‘Calibration Mode’ Mode will shown by pressing
key, after
Mode display.
Setp
4.3 Calibration Mode
0100 0600
~
0200 1000
~
0200 1000
~
0200 1000
~
0200 1000
~
0200 1000
~
7000 8000
~
7000 8000
~
7000 8000
~
7000 8000
~
7000 8000
~
7000 8000
~
INPUT
J - T/C
K - T/C
R - T/C
S - T/C
T - T/C
E - T/C
0 mV
0 mV
0 mV
ZERO VALUE
FEED VALUE
COUNT
SPAN VALUE
FEED VALUE
COUNT
0 mV
0 mV
0 mV
18 mV
18 mV
42 mV
42 mV
42 mV
18 mV
INPUT
ZERO VALUE
FEED VALUE
COUNT
SPAN VALUE
FEED VALUE
COUNT
0100 0600
~
0100 1000
~
0100 1000
~
0100 1000
~
0900 1500
~
7000 8000
~
7000 8000
~
7000 8000
~
7000 8000
~
2000 3000
~
4 ~ 20mA
0 ~ 20mA
1 ~ 5 VDC
10VDC
PT-100
4 mA
0 mA
1 VDC
0 VDC
20 mA
20 mA
5 VDC
10 VDC
CALIBRATION VALUES :
0°C
[100.0Ω]
100°C
[138.51Ω]
UT-30X
UT-100X
MULTI CHANNEL UNIVERSAL PROCESS INDICATOR
CONTROLLER/SCANNER/DATALOGGER
Range / Values
Parameter
pass
0000
CALIBRATION MODE PASSWORD
Password for Calibration Mode Parameters
Display
Scroll the digit by key, Increase by key.
Range : Values between
to
0000
9999
Default Value :
0000
1p1z
----
INPUT : 1 ZERO or LOW CALIBRATION
Calibration Zero / Low at Low / Zero PV Input.
NOTE :
After Zero Cal. press
key for next Para.
Apply Low signal [as per input] & press key.
Range :
Default Value :
----
According to Input Type
1P1S
----
INPUT : 1 SPAN or HIGH CALIBRATION
Calibration Span / High at Span / High PV Input.
NOTE :
After Span Cal. press
key for next para.
Apply High signal [as per input] & press key.
Note :
After Calibration random value
appeared in display, as per input.
Refer below Table for Cal. values range.
Note :
After Calibration random value
appeared in display, as per input.
Refer below Table for Cal. values range.
Range :
Default Value :
----
According to Input Type
CALa
0032
CALIBRATION AMBIENT [THERMO COUPLE INP.]
Ambient adjustment for compensation [T/C Inp.]
NOTE :
After Amb. Cal. press
key for exit.
Set Ambient Temp by & key,press key.
Range :
Default Value :
0032
Enter the actual Ambient
Temperature at the time of
calibration.
1P2Z
----
INPUT : 2 ZERO or LOW CALIBRATION
Calibration Zero / Low same as Input-1
NOTE :
After Zero Cal. press
key for next Para.
Range :
Default Value :
----
According to Input Type
1P2S
----
INPUT : 2 SPAN or HIGH CALIBRATION
Calibration Span / High same as Input-1
NOTE :
After Span Cal. press
key for next para.
Range :
Default Value :
----
According to Input Type
Note :
As per Input-1 zero calibration.
Note :
As per Input-1 span calibration.
1P3Z
----
INPUT : 3 ZERO or LOW CALIBRATION
Calibration Zero / Low same as Input-1
NOTE :
After Zero Cal. press
key for next Para.
Range :
Default Value :
----
According to Input Type
1P3S
----
INPUT : 3 SPAN or HIGH CALIBRATION
Calibration Span / High same as Input-1
NOTE :
After Span Cal. press
key for next para.
Range :
Default Value :
----
According to Input Type
Note :
As per Input-1 zero calibration.
Note :
As per Input-1 span calibration.
1P4Z
----
INPUT : 4 ZERO or LOW CALIBRATION
Calibration Zero / Low same as Input-1
NOTE :
After Zero Cal. press
key for next Para.
Range :
Default Value :
----
According to Input Type
1P4S
----
INPUT : 4 SPAN or HIGH CALIBRATION
Calibration Span / High same as Input-1
NOTE :
After Span Cal. press
key for next para.
Range :
Default Value :
----
According to Input Type
Note :
As per Input-1 zero calibration.
Note :
As per Input-1 span calibration.