency drive supports 7 H M6 screw Pipe clip 10 H M10 nut Compressor chassis Compressor fixing 30 Oil equalisation screw O...

Страница 58: ...14 397 10 987 34 1981 58 3543 13 415 11 1020 35 2034 59 3624 12 434 12 1053 36 2087 60 3706 11 453 13 1087 37 2142 61 3789 10 473 14 1121 38 2197 62 3874 9 493 15 1156 39 2253 63 3961 8 514 16 1192 4...

Страница 59: ...the unit can be recycled for another purpose 12 3 Fluids to be recovered for treatment Refrigerant Heat transfer fluid depending on the installation water brine solution etc Compressor oil 12 4 Mater...

Страница 60: ...reliminary equipment check Is there any shipping damage If so where Will this damage prevent unit start up The unit is installed level The power supply corresponds to the unit nameplate The electrical...

Страница 61: ...rost protection included if required litres of Water pipes have been fitted an electric heater for trace heating up to the evaporator Return water piping is equipped with a screen filter with a mesh s...

Страница 62: ...The unit starts and operates correctly Temperatures and pressures WARNING Once the machine has been operating for a while and the temperatures and pressures have stabilised record the following Evapor...

Страница 63: ......

Страница 64: ...Check ongoing validity of certificate www eurovent certification com Order No 10018 05 2019 Supersedes order No 10018 11 2018 Manufactured by Carrier SCS Montluel France Manufacturer reserves the righ...

Отзывы: