INSTALLATION SAFETY INFORMATION

Read these instructions before continuing this appliance
installation. This is an outdoor combination heating and cool-
ing equipment. The installer must assure that these instruc-
tions are made available to the consumer and with
instructions to retain them for future reference.

1.

Refer to the furnace rating plate for the approved type of 
gas for this furnace.

2.

Install this furnace only in a location and position as 
specified on pages 4 and 5 of these instructions.

3.

Never test for gas leaks with an open flame. Use com-
mercially available soap solution made specifically for 
the detection of leaks when checking all connections, as 
specified on pages 3 and 10 of these instructions.

4.

Always install furnace to operate within the furnace’s 
intended temperature-rise range with the duct system 
and within the allowable external static pressure range, 
as specified on the unit name/rating plate, specified on 
pages 8 and 16 of these instructions.

5.

This equipment is not to be used for temporary heating 
of buildings or structures under construction.

GENERAL

YORK Model D1NP units are cooling/heating air conditioners
designed for outdoor installation. Only gas piping, electric
power and duct connections are required at the point of
installation.

The gas-fired heaters have hot surface to pilot ignition. The
tubular heat exchangers are aluminized steel.

Installer should pay particular attention to the words; NOTE,
CAUTION, and WARNING.  NOTES are intended to clarify or
make the installation easier.  CAUTIONS are given to prevent
equipment damage.  WARNINGS are given to alert the instal-

ler that personal injury and/or equipment damage may result
if installation procedure is not handled properly.

INSPECTION

As soon as a unit is received, it should be inspected for possi-
ble damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill. A
separate request for inspection by the carrier's agent should
be made in writing. Refer to Form 50.15-NM for additional
information.

MAINTENANCE AND RENEWAL PARTS

Refer to User’s, Maintenance and Service Information Man-
ual, Part No. 035-15509-001.

APPROVALS

Design certified by CGA and AGA listed as follows:

1.

For use as a forced air furnace with cooling unit.

2.

For outdoor installation only.

3.

For installation directly on combustible flooring or, in 
U.S., on wood flooring or Class A; B; C roof covering 
material.

4.

For installation on combustible material.

5.

For use with natural gas and/or propane (LP) gas.

Not suitable for use with conventional venting systems.

  

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could
result in serious injury, death or property damage.

Never test for gas leaks with an open flame. Use a
commercially available soap solution made specif-
ically for the detection of leaks to check all connec-
tions. A fire or explosion may result causing
property damage, personal injury or loss of life.

This product must be installed in strict compliance
with the enclosed installation instructions and any
applicable local, state, and national codes includ-
ing but not limited to, building, electrical and
mechanical codes.

Improper installation may create a condition where
the operation of the product could cause personal
injury or property damage.

Содержание CHAMPION PLUS DNP 036

Страница 1: ...to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment damage may result if installation...

Страница 2: ...AS 16 TROUBLE SHOOTING 18 TYPICAL WIRING DIAGRAM NOTES 22 LIST OF FIGURES Fig Pg 1 PRODUCT NOMENCLATURE 4 2 UNIT CENTER OF GRAVITY 5 3 FIELD WIRING DIAGRAM CONTROL WIRING 7 4 POWER WIRING FIELD DIAGRA...

Страница 3: ...er CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the instal ler that personal injury and or equipment damage may result if installation procedure is not handled properly I...

Страница 4: ...llation only 2 Condenser must have an unlimited supply of air Where a choice of location is possible position unit on either north or east side of building FIGURE 1 PRODUCT NOMENCLATURE TABLE 1 UNIT A...

Страница 5: ...be moved or lifted with a fork lift Slotted openings in the skid are provided for this purpose Forks must pass completely through the base Refer to Table 2 for unit weights and to Figure 2 for approx...

Страница 6: ...nents is provided by the fol lowing removable panels Blower compartment Gas control electrical service access Refer to Figure 7 for location of these access panels and min imum clearances in Table 10...

Страница 7: ...N O T E H E A T A N T I C I P A T O R S H O U L D B E S E T A T 0 3 5 A M P S F O R A L L M O D E L S 2 4 V O L T T R A N S F O R M E R FIGURE 4 POWER WIRING FIELD DIAGRAM G R O U N D L U G R E F E R...

Страница 8: ...shown Continuous return air temperature should not be below 55 F TABLE 4 PROPANE1 LP GAS APPLICATION DATA AVAILABLE ON MODELS INPUT CAPACITY MBH 2 OUTPUT CAPACITY MBH GAS RATE3 FT 3 HR NUMBER OF BURN...

Страница 9: ...manual shut off valve may have to be installed outside of the unit 3 Use wrought iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only FIGURE 5 EXTERNAL SUPPL...

Страница 10: ...to the outside of the side gas control electrical compartment with the screws provided in the bag attached to the inside of the gas control electrical compart ment see Figure 6 If flexible stainless s...

Страница 11: ...ill Size 55 53 GAS CONNECTION SIZE 1 2 NPTI 1 2 NPTI COMPRESSOR HERMETIC TYPE Qty 1 Scroll Scroll TABLE 8 ELECTRICAL DATA MODEL DNP POWER SUPPLY VOLTAGE LIMITATIONS1 COMPRESSOR COND FAN MOTOR FLA SUPP...

Страница 12: ...O N A I R I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They...

Страница 13: ...5 8 DIA KNOCKOUT 1 2 NPTI CONNECTION LOW VOLTAGE CONN DIA KNOCKOUT 8 7 FIGURE 9 UNIT DIMENSIONS BACK BOTTOM 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1 4 1 2...

Страница 14: ...ter a cool fan on delay timing of 2 seconds the circulating fan is energized at cooling speed When the thermostat is satisfied terminals G and Y are de energized de energizing the compressor and outdo...

Страница 15: ...to Figure 10 Adjust as follows 1 Remove the cap from the valve body See Figure 11 for location 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure t...

Страница 16: ...rise or temperature difference between the return air and the heated air from the furnace must lie within the range shown on the rating plate and the data in Tables 3 and 4 After the temperature rise...

Страница 17: ...4 67 56 32 64 58 31 62 60 30 60 1 EXAMPLE By actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this infor...

Страница 18: ...CHECKOUT procedures Troubleshooting of components necessitates opening the electrical control box with the power connected to the unit Use extreme care when working with the live circuits Check the u...

Страница 19: ...035 18579 001 B 0103 Unitary Products Group 19 FIGURE 14 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Страница 20: ...035 18579 001 B 0103 20 Unitary Products Group FIGURE 15 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY...

Страница 21: ...035 18579 001 B 0103 Unitary Products Group 21 FIGURE 16 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY...

Страница 22: ...s present wire 202 Y is connected to ASCT 3 If neither LR or ASCT are present Wire 202 Y is connect to M1 coil Open all disconnects before servicing this unit FIGURE 17 TYPICAL WIRING DIAGRAM LEGEND1...

Страница 23: ...035 18579 001 B 0103 Unitary Products Group 23...

Страница 24: ...o change without notice Printed in U S A Copyright by Unitary Products Group 2003 All rights reserved Supersedes 035 18579 000 A 0302 035 18579 001 B 0103 Unitary 5005 Norman Products York OK Group Dr...

Отзывы: