GAS PIPING

Proper sizing of gas piping depends on the cubic feet per
hour of gas flow required, specific gravity of the gas and the
length of run. National Fuel Gas Code Z223.1 or CSA B149.1
should be followed in all cases unless superseded by local
codes or gas company requirements. Refer to Tables 5 and
6.

The heating value of the gas may differ with locality. The
value should be checked with the local gas utility.

NOTE: 

There may be a local gas utility requirement specify-

ing a minimum diameter for gas piping. All units require a 1/2
inch pipe connection at the gas valve.

GAS CONNECTION

The gas supply line can be routed through the hole located
on the left side of the unit. Refer to Figure 7 to locate these
access openings. Typical supply piping arrangements are
shown in Figure 5.

Gas piping recommendations:

1.

A drip leg and a ground joint union must be installed in 
the gas piping.

2.

When required by local codes, a manual shut-off valve 
may have to be installed outside of the unit.

3.

Use wrought iron or steel pipe for all gas lines. Pipe dope 
should be applied sparingly to male threads only.

 

FIGURE 5: EXTERNAL SUPPLY CONNECTION 

EXTERNAL SHUT-OFF

1 / 2   x   1 / 2   G A S   C O C K

1 / 2   x   1 / 2   U N I O N

A U T O M A T I C

G A S   V A L V E

D R I P   L E G

1 / 2   -   1 4 N P T

TABLE 5: NATURAL GAS PIPE SIZING CHART

1

LENGTH

IN

 

FEET

NOMINAL

 

INCHES

 

IRON

 

PIPE

 

SIZE

1/2”

3/4”

1”

1-1/4”

10

132

278

520

1,050

20

92

190

350

730

30

73

152

285

590

40

63

130

245

500

50

56

115

215

440

60

50

105

195

400

70

46

96

180

370

80

43

90

170

350

90

40

84

160

320

100

38

79

150

305

1.

Maximum capacity of pipe in cubic feet of gas per hour 
(based upon a pressure drop of 0.3 inch water column 
and 0.6 specific gravity gas).

TABLE 6: PROPANE (LP) GAS PIPE SIZING 

CHART

1

1.

Maximum capacity of pipe in thousands of BTU per 
hour (based upon a pressure drop of 0.5 inch water col-
umn).

LENGTH

IN

 

FEET

NOMINAL

 

INCHES

 

IRON

 

PIPE

 

SIZE

1/2”

3/4”

1”

1-1/4”

10

275

567

1,071

2,205

20

189

393

732

1,496

30

152

315

590

1,212

40

129

267

504

1,039

50

114

237

448

913

60

103

217

409

834

70

96

196

378

771

80

89

185

346

724

90

83

173

322

677

100

78

162

307

630

Содержание CHAMPION PLUS DNP 036

Страница 1: ...to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment damage may result if installation...

Страница 2: ...AS 16 TROUBLE SHOOTING 18 TYPICAL WIRING DIAGRAM NOTES 22 LIST OF FIGURES Fig Pg 1 PRODUCT NOMENCLATURE 4 2 UNIT CENTER OF GRAVITY 5 3 FIELD WIRING DIAGRAM CONTROL WIRING 7 4 POWER WIRING FIELD DIAGRA...

Страница 3: ...er CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the instal ler that personal injury and or equipment damage may result if installation procedure is not handled properly I...

Страница 4: ...llation only 2 Condenser must have an unlimited supply of air Where a choice of location is possible position unit on either north or east side of building FIGURE 1 PRODUCT NOMENCLATURE TABLE 1 UNIT A...

Страница 5: ...be moved or lifted with a fork lift Slotted openings in the skid are provided for this purpose Forks must pass completely through the base Refer to Table 2 for unit weights and to Figure 2 for approx...

Страница 6: ...nents is provided by the fol lowing removable panels Blower compartment Gas control electrical service access Refer to Figure 7 for location of these access panels and min imum clearances in Table 10...

Страница 7: ...N O T E H E A T A N T I C I P A T O R S H O U L D B E S E T A T 0 3 5 A M P S F O R A L L M O D E L S 2 4 V O L T T R A N S F O R M E R FIGURE 4 POWER WIRING FIELD DIAGRAM G R O U N D L U G R E F E R...

Страница 8: ...shown Continuous return air temperature should not be below 55 F TABLE 4 PROPANE1 LP GAS APPLICATION DATA AVAILABLE ON MODELS INPUT CAPACITY MBH 2 OUTPUT CAPACITY MBH GAS RATE3 FT 3 HR NUMBER OF BURN...

Страница 9: ...manual shut off valve may have to be installed outside of the unit 3 Use wrought iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only FIGURE 5 EXTERNAL SUPPL...

Страница 10: ...to the outside of the side gas control electrical compartment with the screws provided in the bag attached to the inside of the gas control electrical compart ment see Figure 6 If flexible stainless s...

Страница 11: ...ill Size 55 53 GAS CONNECTION SIZE 1 2 NPTI 1 2 NPTI COMPRESSOR HERMETIC TYPE Qty 1 Scroll Scroll TABLE 8 ELECTRICAL DATA MODEL DNP POWER SUPPLY VOLTAGE LIMITATIONS1 COMPRESSOR COND FAN MOTOR FLA SUPP...

Страница 12: ...O N A I R I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They...

Страница 13: ...5 8 DIA KNOCKOUT 1 2 NPTI CONNECTION LOW VOLTAGE CONN DIA KNOCKOUT 8 7 FIGURE 9 UNIT DIMENSIONS BACK BOTTOM 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1 4 1 2...

Страница 14: ...ter a cool fan on delay timing of 2 seconds the circulating fan is energized at cooling speed When the thermostat is satisfied terminals G and Y are de energized de energizing the compressor and outdo...

Страница 15: ...to Figure 10 Adjust as follows 1 Remove the cap from the valve body See Figure 11 for location 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure t...

Страница 16: ...rise or temperature difference between the return air and the heated air from the furnace must lie within the range shown on the rating plate and the data in Tables 3 and 4 After the temperature rise...

Страница 17: ...4 67 56 32 64 58 31 62 60 30 60 1 EXAMPLE By actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this infor...

Страница 18: ...CHECKOUT procedures Troubleshooting of components necessitates opening the electrical control box with the power connected to the unit Use extreme care when working with the live circuits Check the u...

Страница 19: ...035 18579 001 B 0103 Unitary Products Group 19 FIGURE 14 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Страница 20: ...035 18579 001 B 0103 20 Unitary Products Group FIGURE 15 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY...

Страница 21: ...035 18579 001 B 0103 Unitary Products Group 21 FIGURE 16 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY...

Страница 22: ...s present wire 202 Y is connected to ASCT 3 If neither LR or ASCT are present Wire 202 Y is connect to M1 coil Open all disconnects before servicing this unit FIGURE 17 TYPICAL WIRING DIAGRAM LEGEND1...

Страница 23: ...035 18579 001 B 0103 Unitary Products Group 23...

Страница 24: ...o change without notice Printed in U S A Copyright by Unitary Products Group 2003 All rights reserved Supersedes 035 18579 000 A 0302 035 18579 001 B 0103 Unitary 5005 Norman Products York OK Group Dr...

Отзывы: