FORM CIM 0203
The valve is placed in the liquid line after the con-
denser. The receiver is downstream of the valve.
The valve limits the flow of liquid refrigerant from
the condenser while at the same time regulating the
flow of discharge gas around the condenser to the
receiver.
During periods of low ambient operation, the re-
ceiver pressure falls until it approaches the setting
of the control point of the valve (typically 180 PSIG
for R-22). The valve then throttles to restrict the
flow of liquid from the condenser. This raises the
condenser pressure. Since it is the receiver pres-
sure that is being maintained, the valve will then
start to throttle open the discharge port when the
differential between the condensing pressure and
the receiver pressure exceeds 20 PSI. The hot dis-
charge gas serves to heat up the cold liquid being
passed from the condenser to the receiver. Thus the
liquid reaches the receiver warm and with sufficient
pressure to assure proper expansion valve operation.
The receiver is required to hold all of the excess/
additional liquid refrigerant in the system, since the
refrigerant will be returned to the receiver when
high ambient conditions exist.
In the off-cycle the refrigerant can “migrate” to the
condenser, during periods of low outdoor ambient.
On a call for start-up, the evaporator pressure may
not build up to the cut-in point of the low pressure
control. The result may be a failure of the compres-
sor to start or to short cycle. To eliminate this po-
tential problem, a time delay is added to bypass the
low pressure switch during start-up.
BUCK/BOOST TRANSFORMER
Units being applied on a 277-1-60 power supply
require the use of a buck/boost transformer. The
transformer will reduce the voltage from 277-1-60
to 230-1-60. The unit is supplied with components
for 230-1-60 application. Table 5 lists the buck/
boost transformers available from United CoolAir.
Figure 15 illustrates the wiring for each transformer.
SOLENOID BYPASS FOR WATER
REGULATING VALVE
On water-cooled units a N.O. solenoid valve is
placed in the water supply loop. During the “off”
cycle the solenoid is opened, thus allowing water
to bypass the heat exchanger. The solenoid device
is rated for 150 PSIG or less.
CHILLED WATER VALVES
Chilled water valves, if supplied by United CoolAir,
are typically on/off only. The valve would be
shipped loose for installation in the field. The valve
FIGURE 24:
Transformer Wiring
0023CA
Table 5:
Buck/Boost Transformer Table
United CoolAir
Max. Size of
Part Number
LOAD
Fuse or Breaker
4CA1901
KVA
1.44
10A
Amps
6.25
4CA1902
KVA
2.88
15A
Amps
12.5
4CA1903
KVA
4.31
20A
Amps
18.75
4CA1904
KVA
5.75
30A
Amps
25.0
4CA1905
KVA
8.63
40A
Amps
37.5
4CA1906
KVA
11.5
60A
Amps
50.0
4CA1907
KVA
17.25
80A
Amps
75.0
Single-Phase
FIGURE 25:
2-Way Single Circuit With Bypass
0024CA
Water
In
Water
Out
N.O. Solenoid
Valve
2-Way
Valve
Condensing
Coil
Tee
Tee