21
FORM CIM 0203
PHYSICAL DATA
Figure 21:
Physical Data
TONS
1
1-1/2
2
3
4
5
Voltage (d)
208/230-1-60
208/230-1-60
208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
208/230-3-60
208/230-3-60
208/230-3-60 208/230-3-60 208/230-3-60 208/230-3-60
460-3-60
460-3-60
460-3-60
460-3-60
460-3-60
460-3-60
Supply Air (a)
CFM
400
600
800
1200
1600
2000
ESP
.2 to 1"
.2 to 1"
.1 to 1"
.1 to 1"
.1 to 1"
.1 to 1"
Evap. Blower
Size
7 x 7
7 x 7
12 x 9
12 x 9
12 x 9
12 x 9
HP
1/2
1/2
1/2
3/4
1
1
Qty
1
1
1
1
1
1
Evaporator Coil
Rows Deep
3
3
2
2
4
4
Face Area
1.5
1.5
3.1
3.1
3.1
3.1
Filter
Size
13-1/2 x 17-1/2 x 1 13-1/2 x 17-1/2 x 1
20 x 24 x 2
20 x 24 x 2
20 x 24 x 2
20 x 24 x 2
Qty
1
1
1
1
1
1
Condenser Air (a)
CFM
700
850
1600
2000
2500
3300
Max. ESP
.2 to 1"
.2 to 1"
.1 to 1"
.1 to 1"
.1 to 1"
.1 to 1"
Cond. Blower
Size
7 x 7
7 x 7
12 x 9
12 x 9
12 x 9
12 x 9
HP
1/2
1/2
3/4
1
1-1/2
2
Qty
1
1
1
1
1
1
Condenser Coil
Rows Deep
3
3
3
3
4
4
Face Area
2.6
2.6
4.4
4.4
4.4
4.4
Water Cooled Cond.
Pressure Drop (b)
3.7
9.42
7
6.4
8.76
10.2
GPM
3
4.5
6
9
12
15
Int. Volume
0.1
0.1
0.2
0.3
0.4
0.7
(Water, Gallons)
Compressor
Qty
1
1
1
1
1
1
Charge R-22
Water Cooled
2 - 0
2 - 0
2 - 8
3 - 0
4 - 12
5 - 0
(Lbs-Ozs) (c)
Air Cooled
2 - 8
2 - 8
4 - 5
4 - 5
5 - 8
5 - 8
Heat Pump
2 - 11
2 - 11
4 - 8
4 - 8
5 - 11
5 - 11
Weight (Net Operating) Water Cooled
310
310
540
545
600
605
Air Cooled
375
375
600
610
660
665
Chilled Water
125
125
200
210
220
220
Heat Pump
400
400
625
635
690
695
(a) Air flow performance may require other than standard drive components.
(b) Does not include water regulating valve.
(c) Split units need additional refrigerant. Refer to note 7, page 13.
(d) 277-1-60 supply voltage requires use of Buck/Boost Transformer. Refer to page 25 under options.
All specifications subject to change without notice.
Содержание 4CA1901