FORM CIM 0203
TROUBLE SHOOTING
WARNING: Turn OFF power to unit before conducting any trouble shooting, unless the tests
you are performing require system operation. Keep hands, clothing and tools clear of electrical
terminals and rotating components.
NOTE: For operating and trouble shooting instructions for Marvel Controller or humidifier,
refer to specific operating instructions that accompany the unit.
ITEM
PROBLEM
PROBABLE CAUSE
SOLUTION
CODE
1
Control is erratic.
Wired improperly or
Check wiring connections
connections are broken
against schematic diagram.
Defective contactor
Repair or replace contactor.
2
Blower fails to start.
Overload tripped
Reset and check cause.
Marvel alarm
Clear alarm(s) after correcting problem.
Thermostat set too high
Adjust to desired temperature.
Complete loss of
Repair leak and recharge refrigerant system.
refrigerant charge
3
Compressor fails to
Head pressure too high
Check condenser for obstructions and remove.
start.
(high pressure switch
Check for the required water flow through the
open)
water regulating valve and the condenser coil.
Manually reset thermostat.
With Marvel, turn off alarm and reset.
PTCR will keep
Wait for PTCR to cool off. Compressor should
compressor OFF for
start in 3 - 5 minutes.
3 - 5 minutes
Drain pan switch open
Check if the unit is draining properly.
Low line voltage causing
Check power source for cause of
compressor to overheat
electric variation of line voltage.
Dry or icy evaporator coil Defrost and clean coil and replace dirty
(reduced air flow)
filters.
4
Compressor short
cycles.
Lack of refrigerant
Check for leak. Repair and recharge the
(bubbles in sight glass)
system.
Short cycling of
Make sure that duct connections are proper for
conditioned air
return air and supply air and ensure that they
do not mix with each other.
– continued on page 35