![Unipower Sageon III Скачать руководство пользователя страница 78](http://html1.mh-extra.com/html/unipower/sageon-iii/sageon-iii_product-manual_3895940078.webp)
Sageon III Power System
Configuration and Operation
PM990-8800-00, Rev. 9
4-23
(Base Menu continued)
ENTER
3-ph AC Monitor
Off
INC/DEC toggles state
ENTER to accept
(If 3-ph AC Monitor not = Off)
ENTER
3ph AC Vhi Alarm
260V
Modify Value up/down
ENTER to accept
ENTER
3ph AC Vlo Alarm
200V
Modify Value up/down
ENTER to accept
ENTER
3ph AC fhi Alarm
55.0Hz
Modify Value up/down
ENTER to accept
ENTER
3ph AC flo Alarm
45.0Hz
Modify Value up/down
ENTER to accept
ENTER
3ph AC FS Curr.
100A
Modify Value up/down
ENTER to accept
ENTER
Battery Monitor
Off
INC/DEC toggles state
ENTER to accept
(If Battery Monitor not = Off)
ENTER
Selects battery cell type
Battery Config
24 cells
Modify Value up/down
ENTER to accept
ENTER
Number of battery banks
BCM Batteries
1
Modify Value up/down
ENTER to accept
ENTER
Cell Vhi Alarm
2.50V
Modify Value up/down
ENTER to accept
ENTER
Cell Vlo Alarm
1.80V
Modify Value up/down
ENTER to accept
ENTER
Differential cell threshold
Cell +dVc Alarm
10%
Modify Value up/down
ENTER to accept
ENTER
Differential cell threshold
Cell -dVc Alarm
10%
Modify Value up/down
ENTER to accept
ENTER
Site Monitor
Off
INC/DEC toggles state
ENTER to accept
(If Site Monitor not = Off)
ENTER
Status of output relay 1
Output 1
Off
Modify Value up/down
ENTER to accept
ENTER
Status of output relay 2
Output 2
Off
Modify Value up/down
ENTER to accept
ENTER
Status of output relay 3
Output 3
Off
Modify Value up/down
ENTER to accept
ENTER
Status of output relay 4
Output 4
Off
Modify Value up/down
ENTER to accept
Содержание Sageon III
Страница 43: ...Installation Sageon III Power System PM990 8800 00 Rev 9 2 22 FIGURE 2 20 SAGEON III BOARD LOCATIONS...
Страница 46: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 3 FIGURE 3 1 SINGLE PHASE FEED PHASE TO NEUTRAL...
Страница 47: ...Commissioning Sageon III Power System PM990 8800 00 Rev 9 3 4 FIGURE 3 2 SINGLE PHASE FEED PHASE TO PHASE...
Страница 50: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 7 FIGURE 3 5 Y THREE PHASE FEED PHASE TO NEUTRAL...