24
Installation into a Masonry Fireplace:
1.
Your chimney must be inspected by a certified
chimney sweep or installer to determine its structural
condition.
2.
Measure amount of venting required to top
chimney
plus 14”
to ensure the termination is adequate
distance above the roofline.
3.
The first 5’ of exhaust will be Simpson Dura Vent
pellet stove flex vent; the remainder uses rigid pipe. For
each joint subtract 1-1/2” to allow for the overlap. You
may need an adjustable length section to achieve the
correct height. The air intake may be 2” aluminum flex
vent.
4.
Assemble the first rigid section of exhaust pipe
to the flex vent pipe insuring that the “UP” arrows shown
on the pipe labels are pointing up. Connect sections
and twist to lock. Repeat the process for the remain-
der of the pipe sections and lower the assembly down
the chimney. Lower the intake and exhaust pipes be-
low their normal position to connect the pipe to back of
heater. Tie a line to the top section of venting to pull it
back up to the correct position.
5.
Connect to the exhaust of the stove by install-
ing a pipe adapter to the exhaust fan and either a 90º
elbow or a clean out tee with cap. The air intake can be
attached to the heater with a hose clamp.
6.
Connect the heater to the coupling on the bot-
tom of the exhaust flex vent and twist to the locked posi
-
tion. Push the heater into the fireplace to its final posi
-
tion.
7.
From the top of the chimney, pull the vent sys
-
tem up to the desired height.
8.
For the exhaust termination of the pellet vent
use a tall cone flashing and a storm collar. This requires
14” of pipe above the top of the masonry chimney. Pull
the pipe up through the flashing to the desired height
and mark where the storm collar will go. Slip the storm
collar down over the pipe and fasten it to the pipe with a
1/4” stainless steel sheet metal screw. The storm collar
will then support the entire exhaust vent system.
9.
Install the air intake vent through the chimney
cap by cutting a hole and install cap as shown or attach
air intake vent to a flashing and cap. The chimney top
must be properly sealed to prevent rain and or snow
from entering the chimney.
10.
Install the cap and seal around the joint of the
storm collar and any other joints that are visible.
Perform these instructions in reverse if the removal of
this appliance is ever needed for maintenance or repair.
Air Inlet
Exhaust Cap
Steel Plate or Flashing
Rigid Vent Pipe
Damper Removed or
Fastened Open
(for Canada) or sealed
Flexible Exhaust
Vent
Mantle
90º Elbow or Clean-Out Tee
Minimum 6” (150 mm)non-
combustible Floor Protection
Содержание 5560 (I)
Страница 25: ...25 VENT TERMINATION LOCATIONS Figure 22...