SEQUENCE OF OPERATION

The unit is controlled by a conventional four wire heating/
cooling thermostat common to this class of equipment.

HEATING

When the thermostat calls for HEAT, the thermostat terminal
W is energized, energizing the combustion air blower.

After airflow is established, the air proving switch closes, the
hot surface ignitor is energized and the pilot valve opens
igniting the pilot flame.

The flame rod senses a flame and de-energizes the ignitor
opening the main gas valve and the main burners light.

30 seconds after the main burners light the circulating fan is
energized at the heating speed.

When the thermostat is satisfied, terminal W is de-energized,
de-energizing the ignition system closing the gas valve.

After a 5 second postpurge timing period, the combustion air
blower is de-energized and the heat fan off timing begins.

When this field selected heat fan off timing is completed the
circulating fan is de-energized.

If the primary, rollout and auxiliary limit switches open, the
thermostat and ignition system is de-energized and the gas
valve closes. The combustion blower and the circulating fan,
at heat speed, are energized.

The combustion blower remains energized for the 5 second
postpurge timing period if the primary, rollout and auxiliary
limit switches remake the contact (the rollout and auxiliary
limit switches must be manually reset). The circulating fan
remains energized for the selected heat delay off timing.

Normal operation of the system resumes.

COOLING

When the thermostat calls for COOL, the thermostat termi-
nals G and Y are energized signaling the compressor and
outdoor fan to run.

After a cool fan on delay timing of 2 seconds, the circulating
fan is energized at cooling speed.

When the thermostat is satisfied, terminals G and Y are de-
energized, de-energizing the compressor and outdoor fan.

After a cool fan off delay timing of 30 seconds the circulating
fan is de-energized.

CIRCULATING FAN 

When the thermostat calls for FAN, the thermostat terminal G
is energized signaling the circulating fan to run at the heat
speed 2 seconds after the G terminal is energized.

If a call for HEAT occurs, the circulating fan continues to run
at the heat speed.

If a call for COOL occurs, the circulating fan switches to cool
speed after a 4 second delay.

When the thermostat ends the call for FAN, the thermostat
terminal G is de-energized, de-energizing the circulating fan.

START-UP

PRE-START CHECK LIST

Complete the following checks before starting the unit.

1.

Check the type of gas being supplied. Be sure that it is 
the same as listed on the unit nameplate.

2.

Make sure that the vent outlet air hoods has been prop-
erly installed.

OPERATING INSTRUCTIONS

1.

STOP! Read the information on the unit safety label.

2.

Set the thermostat to the OFF position.

3.

Turn off all electrical power to the unit.

4.

DO NOT try to light the burners by hand. This appliance 
is equipped with an ignition device which automatically 
lights the burners. 

5.

Remove the access panel.

6.

Turn the gas valve switch to the OFF position.

7.

Wait five (5) minutes to clear out any gas. If you then 
smell gas, STOP! Follow B in the information on the unit 
safety label. If you don't smell gas, go to the next step.

8.

Turn the gas valve switch to the ON position.

9.

Replace the control access panel.

10. Turn on all electric power to the unit.

11. Set the thermostat to the desired setting.

12. If the unit will not operate, follow the instructions To Turn 

Off Gas To Appliance and call your service technician or 
gas supplier.

Содержание CHAMPION PLUS DNP 036

Страница 1: ...to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment damage may result if installation...

Страница 2: ...AS 16 TROUBLE SHOOTING 18 TYPICAL WIRING DIAGRAM NOTES 22 LIST OF FIGURES Fig Pg 1 PRODUCT NOMENCLATURE 4 2 UNIT CENTER OF GRAVITY 5 3 FIELD WIRING DIAGRAM CONTROL WIRING 7 4 POWER WIRING FIELD DIAGRA...

Страница 3: ...er CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the instal ler that personal injury and or equipment damage may result if installation procedure is not handled properly I...

Страница 4: ...llation only 2 Condenser must have an unlimited supply of air Where a choice of location is possible position unit on either north or east side of building FIGURE 1 PRODUCT NOMENCLATURE TABLE 1 UNIT A...

Страница 5: ...be moved or lifted with a fork lift Slotted openings in the skid are provided for this purpose Forks must pass completely through the base Refer to Table 2 for unit weights and to Figure 2 for approx...

Страница 6: ...nents is provided by the fol lowing removable panels Blower compartment Gas control electrical service access Refer to Figure 7 for location of these access panels and min imum clearances in Table 10...

Страница 7: ...N O T E H E A T A N T I C I P A T O R S H O U L D B E S E T A T 0 3 5 A M P S F O R A L L M O D E L S 2 4 V O L T T R A N S F O R M E R FIGURE 4 POWER WIRING FIELD DIAGRAM G R O U N D L U G R E F E R...

Страница 8: ...shown Continuous return air temperature should not be below 55 F TABLE 4 PROPANE1 LP GAS APPLICATION DATA AVAILABLE ON MODELS INPUT CAPACITY MBH 2 OUTPUT CAPACITY MBH GAS RATE3 FT 3 HR NUMBER OF BURN...

Страница 9: ...manual shut off valve may have to be installed outside of the unit 3 Use wrought iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only FIGURE 5 EXTERNAL SUPPL...

Страница 10: ...to the outside of the side gas control electrical compartment with the screws provided in the bag attached to the inside of the gas control electrical compart ment see Figure 6 If flexible stainless s...

Страница 11: ...ill Size 55 53 GAS CONNECTION SIZE 1 2 NPTI 1 2 NPTI COMPRESSOR HERMETIC TYPE Qty 1 Scroll Scroll TABLE 8 ELECTRICAL DATA MODEL DNP POWER SUPPLY VOLTAGE LIMITATIONS1 COMPRESSOR COND FAN MOTOR FLA SUPP...

Страница 12: ...O N A I R I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They...

Страница 13: ...5 8 DIA KNOCKOUT 1 2 NPTI CONNECTION LOW VOLTAGE CONN DIA KNOCKOUT 8 7 FIGURE 9 UNIT DIMENSIONS BACK BOTTOM 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1 4 1 2...

Страница 14: ...ter a cool fan on delay timing of 2 seconds the circulating fan is energized at cooling speed When the thermostat is satisfied terminals G and Y are de energized de energizing the compressor and outdo...

Страница 15: ...to Figure 10 Adjust as follows 1 Remove the cap from the valve body See Figure 11 for location 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure t...

Страница 16: ...rise or temperature difference between the return air and the heated air from the furnace must lie within the range shown on the rating plate and the data in Tables 3 and 4 After the temperature rise...

Страница 17: ...4 67 56 32 64 58 31 62 60 30 60 1 EXAMPLE By actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this infor...

Страница 18: ...CHECKOUT procedures Troubleshooting of components necessitates opening the electrical control box with the power connected to the unit Use extreme care when working with the live circuits Check the u...

Страница 19: ...035 18579 001 B 0103 Unitary Products Group 19 FIGURE 14 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Страница 20: ...035 18579 001 B 0103 20 Unitary Products Group FIGURE 15 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY...

Страница 21: ...035 18579 001 B 0103 Unitary Products Group 21 FIGURE 16 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY...

Страница 22: ...s present wire 202 Y is connected to ASCT 3 If neither LR or ASCT are present Wire 202 Y is connect to M1 coil Open all disconnects before servicing this unit FIGURE 17 TYPICAL WIRING DIAGRAM LEGEND1...

Страница 23: ...035 18579 001 B 0103 Unitary Products Group 23...

Страница 24: ...o change without notice Printed in U S A Copyright by Unitary Products Group 2003 All rights reserved Supersedes 035 18579 000 A 0302 035 18579 001 B 0103 Unitary 5005 Norman Products York OK Group Dr...

Отзывы: