Installation
Sageon III Power System
PM990-8800-00, Rev. 9
2-4
Torque Specifications
Proper plant performance requires that the hardware employed during installation be tightened securely but not over tightened. Use a
torque wrench to ensure that hardware is tightened to the specification provided in Table 2-2.
TABLE 2-2 TORQUE SPECIFICATIONS, STEEL FASTENERS
Bolt Size
Inch/Pound
s
Foot/Pound
s
Newton-
Meters
4-40
4.5
0.375
0.51
4-48
5.4
0.450
0.61
6-32
9.0
0.750
1.02
6-40
10.8
0.900
1.22
8-32
17.1
1.425
1.93
8-36
18.0
1.500
2.03
10-24
24.3
0.025
2.75
10-32
27.9
2.325
3.15
1/4-20
59.4
4.950
6.71
1/4-28
70.2
5.850
7.93
5/16-18
118.8
9.9
13.42
5/16-24
129.6
10.8
14.64
3/8-16
216.0
18.0
24.40
3/8-24
248.4
20.7
28.07
7/16-14
324.0
27.0
36.61
7/16-20
378.0
31.5
42.71
1/2-13
540.0
45.0
61.01
1/2-20
594.0
49.5
67.11
9/16-12
756.0
63.0
85.42
9/16-18
864.0
72.0
98.62
2.3 SELECTING A LOCATION
Install the Power system in a location that provides the following.
•
Access to a source of reliable, stable, electrically clean AC power
•
A dry, well ventilated room that meets the conditions stated in Section 1.2.2 Power system Environmental Specifications
•
Sufficient access for plant installation and servicing (refer to NEC and local codes)
•
Sufficient ceiling height to permit use of overhead cable trays and conduit for AC input cables and DC load supply and return
cables
•
A level, flat floor capable of supporting the weight of the Power system and accepting bolts or other user-supplied hardware to
securely anchor the plant
•
A pest and varmint free area
2.4 MOVING AND ANCHORING THE POWER SYSTEM
WARNING
Tip Over/Crush Hazard
Power system tip over can cause death or serious injury.
Keep the Power system vertical.
Power system is heavy and also top heavy. Use a forklift or other equipment to move
or transport the Power system.
Содержание Sageon III
Страница 43: ...Installation Sageon III Power System PM990 8800 00 Rev 9 2 22 FIGURE 2 20 SAGEON III BOARD LOCATIONS...
Страница 46: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 3 FIGURE 3 1 SINGLE PHASE FEED PHASE TO NEUTRAL...
Страница 47: ...Commissioning Sageon III Power System PM990 8800 00 Rev 9 3 4 FIGURE 3 2 SINGLE PHASE FEED PHASE TO PHASE...
Страница 50: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 7 FIGURE 3 5 Y THREE PHASE FEED PHASE TO NEUTRAL...