Sageon III Power System
Configuration and Operation
PM990-8800-00, Rev. 9
4-9
Units leave the factory without a pre-programmed password and the security function is not active. To activate the security, a
password must be programmed. Once that is done, security can be enabled.
When the security function is active any changes to the system settings can be done only after a valid password was entered. When the
ENTER key is pressed to change a parameter, the display will show a message “Enter Password” on the top line and a blinking cursor
on the right hand side of the bottom line. Using INC and DEC keys scroll to the first character of the password and press ENTER. The
character will be substituted by an asterisk (*) displayed to the left of the cursor. Enter all characters of the password the same way. If
the password is less than eight characters long press ENTER again after last character. If the entered password was correct the display
will return to the selected parameter ready for modification. If the entry was incorrect following will be displayed.
There is no limit on password entry re-tries. To abort password entry any of the top row buttons should be pressed. The display will
return to the selected parameter. Once unlocked, the security is disabled until there is no keypad activity for >1 minute.
Display test: All LEDs on the rectifiers and operator panel will flash when ENTER is
pressed, and the screen will alternate between the SCU software version and an all pixels
on screen (not shown).
Number of SMRs (Rectifiers) in system: This number must be entered to prevent the
operator panel from indicating that some SMRs are not responding.
Number of battery strings: Set to the number of connected battery strings.
Battery current transducer full-scale rating: Set to the full-scale rating of the battery
current transducer.
Load sensor:
On = SCU displayed System current is derived from the voltage across System shunt.
Off = SCU displayed System current is the sum of the Rectifier currents.
Full Scale Load Current: Set to the full scale rating of the installed plant system shunt.
SCU Access Code (i.e. System ID): Type a unique 7 digit number for each Sageon III
Power System in your network. Be sure to record your access code(s) and store in a
secure location.
Date format: Set the date format: DD/MM/YYYY, MM/DD/YYYY, or YYYY/MM/DD.
Clock set: Set the date and time. Note that this is a 24-hour clock.
Alarm report on/off toggle: When on, the system will dial the Phone 1 number, see the
Phone 1 screen below. If there is no answer, Phones 2 and 3 will be dialed in turn. The
cycle will continue until a connection is made. See Note following Phone 3 below.
Daily report on/off toggle: When on, the system will log in to the telephone numbers
below at the time set in the following screen and download the status and all operating
parameters. See Note following Phone 3 below.
Test Indicators
Press ENTER
Number of SMRs
15
Num of Batteries
2
FS Batt Current
200A
Access Code
1252636
Date Format
MM/DD/YYYY
Date 04/01/2013
Time 21:58:34
Alarm Report
On
Daily Report
On
Load Sensor
ON
FS Load
2500A
Содержание Sageon III
Страница 43: ...Installation Sageon III Power System PM990 8800 00 Rev 9 2 22 FIGURE 2 20 SAGEON III BOARD LOCATIONS...
Страница 46: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 3 FIGURE 3 1 SINGLE PHASE FEED PHASE TO NEUTRAL...
Страница 47: ...Commissioning Sageon III Power System PM990 8800 00 Rev 9 3 4 FIGURE 3 2 SINGLE PHASE FEED PHASE TO PHASE...
Страница 50: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 7 FIGURE 3 5 Y THREE PHASE FEED PHASE TO NEUTRAL...