37
FORM CIM 0203
ITEM
PROBLEM
PROBABLE CAUSE
SOLUTION
CODE
System short of
Check for control wiring
13
capacity in free
to the free cool solenoid
Check wiring diagram and rewire.
cool (water coil)
valve.
mode
Check to see
Locate and repair electrical connection
that power to the
problem.
pump is present.
Float not able
Clean pump and float.
14
Condensate Pump
to move freely.
does not run
Dirt or algae not
Clean pump and float.
not allowing float to
activate pump.
Tubing blocked or kinked Inspect, clean or straighten as necessary.
Check valve blocked
Clean check valve.
15
Condensate Pump runs
with no discharge
Inpeller blocked
Remove debris from pump impeller.
Tubing elevation or run
Verify tubing run is within pump
exceeds head capability
head limitations.
High or low pressure
Refer to items 8 & 10 above.
condition exists
16
Lock out relay tripped
Manually turn off system at
thermostat and then back on to reset.