36
7
Graph
36
Graph
Chapter
7
Stop mode (STOP MODE)
Sets the stop mode for graph.
<Setting range>
CYCLE, MAX. REC.
- CYCLE
Use of encoder
Not used:
Stops plotting when the graph is plotted up to the X-axis
full scale or the maximum recording time.
Used:
Stops plotting when the graph is plotted up to the timing of
the angle to be reset to 0 (set by the setting value "zero clear") or
the maximum recording time.
- MAX. REC.
Stops plotting when the graph is plotted up to the maximum recording time.
The graph will be overwritten.
Maximum recording time (MAX.REC.TM)
The maximum time for recording is set by this function.
<Setting range>
5, 10, 20, 40, 50, 100 [S]
Pretrigger (PRETRIGGER)
Plots a graph by tracing back the length of time set as a rate against the full scale.
* Enabled only when the encoder is not used and the start mode is EDGE
↑
or EDGE
↓
.
<Setting range>
OFF, 10, 20, 30, 40, 50 [%]
X-axis start point (X START)
Sets the start point for X-axis of a graph.
* Enabled only when the encoder is used.
<Setting range>
-1000000 to 1000000
X-axis scale (X SCALE)
Sets the X-axis scale of a graph.
The X-axis scale can also be changed on a graph display screen (
keys).
<Setting range>
Encoder enabled
10, 20, 40, 80, 100, 200, 400, 800, 1000, 2000, 4000, 8000, 10000,
20000, 40000, 80000, 100000, 200000
(Decimal place is automatically determined according to
the minimum scale setting.)
Encoder disabled
0.001, 0.002, 0.004, 0.008, 0.01, 0.02, 0.04, 0.08, 0.1, 0.2, 0.4, 0.8,
1, 2, 4, 8, 10, 20 [s]
* The settable range changes depending on the setting
of maximum recording time.
5s ...........0.001 to 1
40s ........ 0.001 to 8
10s .........0.001 to 2
50s ........ 0.001 to 10
20s .........0.001 to 4
100s ...... 0.001 to 20
▼
▲