‘Setup Mode’ Mode will shown by pressing

key, after

Mode display.

Conf

4.2       Setup Mode

UT-30X

UT-100X

MULTI CHANNEL UNIVERSAL PROCESS INDICATOR

CONTROLLER/SCANNER/DATALOGGER

HY21

sp21

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

199.9

999.9

Default Value  : As per User’s set Reqd.

-

ALARM LOW SET POINT & HYSTERESIS # 2

Activation value & Hysteresis for Low Alarm - 2

(According to Decimal point)

&

HY22

sp22

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

199.9

999.9

Default Value  : As per User’s set Reqd.

-

ALARM HIGH SET POINT & HYSTERESIS # 2

Activation value & Hysteresis for High Alarm - 2

(According to Decimal point)

&

Range / Values

Parameter

pass

0000

SETUP MODE PASSWORD

Password for Setup Mode Parameters

Display

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

0000

9999

Default Value  :

0000

1p1L

000.0

CH:1 ZERO or LOW DISPLAY VALUE [LINEAR I/P]

Display value at Low Input applied.

NOTE :

Applicable for Analog Linear input only.

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

1999

9999

Default Value  :

000.0

-

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

1999

9999

Default Value  :

400.0

-

1p1H

400.0

CH:1 SPAN or HIGH DISPLAY VALUE [LINEAR I/P]

Display value at High Input applied.

NOTE :

Applicable for Analog Linear input only.

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

199.9

999.9

Default Value  :

100.0

-

sp11

100.0

ALARM LOW SET POINT # 1

Activation value for Alarm Relay-1

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

199.9

999.9

Default Value  :

000.2

-

Hy11

000.2

HYSTERESIS LOW ALARM # 1

Value Diff. between On and Off of Relay-1

(According to Decimal point)

(According to Decimal point)

(According to Decimal point)

(According to Decimal point)

HY12

sp12

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

199.9

999.9

Default Value  : As per User’s set Reqd.

-

ALARM HIGH SET POINT & HYSTERESIS # 1

Activation value & Hysteresis for High Alarm - 1

(According to Decimal point)

&

1p2L

000.0

CH:2 ZERO or LOW DISPLAY VALUE [LINEAR I/P]

Display value at Low Input applied.

NOTE :

Applicable for Analog Linear input only.

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

1999

9999

Default Value  :

000.0

-

Scroll the digit by        key, Increase by        key.

Range  :  Values between

to

1999

9999

Default Value  :

400.0

-

1P2H

400.0

CH:2 SPAN or HIGH DISPLAY VALUE [LINEAR I/P]

Display value at High Input applied.

NOTE :

Applicable for Analog Linear input only.

(According to Decimal point)

(According to Decimal point)

Содержание UT-30X

Страница 1: ...6 308 7 304 8 www utplindia in 308 1 308 2 308 3 308 4 www utplindia in 308 5 308 6 308 7 304 8 www utplindia in 308 5 308 6 308 7 304 8 www utplindia in 308 1 308 2 308 3 308 4 www utplindia in 308...

Страница 2: ...o a controller rated for 12 24VDC will severely damage the controller and is a fire and smoke hazard This controller is suitable for connection to 230 15 VAC 50 Hz power mains It is the user responsib...

Страница 3: ...FIGURATION MODE 4 OPERATIONAL MODES 4 2 SETUP MODE 4 3 CALIBRATION MODE 4 4 CHANGE PASSWORD MODE 4 5 ERROR MESSAGE 5 COMMUNICATION MODBUS RTU PROTOCOL 5 1 INTRODUCTION 5 2 MODBUS CONFIGURATION BASIC S...

Страница 4: ...ovide easy access to parameters A4 digit security code perverts una uthorized changes Parameters can also be hidden to user to prevent improper configuration of the unit The UT 30X 100X product group...

Страница 5: ...ay 4 6 8 12 16 20 24 channel option available All input are universal like T C RTD linear selection Simultaneously display for individual channel in compact size 0 1 Accuracy of FSD All channels are f...

Страница 6: ...S ARE STACKED TOGETHER INDIVIDUAL POWER PROVIDED TO EACH UNITS e g 16 CH INDICATOR IS GROUPED AS BELOW CH 01 CH 02 CH 03 CH 04 INPUT SELECTION FOR A CHANNEL RTD T C TEMPERATURE ANALOG LINEAR VOLTAGE 4...

Страница 7: ...COUPLE CH 3 INPUT B RTD PT 100 11 12 13 B A J K R S T E Shor ng 11 12 13 3 WIRE 13 14 30 28 T mA Input TPS 24VDC Transmi er TRANSMITTER 2 WIRE 13 14 30 28 T mA Input TPS 24VDC Transmi er TRANSMITTER...

Страница 8: ...atus of parameter Press to change set points in normal view UP KEY UP Key allows increasing the value of a digit selected or changing the status of parameter in programming mode Press to change set po...

Страница 9: ...pe or Requirement by User To come out from Programming Mode to Normal mode Press key in any step CH 2 CH 1 8888 8888 Normal Mode Configuration Setup Mode Mode Change Password Mode Calibration Mode CAL...

Страница 10: ...NEAR INPUT Decimal Point resolution for display value Values Default Value 01 NOTE Applicable for Analog Linear input only Range Input type is same as Input 1 Default Input RtD1 It can be change as re...

Страница 11: ...for Communication Values Default Value 9600 NOTE Applicable if Communication Output Even Parity EvEn Odd Parity Odd None Parity none Change value by key or by key prty none PARITY COMMUNICATION Parity...

Страница 12: ...es between to 1999 9999 Default Value 400 0 1p1H 400 0 CH 1 SPAN or HIGH DISPLAY VALUE LINEAR I P Display value at High Input applied NOTE Applicable for Analog Linear input only Scroll the digit by k...

Страница 13: ...H 400 0 CH 3 SPAN or HIGH DISPLAY VALUE LINEAR I P Display value at High Input applied NOTE Applicable for Analog Linear input only According to Decimal point According to Decimal point HY41 sp41 Scro...

Страница 14: ...per input Refer below Table for Cal values range Note After Calibration random value appeared in display as per input Refer below Table for Cal values range Range Default Value According to Input Type...

Страница 15: ...ck the supply voltage 4 4 Change Password Mode 4 5 Error Message Range Values Parameter PAsS 0000 CHANGE PASSWORD MODE PASSWORD Password for Change Password Mode Display Scroll the digit by key Increa...

Страница 16: ...RS 485 CONVERTER UT 30X 100X Device 1 D D RS 485 BUS ADD 1 ADD 2 ADD 3 ADD N RS 485 BUS Upto 128 devices UT 30X 100X Device 2 UT 30X 100X Device 3 UT 30X 100X Device 128 2 core 1 sq mm shielded cable...

Страница 17: ......

Отзывы: