9-7.
BCD output check
Each bit of BCD output is turned ON and OFF.
* In BCD output check display, the panel does not return to the indicated value display even
without key operation.
* Output check condition will not be canceled even if setting mode is switched.
A stationary output condition returns after all are completed.
key
HOLD
Approx. 1.6 sec.
Approx. 1.6 sec.
Approx. 0.8 sec.
Approx. 1.6 sec.
All outputs ON
All outputs OFF
All outputs OFF
Only A2 (1) output ON
Approx. 0.8 sec.
Approx. 0.8 sec.
Only A3 (2) output ON
Only A5 (8) output ON
Only A4 (4) output ON
Approx. 0.8 sec.
Only B13 (STROBE) output ON
Back to a stationary output condition
(* Refer to the right.)
Approx. 0.8 sec.
Only A6 (10) output ON
(*)
Display
No.
Signal
0-1
A2
1
0-2
A3
2
0-4
A4
4
0-8
A5
8
1-1
A6
10
1-2
A7
20
1-4
A8
40
1-8
A9
80
2-1
A10
100
2-2
A11
200
2-4
A12
400
2-8
A13
800
3-1
B2
1000
3-2
B3
2000
3-4
B4
4000
3-8
B5
8000
4-1
B6
10000
4-2
B7
20000
4-4
B8
40000
4-8
B9
80000/NZ
5-1
B10
Minus (polarity)
5-2
B11
OVER
5-4
B12
P.C (stable)
5-8
B13
STROBE
Approx. 0.8 sec.
Display
BCD output start
Содержание F325
Страница 1: ...01JUN2015REV 1 01 DIGITAL INDICATOR F325 OPERATION MANUAL...
Страница 153: ...142 15 Specifications 142 Specifications Chapter 15 When BCO BSC option is selected Unit mm When BSC option is selected...
Страница 154: ...143 15 Specifications 143 Specifications Chapter 15 When DAV DAI option is selected Unit mm When DAI option is selected...
Страница 155: ...144 15 Specifications 144 Specifications Chapter 15 When RS 232C option is selected Unit mm...
Страница 160: ......