Unitary Products Group

4.

All piping should be cleaned of dirt and scale by ham-
mering on the outside of the pipe and blowing out the 
loose dirt and scale. Before initial start-up, be sure that 
all of the gas lines external to the unit have been purged 
of air.

5.

The gas supply should be a separate line and installed in 
accordance with all safety codes as prescribed under 
Limitations. After the gas connections have been com-
pleted, open the main shut-off valve admitting normal 
gas pressure to the mains. Check all joints for leaks with 
soap solution or other material suitable for the purpose. 
NEVER USE A FLAME.

6.

The furnace must be isolated from the gas supply piping 
system by closing its individual manual shut-off valve 
during any pressure testing of the gas supply piping sys-
tem at test pressures equal to or less than 1/2 psig (3.48 
kPa).

FLUE VENT HOOD

The flue vent hood with screen is not shipped attached. This
hood must be installed to assure proper unit operation. The
hood must be fastened to the outside of the side gas control/
electrical compartment with the screws provided in the bag
attached to the inside of the gas control/electrical compart-
ment, see Figure 6.

 

 

If flexible stainless steel tubing is allowed by the
authority having jurisdiction, wrought iron or steel
pipe must be installed at the gas valve and extend
a minimum of two (2) inches outside of the unit
casing.

Natural gas may contain some propane.  Propane,
being an excellent solvent, will quickly dissolve
white lead or most standard commercial com-
pounds.  Therefore, a special pipe dope must be
applied when wrought iron or steel pipe is used.
Shellac base compounds such as gaskoloc or sta-
lastic, and compounds such as rectorseal # 5,
Clyde’s orJohn Crane may be used.

Flue hood surfaces may be hot.

FIGURE 6:

FLUE VENT OUTLET AIR HOOD

The flue exhaust hood must be properly installed
and within the recommended clearances. Further
communications and action must be given to the
home or building owner(s) to eliminate any unau-
thorized human contact around this area during
the heating cycle.  Flue hood surface and the
immediate area reach high temperatures during
the heating cycle.

V E N T   O U T L E T   S C R E E N

F L U E   V E N T   O U T L E T

A I R   H O O D

Содержание CHAMPION PLUS DNP 036

Страница 1: ...to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment damage may result if installation...

Страница 2: ...AS 16 TROUBLE SHOOTING 18 TYPICAL WIRING DIAGRAM NOTES 22 LIST OF FIGURES Fig Pg 1 PRODUCT NOMENCLATURE 4 2 UNIT CENTER OF GRAVITY 5 3 FIELD WIRING DIAGRAM CONTROL WIRING 7 4 POWER WIRING FIELD DIAGRA...

Страница 3: ...er CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the instal ler that personal injury and or equipment damage may result if installation procedure is not handled properly I...

Страница 4: ...llation only 2 Condenser must have an unlimited supply of air Where a choice of location is possible position unit on either north or east side of building FIGURE 1 PRODUCT NOMENCLATURE TABLE 1 UNIT A...

Страница 5: ...be moved or lifted with a fork lift Slotted openings in the skid are provided for this purpose Forks must pass completely through the base Refer to Table 2 for unit weights and to Figure 2 for approx...

Страница 6: ...nents is provided by the fol lowing removable panels Blower compartment Gas control electrical service access Refer to Figure 7 for location of these access panels and min imum clearances in Table 10...

Страница 7: ...N O T E H E A T A N T I C I P A T O R S H O U L D B E S E T A T 0 3 5 A M P S F O R A L L M O D E L S 2 4 V O L T T R A N S F O R M E R FIGURE 4 POWER WIRING FIELD DIAGRAM G R O U N D L U G R E F E R...

Страница 8: ...shown Continuous return air temperature should not be below 55 F TABLE 4 PROPANE1 LP GAS APPLICATION DATA AVAILABLE ON MODELS INPUT CAPACITY MBH 2 OUTPUT CAPACITY MBH GAS RATE3 FT 3 HR NUMBER OF BURN...

Страница 9: ...manual shut off valve may have to be installed outside of the unit 3 Use wrought iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only FIGURE 5 EXTERNAL SUPPL...

Страница 10: ...to the outside of the side gas control electrical compartment with the screws provided in the bag attached to the inside of the gas control electrical compart ment see Figure 6 If flexible stainless s...

Страница 11: ...ill Size 55 53 GAS CONNECTION SIZE 1 2 NPTI 1 2 NPTI COMPRESSOR HERMETIC TYPE Qty 1 Scroll Scroll TABLE 8 ELECTRICAL DATA MODEL DNP POWER SUPPLY VOLTAGE LIMITATIONS1 COMPRESSOR COND FAN MOTOR FLA SUPP...

Страница 12: ...O N A I R I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They...

Страница 13: ...5 8 DIA KNOCKOUT 1 2 NPTI CONNECTION LOW VOLTAGE CONN DIA KNOCKOUT 8 7 FIGURE 9 UNIT DIMENSIONS BACK BOTTOM 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1 4 1 2...

Страница 14: ...ter a cool fan on delay timing of 2 seconds the circulating fan is energized at cooling speed When the thermostat is satisfied terminals G and Y are de energized de energizing the compressor and outdo...

Страница 15: ...to Figure 10 Adjust as follows 1 Remove the cap from the valve body See Figure 11 for location 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure t...

Страница 16: ...rise or temperature difference between the return air and the heated air from the furnace must lie within the range shown on the rating plate and the data in Tables 3 and 4 After the temperature rise...

Страница 17: ...4 67 56 32 64 58 31 62 60 30 60 1 EXAMPLE By actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this infor...

Страница 18: ...CHECKOUT procedures Troubleshooting of components necessitates opening the electrical control box with the power connected to the unit Use extreme care when working with the live circuits Check the u...

Страница 19: ...035 18579 001 B 0103 Unitary Products Group 19 FIGURE 14 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Страница 20: ...035 18579 001 B 0103 20 Unitary Products Group FIGURE 15 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY...

Страница 21: ...035 18579 001 B 0103 Unitary Products Group 21 FIGURE 16 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY...

Страница 22: ...s present wire 202 Y is connected to ASCT 3 If neither LR or ASCT are present Wire 202 Y is connect to M1 coil Open all disconnects before servicing this unit FIGURE 17 TYPICAL WIRING DIAGRAM LEGEND1...

Страница 23: ...035 18579 001 B 0103 Unitary Products Group 23...

Страница 24: ...o change without notice Printed in U S A Copyright by Unitary Products Group 2003 All rights reserved Supersedes 035 18579 000 A 0302 035 18579 001 B 0103 Unitary 5005 Norman Products York OK Group Dr...

Отзывы: