Configuration and Operation
Sageon III Power System
PM990-8800-00, Rev. 9
4-22
(Base Menu continued)
ENTER
Sets MiniCSU-3 access code address
Access Code
0000000
Modify Value up/down
ENTER to accept
ENTER
Date Format
DD/MM/YYYY
Modify Value up/down
ENTER to accept
ENTER
Date 25/12/2005
Time 01:11:11
ENTER
Alarm Report
Off
INC/DEC toggles state
ENTER to accept
ENTER
Daily Report
Off
INC/DEC toggles state
ENTER to accept
(If Daily Rep not = Off)
ENTER
Daily Rep Time
15:15
INC/DEC toggles state
ENTER to accept
ENTER
Modem
Off
INC/DEC toggles state
ENTER to accept
(If Modem not = Off)
ENTER
Country Code
61
Modify Value up/down
ENTER to accept
ENTER
External modem initialisation string
Cust Init String
None
Modify Value up/down
ENTER to accept
ENTER
Phone 1
0398887788
Modify Value up/down
ENTER to accept
ENTER
Phone 1 Cont
2323
Modify Value up/down
ENTER to accept
ENTER
Phone 2
0398887788
Modify Value up/down
ENTER to accept
ENTER
Phone 2 Cont
2323
Modify Value up/down
ENTER to accept
ENTER
Phone 3
0398887788
Modify Value up/down
ENTER to accept
ENTER
Phone 3 Cont
2323
Modify Value up/down
ENTER to accept
ENTER
Audio Alarm
Off
INC/DEC toggles state
ENTER to accept
ENTER
Circuit breaker auxiliary contact circuit input configuration
Cct Input
Not Used
INC/DEC toggles state
ENTER to accept
ENTER
Battery circuit breaker auxiliary contact circuit input configuration
Batt Switch Input
Not Used
INC/DEC toggles state
ENTER to accept
ENTER
LVDS Input
Not Used
INC/DEC toggles state
ENTER to accept
ENTER
ENTER
Auxiliary Units
Press ENTER
1-ph AC Monitor
Off
INC/DEC toggles state
ENTER to accept
(If 1-ph AC Monitor not = Off)
ENTER
1ph AC Vhi Alarm
260V
Modify Value up/down
ENTER to accept
ENTER
1ph AC Vlo Alarm
200V
Modify Value up/down
ENTER to accept
ENTER
1ph AC fhi Alarm
55.0Hz
Modify Value up/down
ENTER to accept
ENTER
1ph AC flo Alarm
45.0Hz
Modify Value up/down
ENTER to accept
ENTER
1ph AC FS Curr.
100A
Modify Value up/down
ENTER to accept
Battery low voltage disconnect switch auxiliary circuit input
configuration
ENTER selects hours,
minutes, day, month or year
INC/DEC modifies value
Содержание Sageon III
Страница 43: ...Installation Sageon III Power System PM990 8800 00 Rev 9 2 22 FIGURE 2 20 SAGEON III BOARD LOCATIONS...
Страница 46: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 3 FIGURE 3 1 SINGLE PHASE FEED PHASE TO NEUTRAL...
Страница 47: ...Commissioning Sageon III Power System PM990 8800 00 Rev 9 3 4 FIGURE 3 2 SINGLE PHASE FEED PHASE TO PHASE...
Страница 50: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 7 FIGURE 3 5 Y THREE PHASE FEED PHASE TO NEUTRAL...