5.       COMMUNICATION [MODBUS RTU] PROTOCOL

5.1      Introduction

The unit can be connected in MODBUS/RTU communication data link protocol to messaging
structure, widely used to establish master - slave communications between devices. Each
device must have unique No. node address. Before starting any communication, choose a
baud rate compatible to the host device. A Modbus data sent from a master to slave tells the
selected slave what to do and what information to send back. The MODBUS/RTU protocol
works with RS232, RS485 and RS422 standards

5.2      MODBUS Configuration Basic settings

The Basic settings for RS-485 Modbus protocol are:

Band rate
Start bit
Data bit
Stop bit
Parity

9600
1
8
1
none

5.3      Register addresses for MODBUS / RTU Protocol

The addressees for RS-485 Modbus protocol are as follows :

5.4      MODBUS system schematic.

DATA+

The system schematic for RS-485 Modbus protocol are as follows :

DATA-

Ethernet

RS-232

or

RS-485

CONVERTER

UT-30X,100X

Device-1

D- D+

RS-485 BUS

ADD:1

ADD:2

ADD:3

ADD:N

RS-485 BUS

Upto 128

devices

UT-30X,100X

Device-2

UT-30X,100X

Device-3

UT-30X,100X

Device-128

2 core 1 sq/mm shielded cable

www.utplindia.in

@

www

[email protected]

+91 7046223333 , 9427301436

All content are subject to change without notice
due to continuous improvements.
Doc. Ref. 1410/R04/0819

UNITECH TECHNOCRATS PVT LTD

FACTORY

:- 78/1/Z/3-Makarpura G I D C

. . . .,

N/R Vadasar Bridge.

/p-Gayatri emple

O

T

VADODARA - 390010

INDIA

. Gujarat,

14

COMPUTER- SCADA

UT-30X

UT-100X

MULTI CHANNEL UNIVERSAL PROCESS INDICATOR

CONTROLLER/SCANNER/DATALOGGER

D- D+

D- D+

D- D+

7

40007

READ / WRITE

9

CH : 1 SET POINT-1

40009

8

40008

READ / WRITE

10

CH : 1 SET POINT-2

40010

11

40011

12

40012

PROCESS VALUE CH : 2
PROCESS VALUE CH : 3
PROCESS VALUE CH : 4

CH : 2 SET POINT-1
CH : 2 SET POINT-2
CH : 3 SET POINT-1
CH : 3 SET POINT-2
CH : 4 SET POINT-1
CH : 4 SET POINT-2

READ ONLY

READ / WRITE

READ ONLY

READ / WRITE

READ / WRITE
READ / WRITE

READ ONLY

SR. NO.

1

PROCESS VALUE CH : 1

PARAMETER

ABSOLUTE ADDRESS

ACCESS TYPE

40001

READ / WRITE

3

40003

READ ONLY

2

40002

READ / WRITE

4

40004

5

40005

6

40006

Содержание UT-30X

Страница 1: ...6 308 7 304 8 www utplindia in 308 1 308 2 308 3 308 4 www utplindia in 308 5 308 6 308 7 304 8 www utplindia in 308 5 308 6 308 7 304 8 www utplindia in 308 1 308 2 308 3 308 4 www utplindia in 308...

Страница 2: ...o a controller rated for 12 24VDC will severely damage the controller and is a fire and smoke hazard This controller is suitable for connection to 230 15 VAC 50 Hz power mains It is the user responsib...

Страница 3: ...FIGURATION MODE 4 OPERATIONAL MODES 4 2 SETUP MODE 4 3 CALIBRATION MODE 4 4 CHANGE PASSWORD MODE 4 5 ERROR MESSAGE 5 COMMUNICATION MODBUS RTU PROTOCOL 5 1 INTRODUCTION 5 2 MODBUS CONFIGURATION BASIC S...

Страница 4: ...ovide easy access to parameters A4 digit security code perverts una uthorized changes Parameters can also be hidden to user to prevent improper configuration of the unit The UT 30X 100X product group...

Страница 5: ...ay 4 6 8 12 16 20 24 channel option available All input are universal like T C RTD linear selection Simultaneously display for individual channel in compact size 0 1 Accuracy of FSD All channels are f...

Страница 6: ...S ARE STACKED TOGETHER INDIVIDUAL POWER PROVIDED TO EACH UNITS e g 16 CH INDICATOR IS GROUPED AS BELOW CH 01 CH 02 CH 03 CH 04 INPUT SELECTION FOR A CHANNEL RTD T C TEMPERATURE ANALOG LINEAR VOLTAGE 4...

Страница 7: ...COUPLE CH 3 INPUT B RTD PT 100 11 12 13 B A J K R S T E Shor ng 11 12 13 3 WIRE 13 14 30 28 T mA Input TPS 24VDC Transmi er TRANSMITTER 2 WIRE 13 14 30 28 T mA Input TPS 24VDC Transmi er TRANSMITTER...

Страница 8: ...atus of parameter Press to change set points in normal view UP KEY UP Key allows increasing the value of a digit selected or changing the status of parameter in programming mode Press to change set po...

Страница 9: ...pe or Requirement by User To come out from Programming Mode to Normal mode Press key in any step CH 2 CH 1 8888 8888 Normal Mode Configuration Setup Mode Mode Change Password Mode Calibration Mode CAL...

Страница 10: ...NEAR INPUT Decimal Point resolution for display value Values Default Value 01 NOTE Applicable for Analog Linear input only Range Input type is same as Input 1 Default Input RtD1 It can be change as re...

Страница 11: ...for Communication Values Default Value 9600 NOTE Applicable if Communication Output Even Parity EvEn Odd Parity Odd None Parity none Change value by key or by key prty none PARITY COMMUNICATION Parity...

Страница 12: ...es between to 1999 9999 Default Value 400 0 1p1H 400 0 CH 1 SPAN or HIGH DISPLAY VALUE LINEAR I P Display value at High Input applied NOTE Applicable for Analog Linear input only Scroll the digit by k...

Страница 13: ...H 400 0 CH 3 SPAN or HIGH DISPLAY VALUE LINEAR I P Display value at High Input applied NOTE Applicable for Analog Linear input only According to Decimal point According to Decimal point HY41 sp41 Scro...

Страница 14: ...per input Refer below Table for Cal values range Note After Calibration random value appeared in display as per input Refer below Table for Cal values range Range Default Value According to Input Type...

Страница 15: ...ck the supply voltage 4 4 Change Password Mode 4 5 Error Message Range Values Parameter PAsS 0000 CHANGE PASSWORD MODE PASSWORD Password for Change Password Mode Display Scroll the digit by key Increa...

Страница 16: ...RS 485 CONVERTER UT 30X 100X Device 1 D D RS 485 BUS ADD 1 ADD 2 ADD 3 ADD N RS 485 BUS Upto 128 devices UT 30X 100X Device 2 UT 30X 100X Device 3 UT 30X 100X Device 128 2 core 1 sq mm shielded cable...

Страница 17: ......

Отзывы: